Wiring: 
 

The actuator comes standard with a Turck 6 position connector 

and a 20’ cable with plug. Cut the cable to the 

length required and then connect according to the following wire color schematic: 
 

       

Wire color schematic for 

“Turck6” cable:  

 

 

 
 
 
Otherwise, if the Turck cable is not included in your actuator, see pg.8 for more detailed wiring instructions.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
      

Pin  Colour 

Function 

White ->        +24VDC                     

Black ->    

Power Gnd.                 

Pink ->  

Output TT2         

Grey ->  

Output TT1           

Blue ->  

Signal Input TT2         

Brown ->  

Signal Input TT1           

 

Connect the power:  

 

The 

MDx-xxxDT

 may be connected to voltages ranging from 12 

– 24 VDC 

 
The power consumption will range from max. 3.0A to approx. min. 100mA 
when the actuator is active. When not moving, the actuator draws around 
30mA. 
 
 
 

 
 
 

 

Terminal  

1 2 3 4 5 6  

 

 

 

 

Summary of Contents for MD DT-10.31 Series

Page 1: ...ting the type of actuator pg 6 Calibration pg 6 Troubleshooting pg 6 Appendix pg 6 7 Dimensions pg 7 Cable Installation pg 7 Part Number Breakdown pg 8 Installation Mounting Usually the actuator has t...

Page 2: ...color schematic for Turck6 cable Otherwise if the Turck cable is not included in your actuator see pg 8 for more detailed wiring instructions Pin Colour Function 6 White 24VDC 5 Black Power Gnd 4 Pin...

Page 3: ...to use a fast settling setting on a high torque valve will increase current consumption when holding position and cause heating of the motor DIP 1 DIP 2 Off Off Fastest settling Use only for low torq...

Page 4: ...Off On Medium low 33 1A On Off Medium high 66 2A On On High torque 100 3A Approximate stall torque DIP 10 DIP 11 MDL MDM MDH MDF Off Off 55 in lbs 120 in lbs 405 in lbs 756 in lbs Off On 82 in lbs 16...

Page 5: ...e input is used to operate the valve When the actuator is operated using input 1 an automatic calibration is done every time the valve is actuated This does not happen on input 2 Torque Settings Effec...

Page 6: ...he actuators output gear gets manually rotated while the actuator is powered down and can t properly realign to the center by itself Troubleshooting Upon noticing a problem your first step should almo...

Page 7: ...ight fitting from the actuator casing and insert the cable into it 4 Carefully insert the cable into the actuator base Mind the red motor cable and its plug into the board Moving the plug out of its f...

Page 8: ...HANBAY Inc User Manual MDx xxxDT 10 31 Page 8 of 8 www hanbayinc com Rev 2 July 2019 1 800 315 4461 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number...

Reviews: