Figure 12.4. Fault Finding Procedures.
Continued from
Fig 12.3
Boiler overheats while
system remains cool?
Boiler operates
noisily?
Insufficient water
circulation
Insufficient water
circulation
Temperature control
set too high
Gas control valve
set incorrectly
Gas control valve
faulty
Boiler operates
normally
Number of Flashes
1 Flash
2 Flashes
3 Flashes
4 Flashes
5 Flashes
Fault Condition
Ignition Lockout
Fan Fault (Running at wrong speed or running when should be stopped)
Condensate Drain Trap Blocked (Condensing models only)
Overheat (high limit thermostat tripped)
Premature flame detection (Flame sensing circuit fault)
Boiler Fault Indication
Certain boiler fault conditions are indicated by a sequence of flashes of the fascia fan running indicator
Scale build up in
boiler waterways
Check/replace pump, bleed
trapped air from the system
Check/replace pump, bleed
trapped air from the system
Adjust temperature
control knob setting
Check/replace gas control
valve assembly
Check/replace gas control
valve assembly
Descale boiler
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
33
Summary of Contents for Sherborne Series
Page 8: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E Figure 1 1 Boiler Installation Typical 2...
Page 29: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E Figure 10 6 Gas Pipe Fitting 23...
Page 45: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E NOTES 39...
Page 46: ...HAMWORTHY HEATING LTD SHERBORNE 500001103 E NOTES 40...
Page 47: ...Notes...