Hampton® H35U Direct Vent Freestanding Gas Stove

installation

Ensure that all pipe and elbow connections are 
in their fully twist lock position.

5)

  Ensure vent is vertical and secure flashing to the 

roof  with roofing nails.  Slide the storm collar 
over the pipe section and seal with a mastic.

6)

  Twist lock the vent cap on to the last section.

Support Extensions - Round 
(RDSE) or Square (SQSE)

Steep pitched cathedral ceilings may require the 
use  of  a  support  extension. This  piece  fits  down 
inside the support and can be adjusted to increase 
the  support's  length  by  up  to  22"  (559mm). The 
extension  is  attached  to  the  support  using  the 
eight metal screws provided.  Be sure there is at 
least  a  2"  (51mm)  overlap  where  the  extension 
joins the support.

Gas Connection

The gas connection is a 3/8"  NPT 90

o

 elbow. The 

gas line can be rigid pipe or to make installation 
easier, use a listed flexible connector and/or cop-
per tubing if allowed by local codes. Since some 
municipalities have additional local codes it is always 
best to consult with your local authorities and the 
CAN/CSA B149.1 installation codes.

For USA installations follow local codes and/or the 
current National Fuel Gas Code, ANSI Z223.1.

When  using  copper  or  flex  connectors  use  only 
approved fittings. Always provide a union so that 
gas  lines  can  be  easily  disconnected  for  burner 
and/or valve servicing. Flare nuts for copper lines 
and flex connectors are  usually considered to meet 
this requirement.

I

MPORTANT: ALWAYS CHECK FOR GAS 

LEAKS WITH A SOAP AND WATER SOLU-
TION OR GAS LEAK DETECTOR. DO NOT 
USE OPEN FLAME FOR LEAK TESTING.

Note:  Prior to any pressure testing of the gas 

supply piping system that exceeds test 
pressures of 1/2 psig, this appliance must 
be disconnected from the piping system.  
If test pressures equal to or less than 1/2 
psig are used then this appliance must 
be isolated from the piping system by 
closing its individual manual shut-off 
valve during the testing.

Round Support (RDS) & Square 
Support (SQS)

If your home has a cathedral ceiling (no attic space 
between the ceiling and the roof), install the chimney 
and support as follows.

1)

  Situate the chimney in a convenient location as 

near as possible to the appliance outlet.  Cut 
and frame a hole in the roof for the support. 
The sides of this hole must be vertical with 1 
1/4" (32mm) clearance.

2)

  Place the support in the opening. Lower it to 

the correct height as determined by the table 
and diagram below.

 

Using a level, make sure the support is vertical.  
If the support extends above the roof, cut it 
flush with the top of the roof.  Nail the support 
to the frame opening using (8) 3" spiral nails 
or #8 x 1-1/2" screws.

Note:  If you are using a 6" square support you 

may find it difficult to screw it in place 
because it is fairly small inside.

 

Simpson Dura-Vent has provided angle brack-
ets with this support which can be screwed 
to the outside of the support box and nailed 
to  surrounding  framing  as  required.    Use  a 
minimum of four #8 x 1/2" screws per bracket.  
In some cases these brackets may need to be 
trimmed (e.g.: to fit under a flashing).  Place the 
Finish Collar around the support and fasten it 
to the ceiling using the screws provided.

3)

  Use appropriate roof flashing.  Place the flash-

ing under the upper shingles and on top of the 
lower shingles approximately half of the flashing 
should be under the shingles.  

4)

  Assemble the desired lengths of Black Pipe and 

Elbows necessary to reach from the appliance 
adaptor up through the support box and flashing 
to proper height as per Diagram 12, local codes 
or the "Exterior Vent Terminal Locations" section.  

    Slope 

"X"

0/12  - 2/12 

4"

2/12  - 7/12 

5-1/2"

7/12  - 12/12 

6-3/4"

12/12  - 24/12 

7-1/2"

24/12+   

12-1/2"

SYSTEM DATA - H35U-NG

For 0 to 4500 feet altitude
Natural Gas

Max. Input Rating
Min. Input Rating
Orifice Size

30,000 Btu/h
21,500 Btu/h
#37 DMS

Propane

Max. Input Rating
Min. Input Rating
Orifice Size

29,500 Btu/h
24,000 Btu/h
#52 DMS

Supply Pressure

Natural Gas
Propane

min. 5.0'' w.c.
min. 11'' w.c.

Manifold Pressure

Natural Gas
Propane

3.5'' +/- 0.2'' w.c.
10''  +/- 0.2'' w.c.

Summary of Contents for H35U-LP

Page 1: ...ve the building immediately Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installati...

Page 2: ...instruction can be easily read April 22 14 Created draft Double sided Material Synthetic Paper Size 5 965 W x 5 71 H Color As shown in artwork DANGER HOT GLASS WILL CAUSE BURNS DO NOT TOUCH GLASS UNTI...

Page 3: ...TURES DIAGRAMS SHOWN THROUGHOUT THIS MANUAL ARE FOR ILLUSTRATION PURPOSES ONLY ACTUAL PRODUCT MAY VARY DUE TO PRODUCT ENHANCEMENTS 28 1 8 714mm 6 1 4 159mm 26 7 16 671mm 16 13 16 427mm 15 7 16 391mm 2...

Page 4: ...pton H35U Direct Vent Freestanding Gas Stove dimensions 28 1 8 714mm 6 1 4 159mm 26 7 16 671mm 16 13 16 427mm 15 7 16 391mm 25 5 16 643mm 27 1 2 699mm 16 1 4 412mm 22 13 16 580mm Unit Dimensions Rear...

Page 5: ...ion Precautions 14 Safety Precautions for the Installer 14 Vent Restrictor Position 14 Fan Installation 15 Exterior Vent Terminal Locations 16 4 x 6 5 8 Rigid Pipe Cross Reference Chart only 17 Rigid...

Page 6: ...que minimal Taille de l orifice Altitude Pression d alimentation minimale Pression manifold lev e Pression manifold basse D bit calorifique maximal D bit calorifique minimal Taille de l orifice Altitu...

Page 7: ...e unit converted to top or rear vent per manual instructions and the insulation discarded Venting YES NO Are the venting components approved for the unit installed Does the venting configuration compl...

Page 8: ...Was the air shutter on the proper setting after running the unit for 20 minutes If applicable were the surround and trims installed according to the manual Was the operation of the fan lights if insta...

Page 9: ...in your building Leave the building immediately Immediately call your gas supplier from a neighbours phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire de...

Page 10: ...directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT...

Page 11: ...on producthasbeentestedandlistedby ITS Testing Services as a Direct Vent Wall Furnace to ANSI Z21 88 This Direct Vent System Appliance must be installed in accordance with the manufacturer s installat...

Page 12: ...actmeasurementsforclearances andfloorprotectionbeforeactuallyinstallingthis appliance Have a qualified building inspector review your plans before installation CLOTHING OR OTHER FLAMMABLE MATERIAL SHO...

Page 13: ...c DV Stove Horizontal Vent Kit d Dura Vent Termination Kit 5 Make gas connections Refer to the Gas Con nection section Test the pilot Must be as per diagram in the Maintenance Instruction section If c...

Page 14: ...stion to the outside while the outer pipe draws outside combustion air into the combustion chambertherebyeliminatingtheneedtouseheated room air for combustion and losing warm room air up the chimney N...

Page 15: ...prong receptacle Do not cut or remove the grounding prong from this plug Removing the Fan 1 Unplug or disconnect power source to stove 3 Lift the back cover panel up a unit Take care note to pull o b...

Page 16: ...center line extended above meter regulator assembly 36 90cm a J Clearance to service regulator vent outlet 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inl...

Page 17: ...Length 7 Galvanized N A N A 4D7A N A N A N A N A Adjustable Length 7 Black N A N A 4D7AB N A N A N A N A Extension Pipe 8 1 2 Galvanized 46DVA 08A N A N A N A N A N A N A Extension Pipe 8 1 2 Black 4...

Page 18: ...p 946 205 Vinyl Siding Shield for Riser Vent Terminal 510 994 Rigid Pipe Adaptor Must use with all rigid piping 946 208 P Vent Guard Optional for Riser Vent Terminal 640 530 P Riser Vent Terminal 946...

Page 19: ...AstroCapTM is a proprietary trademark of FPI Fireplace Products International Ltd Dura Vent and Direct Vent Pro are registered and or proprietary trademarks of Simpson Dura Vent Co Inc This product ha...

Page 20: ...nations Maximum one 90O elbow two 45o elbows equal one 90o elbow All approved caps listed on page 12 may be used Propane and Natural Gas Residential Manufactured and Mobile Home Installations The vent...

Page 21: ...permitted Venting Arrangements Straight Horizontal Termination The diagrams show all allowable combina tionsofstraighthorizontalterminationusing Rigid Pipe Restrictor position A Only a snorkel or FPI...

Page 22: ...ontal Please note minimum 1 foot between 90o elbows is required A 3 914 mm min 2 610 mm max B 4 1 2 m min 3 914 mm max C 5 1 5 m min 4 1 2 m max D 6 1 8 m min 5 1 5 m max E 7 2 1 m min 6 1 8 m max F 8...

Page 23: ...1 5 m max 5 1 5 m min E 6 1 8 m max 6 1 8 m min Lengths do not include elbow indicated Vent restrictor position A fully open Refer to the Vent Restrictor Posi tion section Option V H V V1 With these o...

Page 24: ...as straight as possible avoid unnecessary bending The Air Intake pipe must be attached to the inlet air collar of the termination cap Straight Vertical Terminations Required Parts Part Description 946...

Page 25: ...ut withthe45o elbow willseatontoboththe startercollarandthe90o elbow Crimped section of rigid pipe seats into the 90o elbow Only cut the uncrimped side of pipe Dismantle all pipe sections including ve...

Page 26: ...erature silicone and securing with 3 of the 8 x 1 2 black screws 15 Attach the pipe section to the 45o elbow by sealing with Mill Pac and or high temperature silicone and securing with 3 of the 8 x 1...

Page 27: ...he wall It is also important to note the important to note the wall thickness The wall thimble is suitable for 2 x 4 or 2 x 6 wall construc Warning Always maintain required clearances air spaces to ne...

Page 28: ...e SnorkelTermination Refer to Vent Manufacturer Installation instructions for details Do not attempt to enclose the Snorkel within the wall or any other type of enclosure 3 With the pipe attached to t...

Page 29: ...hing the two sheet metal strips extending from the vent cap assembly into the outer wall of the vent pipe Use the two sheet metal screws provided to connect the strips to the pipe Bend any remaining p...

Page 30: ...r mancewitheachapprovedventingsys tem it is highly recommended to apply Mill Pac sealant supplied to every inner pipe connection Failure to do so may result in drafting or performance issues not cover...

Page 31: ...ir intake is not covered under the ANSI Z21 88a 10007 CSA2 33a 10007testmethodsandtheresulting ITS WHIproductcertification ThecodeAuthor ityHavingJurisdictionmustbeconsultedprior to proceeding with th...

Page 32: ...dividual manual shut off valve during the testing Round Support RDS Square Support SQS If your home has a cathedral ceiling no attic space betweentheceilingandtheroof installthechimney and support as...

Page 33: ...ve 1 Make sure the valve is in the OFF position 2 Loosen the IN and or OUT pressure tap s turning counterclockwise with a 1 8 wide flat screwdriver 3 Attach manometer to IN and or OUT pres sure tap s...

Page 34: ...can be adjusted by moving the adjust ing wire up or down The wire is accessed through the bottom Open the air shutter for a blue flame or close for a yellower flame The burner aeration is factory set...

Page 35: ...the control panel door 3 Remove the logs embers and brick panels if used 4 Remove the 2 screws holding the Burner Assembly to the firebox base Push the Burner Assembly to the left and lift out 6 Unscr...

Page 36: ...n wrench as shown in Fig 4 rotate the screw clockwise until snug do not overtighten Fig 4 WARNING Do not overtighten the screw Recommended to grip the wrench by the short side 15 Verify that if the co...

Page 37: ...manual 3 Sprinkle the embers on the left and right sides of the firebox base A 02 43 D 02 46 G 02 48 C 02 44 B 02 56 F 02 47 E 02 45 Optional Brick Panel 1 Remove the cast top and glass front see Glas...

Page 38: ...re to ensure proper light off make sure flame flows smoothly from one end of burner to the other If there is any flame hesitation check that area for any blockage of the burner port F 0 2 4 7 E 02 45...

Page 39: ...ver a 120V A C power supply is needed for the fan blower operation Caution Ensure that the wires do not touch any hot surfaces and are away from sharp edges WARNING Electrical Grounding Instructions T...

Page 40: ...the TH onthegasvalve Usetablebelowtodetermine the maximum wire length Note Preferable if the thermostat is installed on an interior wall Hampton offersanoptionalprogrammablethermo stat but any 250 750...

Page 41: ...from manufactur ing Smoke detectors in the house may go off at this time Open a few windows to ventilate the room for a couple of hours The glass may require cleaning DONOTATTEMPTTOCLEANTHEGLASSWHILE...

Page 42: ...gas supplier from a neighbours phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob...

Page 43: ...contract at different rates resulting in some cracking and ticking sounds will be heard throughout the cycling process WARNING CHILDRENANDADULTS SHOULD BE ALERTEDTOTHE HAZ ARDSOFHIGHSURFACETEMPERA TU...

Page 44: ...as shown in the diagram under Log Installation Note Improper positioning of logs may create carbon build up and will alter the unit s performance which is not covered under warranty Glass Replacement...

Page 45: ...y steps 13 19 10 Remove all 18 screws holding the burner tray assembly in place 12 To replace the burner tray assembly simply reverse these instructions Toremovevalvefromvalveassembly continue 13 Remo...

Page 46: ...ional Fan instructions above Servicing the Thermodisc To replace or service the fan thermodisc temperature switch use the following steps 1 Unplug or disconnect power source to stove 2 Remove two scre...

Page 47: ...he list should be checked by a licensed gas service technician during the annual service check Your unit may require more frequent maintenance checks if you notice any changes in how it operates Opera...

Page 48: ...43 225 Cast Right Timberline Brown 743 227 Cast Right Seaside Sand 12 743 231 Cast Front Charcoal Grey 743 235 Cast Front Timberline Brown 13 743 271 Top Cast Grill Charcoal Grey 743 275 Top Cast Gril...

Page 49: ...N S 904 529 Allen Key 5 32 Long N S 910 940 Black Protective Cap Hi Low Control Knob N S 911 137 Pilot Hood Clip N S 910 941 4 m m Valve Screw With Red O Ring N S 932 012 3 8 Stainless Steel Flexible...

Page 50: ...an Kit Complete N S 740 901 Brick Panels Rustic Brown N S 740 902 Brick Panels Old Town Red N S 744 969 LP Conversion Kit N S 910 399 Fire genie Remote Control N S 910 407 Basic Wall Thermostat N S 91...

Page 51: ...Hampton H35U Direct Vent Freestanding Gas Stove 51 notes...

Page 52: ...ontrol Boards Wiring Switches Blowers Blower Control Module Battery Pack Remote Control Systems 2 Enamel Panels 1 Venting Venting Components 1 All Stainless steel surrounds 1 All Firebox Media Crystal...

Page 53: ...rafts installation error installation by an unqualified installer incorrect chimney components including but not limited to cap size or type operator error abuse misuse use of improper fuels lack of r...

Page 54: ...the U S should consult their local provincial or national legal codes for additional terms which may be applicable to this warranty How to Obtain Warranty Service Customers should contact the authori...

Page 55: ...ow in order for us to serve you better Warranty Registration Form or Register online immediately at the above Web Site Warranty Details Serial Number required Purchase Date required mm dd yyyy Product...

Page 56: ...56 Hampton H35U Direct Vent Freestanding Gas Stove warranty...

Page 57: ...Hampton H35U Direct Vent Freestanding Gas Stove 57 notes...

Page 58: ...58 Hampton H35U Direct Vent Freestanding Gas Stove notes...

Page 59: ......

Page 60: ..._____________________________________________ Phone ____________________________________________________________ Date Installed _______________________________________________________ Serial _________...

Reviews: