Wiring:
The actuator comes standard with a Turck 5 position connector
and a 20’ cable with plug. Cut the cable to the
length required and then connect according to the following wire color schematic:
Wire color schematic for “Turck5”cable:
* “feedback” available in MCx-B-xxxA
F
version of actuator only.
** “isolated” available in MCx-B-xxxA
I
and xxxA
F
versions of actuator only
.
Otherwise, if the Turck cable is not included in your actuator, see pg.9for more detailed wiring instructions.
Pin Colour
Function
6
White -> +24VDC
5
Black ->
Power Gnd.
4
Grey ->
Output Signal (4...20mA)
*
3
Not connected
2
Brown->
Isolated
**
Input Signal Gnd.
1
Blue ->
Isolated
**
Input + Signal (4...20mA)
Connect the power:
The
MCx-B
may be connected to 24 VDC +/- 10%.
The power consumption will range from max. 3.0A to approx. min. 100mA
when the actuator is active. When not moving, the actuator draws around
50mA.
Battery fail safe units will move to the designated “fail”
position upon loss of power, then wait for power to return.
The actuator will be powered by the battery for about one minute to track
the position
of the valve. After one minute, the actuator will go into “sleep”
mode to preserve the life of the battery.
Remove R66 to
convert to 1...5V
input signal
Terminal
1 2 3 4 5 6
Turck male connector pin-out