Hansen VPIF Specifications, Applications, Service Instructions & Parts Download Page 2

2

VPIFb
FEB 2008

MATERIAL SPECIFICATIONS

Electrical

 

Readout: LED, 0.0 –100.0% 

Signal Output to SMV:

Automatic: Pass through

Open: 20 mA
Close: 4 mA

Power Supply: 24 VAC

VPIF Power Consumption: 3.6 VA

Housing: Water tight, NEMA 4X (IP65)

Ambient Temperature: -20ºF to +125ºF 

(-30ºC to +50ºC)

Cables: 7 wires - marked ever y foot 1 thru 6 with 

the 7

th

  yellow/green (ear th ground), 18 AWG 

wire cable with waterproof, quick disconnect 
connectors.

INSTALLATION

The VPIF is shipped in a box with the Sealed Motor 

Valve and comes factory calibrated and tested; ready 

to use. The VPIF can be mounted on the valve or to 
any flat sur face. The clear cover must be removed to 
access the four plate bolts. These same four holes 
are used to mount the VPIF on a flat surface.  Replace 
the clear cover when complete.  

WIRING

The VPIF is provided with waterproof quick disconnect 

cables.  If the VPIF is mounted on the valve, the 8’ 
cable and the 2’ cable with pigtails can be connected 
together for a total of 10’ to the customer supplied 

junction box.

If the VPIF is mounted separately from the valve, the 
8’ cable is connected to the SMV power head.  The 
VPIF can be mounted up to 10’ away from the valve.  
For greater distances, additional 8’ VPIEC Extension 
Cables can be connected.  

Refer to Figure D

.

Proper wiring is ver y impor tant to the operation of 
the Sealed Motor Valve.  Correct wire size for 24VAC 
power to the power head must be selected for the 
distance and number of valves.  

See 24 VAC Power 

Wiring Table 1

.

TABLE 1: 24 VAC POWER WIRING

24 VAC POWER 

WIRING

( WIRES NO. 1 AND 2)

(90 VA PER VALVE 

REQUIRED)

AWG WIRE GAUGE (mm2)

NUMBER OF VALVES POWERED

CABLE LENGTH 

ft(m)

1

2

3

4

50 (15)

18 (1,0)

16 (1,5)

14 (2,5)

12 (4,0)

100 (30)

16 (1,5)

12 (4,0)

10 (6,0)

10 (6,0)

150 (46)

12 (2,5)

10 (6,0)

8 (10,0)

8 (10,0)

200 (61)

12 (4,0)

10 (6,0)

8 (10,0)

300 (91)

10 (6,0)

8 (10,0)

TYPICAL INSTALLATION

Figure A

VPIF MOUNTED ON VALVE

VPIF MOUNTED REMOTELY

Summary of Contents for VPIF

Page 1: ...rs in any direction from the valve VPIEC Extension Cables are available where more length is required KEY FEATURES Provides local indication of the SMV valve position Facilitates SMV recalibration Ver...

Page 2: ...onnect cables If the VPIF is mounted on the valve the 8 cable and the 2 cable with pigtails can be connected together for a total of 10 to the customer supplied junction box If the VPIF is mounted sep...

Page 3: ...the valve from open and closed 1 Secure the refrigeration system to allow the valve to open and close fully without causing undesirable system problems to occur 2 Mount and secure the motor on the se...

Page 4: ...with valve position display No jumper connection standard Place jumper on one post for future use CHANGING THE FEEDBACK MODE Tools required 2mm hex key Phillips head screwdriver and needle nose plier...

Page 5: ...5 VPIFb FEB 2008 MODEL VPIF WIRING Figure D...

Page 6: ...each foot to aid in correct wire connections To a d d a q u i c k d i s c o n n e c t c o n n e c t o r on Sealed Motor Valve power head use Kit number 75 1211 which includes a field solder male cable...

Page 7: ...ate SMV VPIF indicates open greater than 100 0 Recalibrate SMV 3 is within tolerance VPIF indicates open less than 0 0 Recalibrate SMV 3 is within tolerance VPIF LED Display value is greater than or l...

Page 8: ...cted life of seven to ten years is typical This should be understood as only a suggested replacement time period Actual ambient conditions contaminants quality of electric current voltage etc may nece...