background image

 
HAMWORTHY HEATING LTD 

 

LILLIPUT HE 

 

500001047/F 

13 

8. COMMISSIONING 
 

The boiler should be commissioned by a competent 
person.  The Gas Safety (Installation and Use) 
Regulations require that only Registered (i.e. 
CORGI Registered) gas personnel should install, 
commission and service gas fired equipment such 
as these boilers.  

Failure to comply with these 

regulations may lead to prosecution.

 

 
Before commencing the commissioning of the boiler, 
ensure that any personnel involved are aware of the 
action about to be taken. 
 

8.1 Preliminary 

checks 

 
BEFORE

 starting the boiler, check the following: 

a. 

Check that fuel supply is turned off. 

b. 

Check that electrical supply is isolated. 

c. 

Check that electrical installation conforms to 
the requirements of these Instructions, the 
IEE Wiring Regulations for electrical 
installations, and any other local Regulations 
which apply. 

d. 

Check that electrical connections are correctly 
made, e.g. no loose strands at terminals. 

e. 

Check that supply is correctly fused for the 
current rating of the installation. 

f. 

Check that electrical installation is correctly 
earthed (earth continuity between boiler, gas 
pipework and mains electrical supply). 

g.

 

Check that installation is complete. 

h. 

Check boiler is standing level on an adequate 
base. 

i. 

Check boiler castings are undamaged and 
heat exchanger access plates are correctly 
fitted and sealed. 

j. 

Check all thermostat bulbs are correctly 
inserted in the appropriate pocket. 

k. 

Check for water leaks and ensure that both 
boiler and heating system is full of water and 
properly vented. 

l. 

Check that all drain cocks are closed, and 
that all isolating valves in flow and return 
pipework are open. 

m. 

Check that flue is unobstructed and conforms 
to the relevant Regulations, Code of Practice 
or British Standards.  Refer to Section 3.6 

n. 

Check boiler house is adequately ventilated 
(refer to Section 3.7) and that ventilation 
grilles are unobstructed. 

o. 

For OIL

; check that tank(s) have been filled 

and oil supply pipework between tank and 
burner has been primed. 

p. 

For GAS

; check soundness of gas installation 

and that pipework is purged of air, as detailed 
in British Gas Publications IM/5 and IM/2 
respectively.   

 Check that gas meter is operational and has 
been checked by the local region of British 
Gas.   

 

Check that gas meter and supply pipework is 

of sufficient size to meet the input rating of the 
burner/boiler.  Refer to Section 2.1. 

q. 

Check that burner output is correct for size of 
boiler in question, referring to Section 2.1 and 
the manufacturer's technical information 
supplied with the burner. 

 

8.2 

Oil fired Boilers 

 

a. 

Check flexible oil lines are tightly jointed and 
are not twisted or kinked to form an 
obstruction. 

b. 

Check correct nozzle(s) is fitted to burner, 
and that it is tight. 

c. 

Check electrodes and ensure porcelain 
insulation is not cracked. 

d. 

Check electrodes are correctly positioned, 
and gap is correctly set, as specified in the 
manufacturer's technical information supplied 
with the burner. 

e. 

Check blast tube is correctly located, and 
securely fastened in place and internal 
combustion chamber baffle is correctly 
located. 

f. 

Check burner seats correctly onto burner 
mounting plate and is securely fastened in 
place. 

g. 

Set burner for the required fuel and air 
throughputs, as specified in the 
manufacturer's technical information supplied 
with the burner. 

h. 

Fit a pressure gauge on burner oil pump to 
check pump pressure is correctly set. 

i. 

Check that overheat thermostat manual reset 
is set, and that boiler control thermostat and 
control system are set to call for heat. 

 

Switch the boiler on and start the burner. 

j. 

The burner control will first operate the fan to 
pre-purge the boiler, then produce an ignition 
spark and finally open the oil solenoid valve 
and the flame should ignite. 

k. 

Purge air from oil pump through pressure 
gauge port. 

IF BURNER LOCKS OUT WAIT 45 SECONDS 
BEFORE PRESSING RESET BUTTON ON 
BURNER CONTROL BOX. 
 

l. 

With burner firing, check the atomising 
pressure on gauge and adjust as necessary 
using the pressure regulator on burner oil 
pump.  Refer to technical information supplied 
with burner. 

m. 

After allowing burner to reach stable firing 
conditions for approximately 15 minutes, carry 
out combustion gas check. 

 Measure 

CO

2

, CO, smoke number, flue gas 

temperature and circulating water 
temperature rise across the boiler. The 
readings obtained should be as follows:- 

 
CO

2

 11-12% 

CO 

less than 100 ppm 

Summary of Contents for LILIPUT HE

Page 1: ...SE INSTRUCTIONS MUST BE READ AND UNDERSTOOD BEFORE INSTALLING COMMISSIONING OPERATING OR SERVICING EQUIPMENT LILLIPUT HE GAS OIL FIRED CAST IRON SECTIONAL BOILERS INSTALLATION COMMISSIONING AND MAINTE...

Page 2: ......

Page 3: ...ISSION OPERATE OR MAINTAIN THIS UNIT THE LILLIPUT BOILER IS INTENDED FOR USE AS A COMMERCIAL APPLIANCE AND IS NOT CERTIFIED FOR USE IN DOMESTIC APPLICATIONS GAS FIRED VARIANTS OF THE LILLIPUT BOILER R...

Page 4: ...il Supply 3 6 Flue System 3 7 Ventilation and Air Supply 3 7 1 Natural Ventilation 3 7 2 Mechanical Ventilation 4 0 WATER SYSTEM 7 4 1 Pipework 4 2 Pumps 4 3 Vent Pipe 4 4 Safety Valve 4 5 Pressure Ga...

Page 5: ...ater Flow Rates and Pressure Drops 7 Table 4 Composition of Sections within Heat Exchanger 10 FIGURES Figure 1 Overall Dimensions and Clearances 3 Figure 2 Boiler Control Panel Wiring Diagram 9 Figure...

Page 6: ...be used individually or in a multiple boiler configuration and are suitable for use on either open vented or sealed low temperature hot water heating systems For hot water production they can be used...

Page 7: ...AS VOLUME AT NTP NAT GAS m3 h ft3 h 90 0 3178 118 2 4174 APPROX FLUE GAS TEMP NAT GAS deg C 190 FLUE DRAUGHT REQUIRED AT BOILER OUTLET mbar in wg 0 1 0 25 0 04 0 10 WEIGHT FILLED WITHOUT BURNER kg lb...

Page 8: ...Dimensions and Clearances Fig 1 Overall Dimensions and Clearances BOILER MODEL Lmm Hmm Amm Gas Amm Oil Bmm Cmm Dmm min LILLIPUT HE 65 800 530 347 261 400 500 400 LILLIPUT HE 90 960 530 389 261 400 500...

Page 9: ...allation commissioning and maintenance c British Gas Publications IM 2 Purging procedures for non domestic gas installations IM 5 Soundness testing procedures for industrial and commercial gas install...

Page 10: ...sh Standards and Local Authority Regulations Oil Supply Lines The oil supply line s between storage tank and burner should be run in copper steel or aluminium pipe Galvanised pipes and fittings should...

Page 11: ...output and above The following notes are given as general guidance 3 7 1 Air Supply by Natural Ventilation The boiler room must have or be provided with permanent air vents directly to the outside ai...

Page 12: ...d be taken into account when selecting the circulating pump for the system In the case of open vented systems it is essential that the pump does not pump over i e push water out of the open vent pipe...

Page 13: ...ief safety valve of approved manufacture and sized to match the boiler s rating in accordance with BS 6644 should be installed in the flow pipe between the boiler s and open vent pipe connection The s...

Page 14: ...The boiler control panel includes a terminal block for all electrical connections to the boiler Refer to Fig 2 below Wiring diagrams showing the electrical connection of burner to boiler are given in...

Page 15: ...One front section F Intermediate sections I Special intermediate sections SI For the purposes of identification the Intermediate sections have a joint face between the middle and upper part of the se...

Page 16: ...oiler sections Check that the cut outs A are positioned around the rear spacers and secure in position with duct tape A Fit the rear insulation jacket over the flue outlet Secure the top and side edge...

Page 17: ...cable entry hole A is at the front of the boiler Se cure the top cover to the rear cover using the 4x10 self tapping screws B A B B Remove the cable entry blanking plate A from the control con sole a...

Page 18: ...r as detailed in British Gas Publications IM 5 and IM 2 respectively Check that gas meter is operational and has been checked by the local region of British Gas Check that gas meter and supply pipewor...

Page 19: ...aximum pressure of gas train governor is not exceeded i Adjust start and main output gas rates as detailed in the manufacturer s technical information supplied with the gas train j Check that overheat...

Page 20: ...ISOLATOR AND SHUT OFF FUEL SUPPLY TO BOILER a a For oil installations Desludge oil storage tank and examine for leaks and signs of deterioration b Examine contents gauge for visibility and clean or r...

Page 21: ...LLIPUT HE 500001047 F 16 i h Check all flue joints for integrity j i Check ventilation ducts grilles to boiler room and ensure they are clear k j Re commission boiler as detailed in relevant parts of...

Page 22: ...Hexagonal bush 1 BSP 573405119 9 Thermostat pocket 573405228 10 Plug BSP 573405121 11 Door hinge 573405229 12 Insulation front door 573405230 13 Insulation front 573405231 14 Front door 573405232 15...

Page 23: ...HAMWORTHY HEATING LTD LILLIPUT HE 500001047 F 18 Fig 4 Exploded View of Boiler 26 Item 26 insulation to be placed between refractory brick and door casting...

Page 24: ...LIGHT L N 3 WIRE BURNER CONNECTION FOR REMOTE LOCKOUT LAMP OR VOLT FREE SIGNAL FOR OVER TEM PERATURE LOCKOUT FOR BURNER WORKING SIGNAL FOR EXTERNAL THERMOSTAT OR PRESSURE SWITCH FOR EXTERNAL PUMP SWI...

Page 25: ...mm 616 776 Combustion Chamber Type Reversed BURNER TYPE FOR GAS INSTALLATIONS Burner Manufacturer RIELLO BURNER MODEL 40 GS10 40 GS10 Blast Tube Penetration Dimension A mm 110 110 Burner Manufacturer...

Page 26: ...HAMWORTHY HEATING LTD LILLIPUT HE 500001047 F 21 INSTALLER SITE ADDRESS BOILER TYPE BOILER SIZE S UNIT NO S SERIAL NO S FLUE NOTES...

Page 27: ......

Page 28: ......

Reviews: