User Manual RDx-AC-xxxDT-10.31
Page 5 of 13
www.hanbayinc.com | 1 800 315 4461
Rev.2021.9 [email protected]
In this example DIPs 1, 2, 5 and 12 are on.
OPERATION
DIP Switches
The DIP switches allow you to change the
settings on your actuator. To flip a switch,
gently use a small flat-head screwdriver.
See the table below for DIP switch functionality.
DIP switches 1 and 2 set the actuator position control parameters. High settling speed settings are suitable
for fast positioning of light valves. Longer settling times will allow heavier valves to reach their target
positions; trying to use a fast settling setting on a high torque valve will increase current consumption when
holding position, and cause heating of the motor.
DIP switches 10 and 11 set the actuator torque. These settings are adapted to the valve at the factory. Worn-
in valves may require a higher torque setting after some time. The actuator will use 100% of available torque
to try and reach maximum speed.
DIP 1 DIP 2
Description
Recommended Use
Off
Off
Fastest settling
Use only for low torque valves
Off
On
Medium-fast
Typical setting
On
Off
Medium-slow
Typical setting
On
On
Slowest settling
Use for high torque valves
DIP 10 DIP 11
Torque
description
Approximate
stall current (A)
Approximate stall torque (in-lbs)
RDL
RDM
RDH
RDF
Off
Off
Low
0.75
70
212
430
715
Off
On
Medium-low
1.0
79
236
522
832
On
Off
Medium-high
2.0
81
243
525
949
On
On
High
3.0
82
247
532
1067
Note: Medium-high and high settings require voltage supply minimum values as follows:
-
Supply voltage needs to be min 14 VDC for medium-high
-
Supply voltage needs to be 16 VDC for high
-
When operating above 20 VDC and 66% power, Duty cycle is reduced to 50% - 25%
maximum. At these levels, the electronics produce more heat which must be dissipated
(depending on environmental temperature)