peratures recorded during site tests

Application

Mixedwater

temperature

Shower 

43°C

Washbasin 

43°C 

Bath (44°C fill) 

46°C

Bath (46°C fill) 

48°C

The mixed water temperature at terminal fitting should 
never exceed 46ºC.

If  there  is  a  residual  flow  during  the  commissioning  or 
the annual verification (cold water supply isolation test), 
then this is acceptable providing the temperature of the 
water seeping from the valve is no more than 2°C above 
the designated maximum mixed water outlet temperature 
setting of the valve.
Temperature readings should be taken at the normal flow 
rate after allowing for the system to stabilise. 
The sensing part of the thermometer probe must be fully 
submerged in the water that is to be tested.
Any  TMV  that  has  been  adjusted  or  serviced  must  be 
re-commissioned  and  re-tested  in  accordance  with  the 
manufacturers' instructions.

Commissioningandin-servicetests

Commissioning

Purpose

Since the installed supply conditions are likely to be different 
from those applied in the laboratory tests it is appropriate, 
at commissioning, to carry out some simple checks and tests 
on each mixing valve to provide a performance reference 
point for future in-service tests.

Procedure

1.

  Check that:

a)  the  designation  of  the  thermostatic  mixing  valve 

matches the intended application

b)  the supply pressures are within the range of ope-

rating pressures for the designation of the valve

c)  the supply temperatures are within the range per-

mitted for the valve and by guidance information 
on the prevention of legionella etc.

2.

  Adjust the temperature of the mixed water in accor-

dance with the manufacturer’s instructions (page 10) 
and the requirement of the application and then carry 
out the following sequence:

a)  record the temperature of the hot and cold water 

supplies

b)  record the temperature of the mixed water at the 

largest draw-off flow rate

c)  record  the  temperature  of  the  mixed  water  at 

a  smaller  draw-off  flow  rate,  which  shall  be 
measured

d)  isolate the cold water supply to the mixing valve 

and monitor the mixed water temperature

e)  record the maximum temperature achieved as a 

result of (d) and the final stabilised temperature

 

NOTE:

 The final stabilised mixed water temperature 

should not exceed the values in Table A.

f)  record the equipment, thermometer etc. used for 

the measurements

 

TableA:Guidetomaximumstabilisedtem-

Summary of Contents for Ecomax 13354000

Page 1: ...DE Gebrauchsanleitung Montageanleitung 2 EN Instructions for use assembly instructions 4 Ecomax 13356000 Ecomax 13354000...

Page 2: ...optional erh ltliche Drossel Artikelnummer 97510000 in den Kaltwasser zulauf eingesetzt werden Technische Daten Betriebsdruck max 1 MPa Empfohlener Betriebsdruck 0 1 0 5 MPa Pr fdruck 1 6 MPa 1 MPa 1...

Page 3: ...ckflussverhinderer reinigen ggf austauschen Auslauftemperatur stimmt nicht mit der eingestellten Temperatur berein Thermostat wurde nicht justiert Thermostat justieren Zu niedrige Warmwassertemperatu...

Page 4: ...install a water limiter to the cold supply ordered separately article number 97510000 Technical Data Operating pressure max 1 MPa Recommended operating pressure 0 1 0 5 MPa Test pressure 1 6 MPa 1 MP...

Page 5: ...ty or leaking Clean backflow preventers ex change if necessary Spout temperature does not cor respond with temperature set Thermostat has not been adjusted Adjust thermostat Hot water temperature too...

Page 6: ...6 X X 36 mm X 36 1 3b 2 3a 1 2 1 2 Silicone max 39 mm max 5 mm 1 2 5 4 36 mm SW 24 mm...

Page 7: ...7 6 7 8 SW 30 mm 17 Nm...

Page 8: ...8 Ecomax 13354000 Ecomax 13356000 R 1 2 R 1 2 P IX DVGW SVGW ACS WRAS ETA KIWA 13354000 X 13356000 X...

Page 9: ...9 SW 3 mm SW 3 mm 2 Nm 1 3 4 2 5 6...

Page 10: ...10 z B 42 C for example 42 C 4 3 1 2 5 1 2 S W 3 m m S W 3 m m 2 N m...

Page 11: ...11 5 6 SW 30 mm SW 30 mm 17 Nm SW 12 mm SW 12 mm 20 Nm 4 1 1 2 2 3 1 2 SW 24 mm 1 2 SW 24 mm 20 Nm 1 2...

Page 12: ...12 1 2 3...

Page 13: ...13 schlie en close 90 ffnen open 1 2 kalt cold 40 C warm hot 90 1 2...

Page 14: ...00 97211000 25x2 97164000 95041000 96633000 98147000 26x2 34x2 38x2 5 A 96264000 97162000 92929000 96264000 Ecomax 13356000 94140000 96429000 98163000 15x2 96157000 96467000 96922000 97220000 96644000...

Page 15: ...terproofed wall surface usually tiles If you are using power tools e g to drill holes wear sa fety glasses and always disconnect tools from the power supply after use Do not operate the shower unit if...

Page 16: ...herent in thermostatic mixing valves and temperature losses in metal baths It is not a safe bathing temperature for adults or children The British Burns Association recommends 37 to 37 5 C as Installa...

Page 17: ...17 KEY Isolating valve Reducing valve Mixer Valve Pump Gas Combination Boiler multi point Unvented System pressure balanced Pumped System...

Page 18: ...me simple checks and tests on each mixing valve to provide a performance reference point for future in service tests Procedure 1 Check that a the designation of the thermostatic mixing valve matches t...

Page 19: ...ce of any other instruction or guidance on the means of determining the appropriate frequency of in service testing the following procedure may be used 1 6 to 8 weeks after commissioning carry out the...

Page 20: ...xer is fitted with check valves page 14 pos 96644000 and filters page 14 pos A and 96922000 If the water flow drops the filters need to be cleaned For that purpose please follow the steps 1 8 on page...

Reviews: