Changing the number of turns:  

 

The 4...20mA (or 1

…5V) input signal represents a total span of a number of turns. 

i.e.:  If you set the number of turns to 2, then a signal of 12mA will set the actuator to exactly 1 turn from the fully 
closed position. 15 mA will give:   (15-4)/16=0.6875   =>     68.75% of 2 turns    =>   1.375 turns from closed etc. 
 
With the DIP switch settings, you can adjust anything between 1 and 31 turns to represent the full signal range of  
4.

..20mA. Check in the table below. (1 = “On”   0 = “Off”) 

 
 

Total Turns 
Dip4=0

DIP 5

DIP 6

DIP 7

DIP 8

reserved

0

0

0

0

1

0

0

0

1

2

0

0

1

0

3

0

0

1

1

4

0

1

0

0

5

0

1

0

1

6

0

1

1

0

7

0

1

1

1

8

1

0

0

0

9

1

0

0

1

10

1

0

1

0

11

1

0

1

1

12

1

1

0

0

13

1

1

0

1

14

1

1

1

0

15

1

1

1

1

 

 

WARNING

: Be sure that the number of turns the actuator is set for is LESS than the number of turns for the 

valve. The actuator should not stop itself on a fully opened valve. It can damage the valve, and the actuator will 
lose its position.  

 

 

Speed and Torque Details: 

 

 

The maximum speed of the actuator can be set

 by using the first two positions of the 

DIP switch selector

As a result of this setting, the actuator will limit the maximum speed. The tables below show the maximum torques 
that can be expected at the given maximum speeds.  
The torque available also depends on the voltage provided in the power connection and on the seating power 
settings on DIP 10, 11 as shown below. 
 

Speed and Torque of MC

L

-B-xxxAx Actuators        

NOTE

: If actuator is MC

J

-B-xxxAx, divide torque values by 3. 

Time for

1 turn

(sec)

OFF

OFF

7

OFF

ON

3

ON

OFF

2

ON

ON

1

24VDC

48

24VDC

12

24VDC

20

24VDC

38

Torque in in-lbs

Torque in in-lbs

DIP 1

DIP 2

Torque in in-lbs

Torque in in-lbs

66% Power*

100% Power*

16% Power*

33% Power*

 

 

 

 

 

 

 

 

To convert in-lbs to Nm, divide the in-lbs value by 9

 

 
 

For more turns set DIP 4 as follows: 

 

DIP 4=0 

0

 

DIP 4=1 

+16 turns 

 

Note: 
This actuator can accommodate up to the following 
number of turns on its different models: 
 
MCL-B-xxxAx    31 turns    MCJ -xxxAx   31 turns 
MCM-B-xxxAx    31 turns    MCK -xxxAx   31 turns 
MCF-B-xxxAx      xx turns 
 

 

 

 

 
 
 

This will add 16 turns  
to the function of DIPs 5 
to 8 

Operating torque is 100%.  These torque values are for valve seating. 

Summary of Contents for MC-B-A-8.09 Series

Page 1: ...l loss and Calibration pg 5 6 Troubleshooting pg 6 Appendix pg 7 9 Changing number of turns pg 7 Speed and Torque Details pg 7 8 Dimensions pg 9 Installing a cable pg 9 Part Number Breakdown pg 10 Ins...

Page 2: ...tructions Pin Colour Function 6 White 24VDC 5 Black Power Gnd 4 Grey Output Signal 4 20mA 3 Not connected 2 Brown Isolated Input Signal Gnd 1 Blue Isolated Input Signal 4 20mA Connect the power The MC...

Page 3: ...ut is internally supplying the signal current and can drive sufficient voltage for any sensing resistor of up to 250 ohms The potential of the external GND after the sensing resistor may not be more t...

Page 4: ...on of the DIP switches vs number of turns Turning on a switch will add that number of turns to the actuator s movement Example Turning on DIP 6 will add four turns turning on DIP 8 adds one turn If bo...

Page 5: ...3 on the following page 2 For actuators that are connected to a UPS the behavior on signal loss can be set as follows Normal position of DIP9 OFF With DIP9 in the off position the actuator will ignor...

Page 6: ...Terminal strip 1BLUE to 4 GRAY Also re connect the power and signal grounds terminals 5 6 c Power up the actuator with this signal loop back setup d Short SP1 on the circuit board It will automaticall...

Page 7: ...he actuator will lose its position Speed and Torque Details The maximum speed of the actuator can be set by using the first two positions of the DIP switch selector As a result of this setting the act...

Page 8: ...n sec OFF OFF 161 OFF ON 77 ON OFF 49 ON ON 28 24VDC 1241 24VDC 756 24VDC 1008 24VDC 1134 DIP 1 DIP 2 Torque in in lbs Torque in in lbs Torque in in lbs Torque in in lbs 16 Power 33 Power 66 Power 100...

Page 9: ...ng and insert the cable into it Carefully insert the cable into the actuator base Mind the red motor cable and its plug into the board Moving the plug out of its fully inserted position may cause malf...

Page 10: ...User Manual MCx B xxxAx 8 09 Page 10 of 10 www hanbayinc com 1 800 315 4461 Rev 2020 3 hanbaysales hanbayinc com Part Number Breakdown Serial Number Full Hanbay Part Number...

Reviews: