Operation 

DIP switches: 

 

The DIP switches allow you to change the  
settings on your actuator. To flip a switch, 
gently use a small flat-head screwdriver. 
See chart below for DIP switch functionality. 

 

 
 
 

 

Switches 1 and 2 set the actuator position control parameters.  High settling speed settings are suitable for fast 
positioning of light valves.  Longer settling times will allow heavier valves to reach their target positions; trying to  
use a fast settling setting on a high torque valve will increase current consumption when holding position, and  
cause heating of the motor.   

 
 
 
 

DIP 1 

DIP 2 

 

Off 

Off 

Fastest settling 

Use only for low torque valves 

Off 

On 

Medium-fast 

Typical setting 

On 

Off 

Medium-slow  

Typical setting 

On 

On 

Slowest settling 

Use for high torque valves 

Connect the signal: 

 
Locate the correct connection terminals as shown on the previous page then connect  
your input signal on pos. 1 and 2 and the output signals on 3 and 4 as shown below. 

 
 
 

 

1   2   3   4   5   6  

 

P1

 

Input #1

 

TTL I/O Signals

 

Input #2

 

Output #2

 

Output #1

 

MDM 
Actuator

 

USER SUPPLIED

 

GND

 

GND

 

2

 

1

 

1

 

2

 

RL 
(max drive 
current 2mA)

 

External 
I/O device 
supplied by 
user < 1mA

 

MDx

 

DIP switches. In this example DIPs 1, 2, 6 and 12 are on. 

Summary of Contents for MD DT-10.31 Series

Page 1: ...ting the type of actuator pg 6 Calibration pg 6 Troubleshooting pg 6 Appendix pg 6 7 Dimensions pg 7 Cable Installation pg 7 Part Number Breakdown pg 8 Installation Mounting Usually the actuator has t...

Page 2: ...color schematic for Turck6 cable Otherwise if the Turck cable is not included in your actuator see pg 8 for more detailed wiring instructions Pin Colour Function 6 White 24VDC 5 Black Power Gnd 4 Pin...

Page 3: ...to use a fast settling setting on a high torque valve will increase current consumption when holding position and cause heating of the motor DIP 1 DIP 2 Off Off Fastest settling Use only for low torq...

Page 4: ...Off On Medium low 33 1A On Off Medium high 66 2A On On High torque 100 3A Approximate stall torque DIP 10 DIP 11 MDL MDM MDH MDF Off Off 55 in lbs 120 in lbs 405 in lbs 756 in lbs Off On 82 in lbs 16...

Page 5: ...e input is used to operate the valve When the actuator is operated using input 1 an automatic calibration is done every time the valve is actuated This does not happen on input 2 Torque Settings Effec...

Page 6: ...he actuators output gear gets manually rotated while the actuator is powered down and can t properly realign to the center by itself Troubleshooting Upon noticing a problem your first step should almo...

Page 7: ...ight fitting from the actuator casing and insert the cable into it 4 Carefully insert the cable into the actuator base Mind the red motor cable and its plug into the board Moving the plug out of its f...

Page 8: ...HANBAY Inc User Manual MDx xxxDT 10 31 Page 8 of 8 www hanbayinc com Rev 2 July 2019 1 800 315 4461 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number...

Reviews: