Installation Instructions 

Page 4 

 

Step 1

 

Once you are satisfied that the sub-floor is suitable (see pre-
installation notes page 3), lay out the insulation underlay to 
cover the entire floor area, except for the 50mm gap. The 
foam underlay sheets should be laid with staggered joints 
Fig.4.  
If laying a double layer (recommended in conservatories & 
other areas with a high heat loss) the second layer should 
be laid at right angles to the first. 

 

Notes: 

 
The foam underlay should be cut with a Stanley knife or similar. 

Step 2

 

Leave a gap of approximately 50mm at one edge of the room along where the cold cables are to be run, so as to allow 
them to sit flush under the floor covering when it is laid. For systems of more than 8 elements a gap wider than 50mm may 
be required. 
 
Using a length of 50mm wide double sided tape on the sub floor within the gap that has been made in the underlay, can 
be used to hold the cold cables in place.

 

Step 3

 

If you wish, you can join the sheets of underlay together to 
prevent them from moving apart.  This can be done by 
taping the edges of adjoining sheets together with a self 
adhesive cloth tape (Duct Tape) Fig. 5

 

Fig. 4 

Fig. 5 

Insulation Underlay - Installation 

Summary of Contents for Carbon Film

Page 1: ...Page 3 Pre Installation Electrical Provision Page 4 Insulation Underlay Installation Page 5 Carbon Film Installation Under Wood Laminate Flooring Page 8 Notes Trouble shooting Carbon Film Installation...

Page 2: ...ue to their moisture content solid and kiln dried wood floor coverings should be laid but not fixed to allow acclimatisa tion with the heating system energised before final fixing Allowances should be...

Page 3: ...e heating is installed Make the electrical provision as per the diagram Fig 3 The circuit must incorporate a 30mA RCD protection For installations below 13Amp A fused spur or combined spur RCD is reco...

Page 4: ...anley knife or similar Step 2 Leave a gap of approximately 50mm at one edge of the room along where the cold cables are to be run so as to allow them to sit flush under the floor covering when it is l...

Page 5: ...d a coloured outer and a clear inner Carbon Film Installation Under Wood Laminate Flooring Only LIGHT FOOTWARE should be worn Avoid foot traffic on the heating elements and cold tail joints Un pack th...

Page 6: ...Step 7 Step 8 Fig 9 Step 9 Once the cold tails are in position a resistance test needs to be per formed on each individual element for a second time The desired resistance readings for each element ar...

Page 7: ...s being laid a 100micron sheet clear will be provided When fitting Heat Pak over a carbon heating sys tem a 200micron sheet coloured blue has to be used The joints of the sheeting have to overlap by a...

Page 8: ...ectrical contractor in respect of the individual heating circuit ratings relative to the thermostat rating circuit breakers interconnecting cable sizing and switched contactors where the load of the h...