Setting the operating temperature FK207T 

 
 

 

Unit must be switched on 

 

Adjustment 

parameters 

 
 

 Press and hold Set key  

 
 

Adjust 

¿

 and 

À

key 

 

FREEZER 

UNIT 

 

-24

°

CHILLER 

UNIT 

 

01

°

C

 

 

Fault codes FK207T 

 

This new controller has a fault indication program that aid’s in 

recognising problem’s that may occur with the refrigeration aspects. 

A simple code, listed below, will show on the controller display.  

 

Code Reasons 

Remedies 

E2 

Corrupted 

memory 

data 

• 

There is the 
corruption of the 
configuration data of 
the memory of the 
instrument 

• 

Switch off the power supply for 2minutes. 
Reconnect the power supply; if error code still 
displayed replace the unit. 

E0 

Cabinet 

probe 
alarm 

• 

Probe type incorrect 

• 

Probe fault 

• 

Fit correct probe type 

• 

Check probe connections  

E1 

Evaporator 

probe 
alarm 

• 

Probe type incorrect 

• 

Probe fault 

• 

The evaporator 
temperature is 
outside the limits of 
the controller 

• 

Fit correct probe type 

• 

Check probe connections 

• 

Test the temperature close to the probe to 
ensure its between the set operating range 

COH 

• 

Condenser fins dirty 

 

• 

The condenser 
temperature is 
outside the limit set 
within the parameter 
C7 

• 

Clean the condenser fins (see page 7) 

 

• 

Check temperature close to the probe and 
adjust parameter C7 

 

CSd 

• 

Condenser fins dirty 

 

• 

The condenser 
temperature is 
outside the limit set 
within the parameter 
C8 

• 

Clean the condenser (See page 7) 

 

• 

Turn unit off 

• 

Check temperature close to the probe and 
adjust parameter C8 

Issue 1:1 31.10.2002  

11

 

Summary of Contents for 804048V

Page 1: ...H K EUROPE Please keep in the McDonald s store equipment manual for future reference User manual Filet Freezer 804048V Filet Chiller 804800...

Page 2: ...eration 6 Technical information 6 Maintenance 7 Troubleshooting 8 Setting operational temperature MTR12 8 Controller configuration LAE MTR12 9 Controller configuration FK207T 10 Setting operational te...

Page 3: ...ng difficulties Disconnect power source before maintaining or repairing the unit Do not steam clean jet wash or use high pressure hoses on or in the vicinity of this unit A poorly maintained condenser...

Page 4: ...and chilled products are held at 1 C to 4 C in the Filet Chiller Manufacturer s details H K Rugby 1 Cosford Lane Swift Valley Rugby CV21 1QN United Kingdom Tel 44 0 1788 554000 Fax 44 0 1788 554100 H...

Page 5: ...buse or neglect of equipment Parts replaced after the one year period has elapsed are covered under warranty for 90 days Purchase record This information should be entered upon receipt of Filet Freeze...

Page 6: ...r switching on allow 1 to 2 hours for the unit to reach operating temperature The door must be closed during this chill down period Freezer When operating temperature has been reached 18 to 24 C food...

Page 7: ...es The condenser fins are likely to require cleaning at least once a month but the frequency will depend on unit usage and operating conditions Step Action 1 Isolate power and unplug the unit 2 Remove...

Page 8: ...operating temperature Product loaded above 18 C 2 Condenser fins dirty 3 Operating temperature set point incorrect 4 Unit still not operating 1 Remove product until unit has reached operating temperat...

Page 9: ...est temperature 00 sets lowest temperature 3 Set SP Set previous setting 24 sets high point 02 sets high point 4 Set RT1 Set previous setting 2 sets for delayed start 2 sets for delayed start 5 Set PF...

Page 10: ...HILLER UNIT 1 and simultaneously and hold for approx 4sec PA Set 0 19 19 2 and simultaneously hold for approx 4sec 1 Set previous setting 32 32 3 key 6 Set previous setting 0 0 4 key r0 Set previous s...

Page 11: ...eplace the unit E0 Cabinet probe alarm Probe type incorrect Probe fault Fit correct probe type Check probe connections E1 Evaporator probe alarm Probe type incorrect Probe fault The evaporator tempera...

Page 12: ...er 1000 R02012 1 2 Fk207T controller Chiller 1001 R02012 1 3 Probe R02009 1 4 Compressor R01112 1 5 Capillary Tube and Drier R01201 1 6 Condenser Fan Motor R01020 1 7 Condenser Fan Blade R01021 1 8 Ma...

Page 13: ...Freezer Wiring schematic Chiller Issue 1 1 31 10 2002 13...

Reviews: