Table A: Guide to maximum stabilised tem-
peratures recorded during site tests
Application Mixed
water
temperature
Shower 43°C
Washbasin 43°C
Bath (44°C fill)
46°C
Bath (46°C fill)
48°C
The mixed water temperature at terminal fitting should
never exceed 46ºC.
If there is a residual flow during the commissioning or
the annual verification (cold water supply isolation test),
then this is acceptable providing the temperature of the
water seeping from the valve is no more than 2°C above
the designated maximum mixed water outlet temperature
setting of the valve.
Temperature readings should be taken at the normal flow
rate after allowing for the system to stabilise.
The sensing part of the thermometer probe must be fully
submerged in the water that is to be tested.
Any TMV that has been adjusted or serviced must be
re-commissioned and re-tested in accordance with the
manufacturers' instructions.
Commissioning and in-service
tests
Commissioning
Purpose
Since the installed supply conditions are likely to be differ-
ent from those applied in the laboratory tests it is appropri-
ate, at commissioning, to carry out some simple checks
and tests on each mixing valve to provide a performance
reference point for future in-service tests.
Procedure
1.
Check that:
a) the designation of the thermostatic mixing valve
matches the intended application
b) the supply pressures are within the range of op-
erating pressures for the designation of the valve
c) the supply temperatures are within the range per-
mitted for the valve and by guidance information
on the prevention of legionella etc.
2.
Adjust the temperature of the mixed water in accord-
ance with the manufacturer’s instructions (page 62)
and the requirement of the application and then carry
out the following sequence:
a) record the temperature of the hot and cold water
supplies
b) record the temperature of the mixed water at the
largest draw-off flow rate
c) record the temperature of the mixed water at a
smaller draw-off flow rate, which shall be meas-
ured
d) isolate the cold water supply to the mixing valve
and monitor the mixed water temperature
e) record the maximum temperature achieved as a
result of (d) and the final stabilised temperature
NOTE: The final stabilised mixed water temperature
should not exceed the values in Table A.
f) record the equipment, thermometer etc. used for
the measurements
Summary of Contents for AXOR Starck 10754180
Page 31: ...31 P IX DVGW SVGW ACS WRAS ETA KIWA 10754180 X X X 10754180...
Page 32: ...32 10971180 10754180 DN 20 DN 20 DN 15 10972000 10755000 28494000 27413000...
Page 34: ...34 DN 20 DN 20 DN 15 10971180 10754180 10650180 10972000 10755000 10651000 28494000 27413000...
Page 46: ...46 Nr 10476220 Armaturenfett Grease Nr 10476220 Armaturenfett Grease 1 2 2a 1 2 2b 4 G G 3 1...
Page 58: ...58...
Page 59: ...59...
Page 85: ...60 MTC 42 C 65 C 180 180 25...
Page 87: ...60 42 65 180 27...
Page 103: ...60 42 C 65 C 180 180 43...
Page 115: ...60 42 C 65 C 180 180 55...
Page 118: ...60 42 65 180 180 58...
Page 119: ...66 67 67 68 64 DIN EN 1717 DIN 1988 62 42 62 1 0 5 0 1 1 6 PSI 147 10 1 80 C 65 C 4 70 C 59 76...
Page 120: ...60 1 2 mm X 1 2 3 4 6 5 10754180 SW 24 mm 15 Nm SW 27 mm SW 17 mm 1 2...
Page 121: ...61 1 2 SW 3 mm 4 Nm 0 1 Nm X 11 11 12 8 7 10 9 1 2 SW 2 mm 4 Nm 3...
Page 122: ...62 1 2 1 3 2 SW 2 mm 4 Nm SW 2 mm SW 2 mm 2 2 2 2 1 1 1 1 SW 3 mm...
Page 123: ...63 4 3 6 5 7 8 2 2 2 2 1 1 1 1 SW 3 mm 4 Nm SW 2 mm 4 Nm...
Page 124: ...64 2 3 4 1 6 5 SW 24 mm SW 2 mm SW 3 mm 1 2 3...
Page 125: ...65 8 9 10 7 11 SW 2 mm 4 Nm SW 3 mm 4 Nm SW 24 mm 15 Nm 1 2 3...
Page 126: ...66 40 C 1 2...
Page 127: ...67 Starck 10755000 Citterio E 36702000 120 120 12 57 85 49...
Page 135: ...75...
Page 167: ...31 10921180 P IX DVGW SVGW ACS WRAS ETA KIWA 10921180 X X...
Page 168: ...32 10971180 10754180 10650180 DN 15 DN 15 DN 15 10972000 10755000 10925000 10921180 10651000...
Page 180: ...44 1 3 SW 4 mm SW 13 mm 2...
Page 182: ...46 5...
Page 191: ...55...
Page 201: ...16 10 17 20 9...
Page 202: ...10 Montage Starck 10932000 2 3 4 5 6 SW 27 mm 2 Nm 1a 1b 2 3 1...
Page 203: ...11 Starck 10932000 7 8 0 8 Nm 9...
Page 205: ...13 Starck 10972000 Starck Organic 12731000 12771000 8a 7 8b 9 0 8 Nm 0 8 Nm...
Page 206: ...14 2 3 4 1 2 3 4 1 2 3 4 5 1a 1b Citterio E 36771000 36772000 2 3 10 mm 10 mm 1...