HANLI HL-1000 Series User Manual Download Page 19

User's Manual of Fiber Laser Chiller

19

7.3 Power on display

When the split controller unit is powered up, the display shows the software version information

(Fxx/v100 /A00) and after approx. 7seconds it enters the temperature display.

When the LCD controller is in the main interface, press

for 3 seconds to switch on the

machine, the status bar of the main interface will show "Running" after switching on the machine;

press

again for 3 seconds to switch off the machine, the main interface will show "Stop" after

switching off the machine.

7.4 Temperature display

7.4.1 Split controller temperature display

The display shows the measured water temperature (L.xx.x) for low temperature water by

default.

When the temperature is displayed, press <▼> to switch between the display of the measured

water temperature (H.xx.x), the set water temperature (S.xx.x) and the set temperature difference

(d.xx.x) for normal water, and return automatically after 30 seconds without switching.

Back to the low temperature water interface.

[Note]: L./H./S./d. is the temperature code, xx.x is the temperature value.

7.4.2 Integrated controller temperature display

The PV zone shows "actual temperature" and the SV zone shows "set temperature".

7.5

Parameter setting

7.5.1 Parameter setting of the split controller

In the non-fault state, press <▲>+<▼> at the same time to enter the low temperature water

setting temperature setting interface, the setting temperature xx.x is displayed flashing, at this time
the setting temperature can be modified by pressing <▲> or <▼> keys.

If no key operation is performed for 5 seconds after setting, the system will automatically save

the set value and exit the setting state.

Normal water set temperature = [Low temperature water set temperature] + [F01 Normal water

temperature difference], to change this ,you need to modify the factory parameter [F01 Normal
water temperature difference].

In the temperature display, press the <▲>+<▼> keys simultaneously for 5s to enter the

manufacturer's parameter setting status, the factory set parameters are generally not adjusted, if you
need to adjust, please seek the chiller manufacturer's agreement.

During the selection of the manufacturer's parameters, press <▼> to select the parameter item,

press <▲> to enter the parameter setting and exit the manufacturer's parameter setting after 15s of
operation without pressing the key (the display shows the parameter item).

For parameter setting, the parameter value can be modified by <▲> or <▼>, after 5S of

keyless operation or by pressing <▲>+< ▼> to return to the parameter selection and save (the
display flashes to show the parameter value).

Summary of Contents for HL-1000 Series

Page 1: ...0 2000 3000 Series SCL 1500 2000 3000 Series SCHYTJ 1500 2000 3000 Series SY 1500 2000 Series User s Manual of Fiber Laser Chiller WUHAN HANLI REFRIGERATION TECHNOLOGY CO LTD Add No 1 Second Road XinF...

Page 2: ...6 4 1 Add water 15 6 4 2 Exhaust and drainage 15 6 5 Warm Tips 16 7 Product use 16 7 1 Inspection before commissioning 16 7 2 Introduction to controller panel 16 7 2 1 Introduction to Hanli split con...

Page 3: ...ne maintenance 22 9 Fault analysis and troubleshooting 23 10 Circuit diagram 25 11 Transportation and storage 27 11 1 Transport requirements 27 11 2 Storage requirements 27 12 Other instructions 27 12...

Page 4: ...f product information and product improvements are the final interpretation of the company without prior notice and the updated content will be compiled into the reprinted manual If you have any quest...

Page 5: ...ented It must be cut off for 3 minutes before it can work Scrap Must be implemented When the equipment has reached its service life and needs to be scrapped it must be disposed of with industrial garb...

Page 6: ...ge occurs please be sure to get some air and ventilation Otherwise a large amount of refrigerant filled with closed space will produce anesthesia to the human body and cause asphyxiation risk b Avoid...

Page 7: ...e air filter at least once a week If the air filter is obstructed the refrigeration capacity will be reduced the power consumption will increase and even the alarm will not work properly Keep surface...

Page 8: ...ture and high pressure gas and discharges it to the condenser to condense and release heat into a high pressure liquid The low temperature and low pressure super cooled liquid is vaporized by the evap...

Page 9: ...mbient temperature a Operating range of Pure Softened Water Ambient temperature b Operating range of anti freeze water FIG 2 Operation range of equipment Note The above operating range is obtained in...

Page 10: ...re equipped with water filters and double temperature and two channels of water supply For example SCH 1500 represents a handheld welding chiller with a matching laser power of 1500W which is equipped...

Page 11: ...SCH 1500 220V 50Hz 2 1 R32 0 27 20 5 2 41 760 485 430 13 15 SCH 2000 220V 50Hz 2 5 R32 0 36 27 5 2 43 760 485 430 13 16 SCH 3000 220V 50Hz 3 9 R32 0 53 51 2 60 850 485 577 13 17 SCL 1500 220V 50Hz 2...

Page 12: ...wheels shall be locked for equipment with caster No shielding shall be allowed in the air inlet within the range of 1 5m and the air outlet within the range of 2 0m so as not to affect the heat dissi...

Page 13: ...ser Chiller 13 FIG 3 Requirements for equipment installation form FIG 4 Equipment installation space requirements FIG 5 Environmental requirements for equipment installation Air suction Air suction Ex...

Page 14: ...p supply pressure Fig 6 Connection diagram of chiller and laser 6 3 Circuit connection 1 Please refer to the wiring label of the chiller when wiring 2 Recommended reference standard for power cord dia...

Page 15: ...ischarge air until water flows out and then tighten the air exhaust screw plug see Figure 8 in which only the exhaust positions of vertical pump and horizontal pump are shown According to customer req...

Page 16: ...vel is in the standard zone Verify that the power supply form matches the product nameplate the 380V power line is three phase and five wire and that the 220V power supply The line is a single phase t...

Page 17: ...sor operating flashing cooling demand Off compressor off Low temperature water heating Heating1 Illuminated low temperature water heating active extinguished low temperature water heating off Ambient...

Page 18: ...eating off Switching to the low temperature water interface indicates low temperature water heating switching to the ambient water interface indicates ambient water heating Solenoid valves Valve Does...

Page 19: ...et temperature 7 5 Parameter setting 7 5 1 Parameter setting of the split controller In the non fault state press at the same time to enter the low temperature water setting temperature setting interf...

Page 20: ...nquiry Reset Fault When a fault occurs an alarm appears in the main interface and the fault is queried and reset as follows 8 Maintenance The equipment must be stopped and cut off after 3 minutes for...

Page 21: ...and the freezing point prevented is equal to the ambient temperature at which the equipment is located minus approximately 5 C When the average daily temperature is above 5 C replace the water contai...

Page 22: ...edium in 15 20 days the cooling medium must be pure distilled or high purity water Checking water connections for looseness and pump leaks Inspection of the water tank and cleaning of the dirt deposit...

Page 23: ...C Condensing fan not running D Too much dust in the filter E Damaged pressure switch Stop the compressor not the pump A Clear the surrounding clutter B Checking for leaks C Check the fan D Cleaning th...

Page 24: ...or adhesion E12 Room temperature water Flow alarms A Clogged normal temperature water line B reversed inlet and outlet connections C Leakage in ambient water line D Damaged flow switch Stop electric h...

Page 25: ...ns Automatic Water flow switch Alarm Alarm power failure heating Automatic Water level switch alarm Power up detection Alarm power failure heating Automatic Water level switch Alarm Power up detection...

Page 26: ...troller Passive output signal Normal temperature water flow switch Low temperature water Normal temperature water alarm pump By pass valve compressor Low temperature water heating Normal temperature w...

Page 27: ...r handling do not bump or tilt excessively not more than 45 avoid bumping hitting and overturning 2 When moving the equipment use the proper tools such as a forklift or overhead crane and do not carry...

Page 28: ...quality problems arising from manufacturing the company provides free repair and replacement parts The warranty period expires lifetime paid maintenance 12 1 2 Non warranty range of cases Not in accor...

Reviews: