Wiring:
The actuator comes standard with a Turck 6 position connector
and a 20’ cable with plug. Cut the cable to the
length required and then connect according to the following wire color schematic:
Wire color schematic for
“Turck6” cable:
Otherwise, if the Turck cable is not included in your actuator, see pg.8 for more detailed wiring instructions.
Pin Colour
Function
6
White -> +24VDC
5
Black ->
Power Gnd.
4
Pink ->
Output TT2
3
Grey ->
Output TT1
2
Blue ->
Signal Input TT2
1
Brown ->
Signal Input TT1
Connect the power:
The
MDx-xxxDT
may be connected to voltages ranging from 12
– 24 VDC
The power consumption will range from max. 3.0A to approx. min. 100mA
when the actuator is active. When not moving, the actuator draws around
30mA.
Terminal
1 2 3 4 5 6