1.0 INSTALLATION
1.1 Operating conditions
Maximum operating pressure: 250 psig, 17.6 kgf/cm
2
,
17.2 bar
Maximum compressed air temperature: 180
°
F, 82
°
C
Minimum/maximum ambient temperature: 10/130
°
F,
-12/54
°
C
1.2 Mounting
A.
Changing orientation on units with Monitor
installed
1.
Remove Monitor mounting screw.
2.
Lift Monitor and turn 180
°
.
Note: Make certain that connector to mounting block is
not disconnected.
3.
Reinstall Monitor to mounting block with mounting
screw.
B.
Retro-fitting bowl/head type housings
Make certain filter is depressurized before disassembly.
1.
Remove existing differential pressure devices or port
plugs if installed.
2.
Install mounting block on filter head using o-rings,
gaskets and transmission bolts supplied with Monitor.
NOTE: Torque bolts to 30 inch-pounds (3.4 N-m). Do not
over tighten.
IMPORTANT: Mount block so that raised rectangle is next to
the INLET (high pressure or upstream) side of filter.
Note: Enlarge opening in cap if necessary. A pattern for a
larger cutout is located on underside of cap.
3.
Connect lead from Monitor to prongs in mounting
block.
IMPORTANT: Position connector so that legs on connector
are on same side as raised rectangle.
4.
Mount Monitor on mounting block using mounting
screw provided.
NOTE: Monitor may be rotated 180
°
so that it faces forward
with filter flowing from left-to-right or right-to-left.
C.
Pressure vessel type housings
Make certain filter is depressurized before disassembly.
1.
If mounting hardware has not been previously
installed, remove inlet/outlet port plugs and install
fittings, tubing, couplings, and brackets using parts
from Mounting Kit.
2.
Connect mounting block to couplings using o-rings
and transmission bolts supplied with Monitor.
NOTE: Torque bolts to 30 inch-pounds (3.4 N-m). Do not
over tighten.
IMPORTANT: Mount block so that raised rectangle is next to
the INLET (high pressure or upstream side) connection.
3.
Connect lead from filter monitor to prongs in
mounting block.
IMPORTANT: Connect so that legs on connector are on same
side as raised rectangle.
4.
Mount Monitor on mounting block using mounting
screw provided.
2.0 OPERATION
2.1 Display Legend
LED DISPLAY
1. Unit of measure selection - pressure - pounds per
square inch.
2. Unit of measure selection - pressure - kilograms per
square centimeter.
3. Unit of measure selection - pressure - bar.
MONITOR
OPTIONAL
FILTER
BRACKET
LEAD
CAP
LEAD
MOUNT WITH LEGS FACING
RAISED RECTANGLE
MOUNT WITH
RAISED RECTANGLE
ON INLET SIDE
IN
OUT
O-RINGS
MOUNTING
BLOCK
TRANSMISSON
BOLTS
ENLARGE OPENING
IF NECESSARY
MOUNTING SCREW
LEG
LEG
GASKETS
LEAD
MOUNT WITH LEGS FACING
RAISED RECTANGLE
MOUNT WITH
RAISED RECTANGLE
ON INLET SIDE
LEG
MOUNT TO VESSEL
AS SHOWN
OR REMOTELY TO WALL.
IN
OUT
SHIFT LEFT
BUTTON
SHIFT RIGHT
BUTTON
SCROLL
BUTTON
ENTER
BUTTON
OPERATOR
ALERT LIGHT
(RED LED)
LIQUID
CRYSTAL
DISPLAY
1
2
3
4
5
6
7
9
10
11
12
13
14
15
16
17
8
2