Start-up
Page GB-22
Space requirement (when the door is open and when the door is closed)
637
11
3
5
840
e
adhesive strips, protective film and foam
padding from the inside, outside and back
of the appliance.
2. Select a suitable location and adhere to
the stipulated minimum distances and
ambient temperatures (see the next
page).
– To prevent the formation of a flammable
gas-air mixture in the event of a leakage
in the refrigeration circuit, the installation
space must have a minimum size of 1 m3
per 8 g of refrigerant in compliance with the
EN 378 standard.
The amount of refrigerant contained in your
appliance can be found on the data sheet
page GB-31.
The minimum size of the area in which your
appliance is set up is as follows:
Model A1
Model A2
Model A3
5.75 m³
5.75 m³
7.2 m³
– Suitable locations are dry, well-ventilated
areas that are cool if possible.