background image

1

Model

Code

Content

LT4

һ

LCD timer, 48 (W) X 48 (H) mm

Control 

output

-

time limit 2c, time limit 1c + instantaneous 1c

S

time limit 1c

Model

LT4

LT4S

Power voltage

24 - 240 V a.c. 50/60 Hz, 24 - 240 V d.c. (dual usage)

Voltage fluctuation rate

± 10 % of power voltage

Power Consumption

4 VA max. (24-240 V a.c. 50/60 Hz) 
1.6 W max. (24- 240 V d.c.)

4.5 VA max. (24-240 V a.c. 50/60 Hz) 
2 W max. (24-240 V d.c.)

Display

Wide viewing angle negative LCD display

Display mode

Addition and subtraction 

Display digits

4 digits

Character height

PV display: 14mm, SV display: 8.5mm

Return time

100 ms max.

External connection

socket 8 pin

Operating time range

0.01 sec ~ 9999 hour

External 

input

Input signal

-

START, INHIBIT, RESET 

Input 

method

-

non-voltage input, impedance during short 
circuit : 1 kΩ max.
Residual voltage during short circuit : 0.5 V 
max.
impedance during open : 100 kΩ min.

Minimum input time

-

START, INHIBIT, 

RESET min. input signal width 

1ms / 20ms selection

Operating time error

Power START : ± 0.01 % ±0.05 sec max., 

Signal START : ± 0.005 % ±0.03 sec max.

Control 

output

Operation 

mode

POND / PFKF / PFKN / PINT / 

TWON / TWOF / S-D

SOND / SFKF / SINT / SNFN / 

SNFF / SOFD / S.OND / S.FKN / 

S.INT / S.ODR

Contact 

configuration

time limit 1c

time limit 2c, instantaneous 1c 

+ time limit 1c

Contact 

capacity

250 V a.c. 5A resistive load

250 V a.c. 3A resistive load 

(N.O.:5A, N.C.:3A)

Relay life

Mechanical life : 10,000,000 times min., 

Electrical life : 100,000 times min. (250 V a.c. 5A resistive load)

Insulation resistance

100 MΩ min. (500 V d.c. mega standard, 

conductive part terminal and exposed unfilled metal)

Dielectric strength

2,000 V a.c. 60 Hz for 1 minute (conductive part terminal 

and exposed unfilled metal)

Noise immunity

± 2 kV (among operation power terminals, 

pulse width = 1 us, square-wave noise by noise simulator)

Vibration resistance

10 - 55 Hz (for 1 minute)  single amplitude 0.5 mm 

X, Y, Z each direction, 2 h

Shock resistance

300 ㎨ (30G)  X, Y, Z each direction, 3 times

Ambient temperature

-10 ~ 55 ℃ (with no icing)

Storage temperature

-25 ~ 65 ℃ (with no icing)

Ambient humidity

35 ~ 85 % R. H.

MD1101E170927

Specification

• Any use of the product other than those specified by the manufacturer may result in

personal injury or property damage.

• If there is a possibility that a malfunction or abnormality of this product may lead to a

serious accident to the system, install an appropriate protection circuit on the outside.

• Since this product is not equipped with a power switch and fuse, install them separately

on the outside (fuse rating: 250 V a.c. 0.5 A).

• Please supply the rated power voltage, in order to prevent product breakdowns or

malfunctions. 

• To prevent electric shocks and malfunctions, do not supply the power until the wiring is

completed.

• The product does not have an explosion-proof structure, so avoid using it in places with
    flammable or explosive gases.
• Never disassemble, modify, process, improve or repair this product, as it may cause
    abnormal operations, electric shocks or fires.    
• Please disassemble the product after turning OFF the power. Failure to do so may result

in electric shocks, product abnormal operations or malfunctions.

• Please use this product after installing it to a panel, because there is a risk of electric shock.

WARNING

• The input/output terminals are subject to electric shock risk. Never let the input/output

terminals come in contact with your body or conductive substances.

DANGER

• The contents of this manual may be changed without prior notification.
• Please make sure that the product specifications are the same as you ordered.
• Please make sure that there are no damages or product abnormalities occurred during shipment. 
• Please use the product in places where corrosive gases (especially harmful gases, 

ammonia, etc.) and flammable gases are not generated.

• Please use the product in places where vibrations and impacts are not applied directly.
• Please use the product in places without liquids, oils, chemicals, steam, dust, salt, iron, etc.
• Please do not wipe the product with organic solvents such as alcohol, benzene, etc.

(use neutral detergents).

• Please avoid places where large inductive interference, static electricity, magnetic noise 

are generated.

• Please avoid places with heat accumulation caused by direct sunlight, radiations, etc.
• Please use the product in places with elevation below 2000 m.
• When water enters, short circuit or fire may occur, so please inspect the product carefully.
• When there is a lot of noise from the power, we recommend to use insulation 

transformer and noise filter. Please install the noise filter to a grounded panel or
structure  etc. and make the wiring of noise filter output and product power supply
terminal as short as possible.

• Tightly twisting the power cables is effective against noise.
• Do not wire anything to unused terminals.
• Please wire correctly, after checking the polarity of the terminals.
• When you install this product to a panel, please use switches or circuit breakers

compliant with IEC60947-1 or IEC60947-3.

• Please install switches or circuit breakers at close distance for user convenience.
• We recommend regular maintenance for the continuous safe use of this product.
• Some components of this product may have a lifespan or deteriorate over time.
• The warranty period of this product, is 1 year, including its accessories, under normal

conditions of use.

• The preparation period of the contact output is required during power supply.

If used as a signal to external interlock circuit, etc. please use a delay relay together.

CAUTION

Suffix code

LCD Timer

LT4

 

series

Thank you for purchasing Hanyoung Nux products. Please read the  instruction 
manual carefully before using this product, and use the product correctly. Also, 
please keep this manual where you can view it any time.

 

Safety information

Please read the safety information carefully before the use, and use the product 
correctly.The alerts declared in the manual are classified into Danger, Warning and 
Caution according to their importance

Time range

 28, Gilpa-ro 71beon-gil, Nam-gu, Incheon, Korea
TEL : (82-32)876-4697  FAX : (82-32)876-4696  http://www.hynux.com

HANYOUNGNUX CO.,LTD

HEAD OFFICE/

FACTORY

DANGER

Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury

CAUTION

Indicates a potentially hazardous situation which, if not avoided, may result in minor iinjury or property damage

Parameter

Time range

UP

DOWN

Decimal

Sexagesimal

0.01sec ~ 9.999sec

0.01sec ~ 9.999sec

0.01sec ~ 99.99sec

0.01sec ~ 59.99sec

0.1sec ~ 999.9sec

0.1sec ~ 9m 59.9sec

1sec ~ 9999sec

1sec ~ 59min 59sec

0.1min ~ 999.9min

0.1min ~ 9hour 59.9min

1min ~ 9999min

1min ~ 99hour 59min

0.1hour ~ 999.9hour

0.1hour ~ 999.9hour

 1hour ~ 9999hour

1hour ~ 9999hour

 INSTRUCTION MANUAL

TD

Summary of Contents for LT4 Series

Page 1: ...ontact with your body or conductive substances DANGER The contents of this manual may be changed without prior notification Please make sure that the product specifications are the same as you ordered...

Page 2: ...N TWON TWOF S D SFKF SNFN SNFF S FKN operation modes MODE KEY enters and quits function setting mode automaticaly saves function set value during termination SHIFT KEY enters set value change mode and...

Page 3: ...play when START signal is applied OFF timing starts START signal holds ON status when displayed time reaches Toff set time output turns ON after displayed time initialization ON timing starts when dis...

Page 4: ...changing the set value of SV display press to save the changed set value and return to operation mode If ON time set value and OFF time set value are 0 even if you press it does not return to operati...

Page 5: ...s configured as time limit 2c in operation mode TWON TWOF S D it is automatically fixed to time limit 2c Minimum input time selection displayed only on LT4S models selects START INHIBIT RESET minimum...

Page 6: ...e POWER RESET OUT1 OUT2 1 When power is applied OUT1 and OUT2 turn ON and timing starts When CONT is set as 1C 1C in function setting mode OUT1 turns ON when power is applied instantaneous output When...

Page 7: ...elled during ON time timing OUT turns ON time value is initialized Toff time is displayed 6 If START signal is applied suring OFF time timing OUT turns OFF time value is initialized Ton time is displa...

Reviews: