5
VPIFb
FEB 2008
MODEL: VPIF WIRING
Figure D
Page 1: ...rs in any direction from the valve VPIEC Extension Cables are available where more length is required KEY FEATURES Provides local indication of the SMV valve position Facilitates SMV recalibration Ver...
Page 2: ...onnect cables If the VPIF is mounted on the valve the 8 cable and the 2 cable with pigtails can be connected together for a total of 10 to the customer supplied junction box If the VPIF is mounted sep...
Page 3: ...the valve from open and closed 1 Secure the refrigeration system to allow the valve to open and close fully without causing undesirable system problems to occur 2 Mount and secure the motor on the se...
Page 4: ...with valve position display No jumper connection standard Place jumper on one post for future use CHANGING THE FEEDBACK MODE Tools required 2mm hex key Phillips head screwdriver and needle nose plier...
Page 5: ...5 VPIFb FEB 2008 MODEL VPIF WIRING Figure D...
Page 6: ...each foot to aid in correct wire connections To a d d a q u i c k d i s c o n n e c t c o n n e c t o r on Sealed Motor Valve power head use Kit number 75 1211 which includes a field solder male cable...
Page 7: ...ate SMV VPIF indicates open greater than 100 0 Recalibrate SMV 3 is within tolerance VPIF indicates open less than 0 0 Recalibrate SMV 3 is within tolerance VPIF LED Display value is greater than or l...
Page 8: ...cted life of seven to ten years is typical This should be understood as only a suggested replacement time period Actual ambient conditions contaminants quality of electric current voltage etc may nece...