Flood sensor can send BASIC SET command to nodes associated with group 2.
0
– Disable.
1
– Enable.
Default setting:
0
Parameter size:
1 [byte]
Parameter No.15 Value of the BASIC SET
Flood sensor can reverse its value of BASIC SET when flooding is triggered.
0
–Send BASIC SET VALUE = 255 to nodes associated with group 2 when flooding alarm is
triggered.
Send BASIC SET VALUE = 0 to nodes associated with group 2 when flooding alarm is canceled.
1
–Send BASIC SET VALUE = 0 to nodes associated with group 2 when flooding alarm is triggered.
Send BASIC SET VALUE = 255 to nodes associated with group 2 when flooding alarm is
canceled.
Default setting:
0
Parameter size:
1[byte]
Parameter No.17 Set resend flooding alarm interval(Minute)
Available settings:
1-240
Default setting
: 5
Parameter size
: 1[byte]
Parameter No.19 Temperature report time
(
minute
)
Available settings:
30-240
Default setting:
240
Parameter size:
1[byte]
Parameter No.20 Set the high temperature alarm trigger value
the precision of the temperature value is 1.
Available settings(US):
-670 - 2570
(
-67 – 257°F
)
Available settings(Other):
-550 - 1250
(
-55 – 125°C
)
Default setting (US):
1040 (104°F)
Default setting (Other):
400(40°C)
Parameter size:
2[byte]
Parameter No.22 Set the low temperature alarm trigger value
the precision of the temperature value is 1.