background image

ELECTRICAL

 INSTALLATION

CorrECt wIrIng sChEmE

To minimize the risk of an indirect lightning strike, avoid forming closed loops when designing the system. Check 
that wiring is correct before starting the generator. If the measured open circuit voltage (V

oc

) and short-circuit 

current (I

sc

) differ from the specifications, there may be a wiring fault.

soLar modULE PLUg ConnECtors

All solar modules are equipped with solar cables with 4-6mm² serving a temperature range from -40°C to 90°C. 
The connectors have specified polarities; they are marked with ´+´ and ´-´ signs. Make sure that the connection is 
safe and tight. Connectors should only be used to connect the circuit, but never used to turn the circuit on or off. 
Connectors must not be exposed to direct rain or laid in water drains.

UsE of ProPEr ComPonEnts

Use cable extensions and plugs that are designed for outdoor applications. Ensure that they are in good electrical 
and mechanical condition. Only cables with one conductor are to be used. Ensure that all materials meet the 
requirements of the systems` maximum voltage, current, moisture, and temperature when they are exposed to 
sunlight. Under normal conditions, a photovoltaic module is likely to produce more current and/or voltage than 
that reported under Standard Test Conditions. Accordingly, the values of I

sc

 and V

oc

 marked on the module should 

be multiplied by a factor of 1.25 when selecting electrical components voltage ratings, conductor capacities, fuse 
type, and type of control components connected to the PV output.

 

The maximum series fuse rating is:

 

  10A for modules with Hanwha Solar 125x125mm cells

 

  15A for modules with Hanwha Solar 156x156mm cells

The maximum reverse current is known as series fuse rating multiplied by a factor of 1.35. Each module (or series 
string of modules so connected) shall be provided with the maximum series fuse as specified.
For USA:
Refer to Section 690-8 of the U.S. National Electrical Code for an additional multiplying factor of 1.25 which may 
be applicable.

ByPass dIodEs

When modules in series are partially shaded, it may cause reverse voltage across cells or modules, this may cause 
undesirable heating to occur. The use of a diode to bypass the shaded area can minimize both heating and array 
current reduction. All Hanwha Solar modules are equipped with factory installed bypass diodes. The factory 
installed diodes provide proper circuit protection for the system.

othErs

During installation, be sure to tie the cable from the junction box to the mounting substructure with nylon line, etc. 
to avoid direct contact of the cable with the back surface of the module.

8

Summary of Contents for HSL60P6-PB-0-xxxT Series

Page 1: ...Installation Guide HSL Poly Series...

Page 2: ...le is used only in applications for which it is suitable see Mounting Instructions All work on a PV system installation setup maintenance must be carried out only by appropriately qualified and author...

Page 3: ...s should be read and understood prior to installing the modules The installer should conform to all the safety precautions in this guide when installing the modules Local standards and regulations sho...

Page 4: ...odule Very hot module s can reduce power output performance Ensure the module has good ventilation conditions to prevent overheating Site specific environment loads such as wind and snow should be tak...

Page 5: ...ouch each other at any operating temperature to avoid unfavorable forces Keep in mind different modules mounting systems and building materials do have different thermal expansion coefficients Hanwha...

Page 6: ...les Moun ng holes Moun ng holes Moun ng holes 140mm 250mm 140mm 250mm Moun ng holes Moun ng holes Moun ng holes Moun ng holes Clamping Area 200mm Clamping Area 200mm MOUNTING INSTRUCTIONS Clamping Are...

Page 7: ...Moun ng holes Moun ng holes Moun ng holes Moun ng holes 200mm 300mm 200mm 300mm Moun ng holes Moun ng holes Moun ng holes Moun ng holes Clamping Area 550mm Clamping Area 550mm Clamping Area 150mm 400m...

Page 8: ...current and or voltage than that reported under Standard Test Conditions Accordingly the values of Isc and Voc marked on the module should be multiplied by a factor of 1 25 when selecting electrical c...

Page 9: ...ed washer Module frame Lay in lug Flat washer Machine screw In case grounding is required Hanwha Solar recommends using the follow components or equivalents IEC EN61730 INFORMATION Hanwha Solar module...

Page 10: ...wiring with wet plugs and sockets Make sure to use proper safety equipment insulating tools and gloves etc when wiring Make sure that the connection is made when the circuit is cut off Do not disconne...

Page 11: ...age Location with extreme air pollution chemical vapors acid rain and or soot etc Location with extreme hail and or snow Location with potential extreme salt damage MAINTENANCE AND CARE Dirt on the su...

Page 12: ...Co Ltd No 888 Linyang Road Qidong Jiangsu Province 226200 China Phone 86 513 8360 6222 Fax 86 513 8360 6278 Hanwha SolarOne GmbH Headquarter Sales EA Germany Oskar Messter Stra e 13 85737 Ismaning Ger...

Reviews: