Fault Type
Persist Time
Fault Action
Motor
10 Secs
1 Sec
Motor temp > 130° C, Fault.
. If fault exists and
Motor temp > 135° C for 10 Secs, shutdown.
Motor temp > 130° C, Fault
. If fault exists and Motor
temp > 130° C for 60 Secs, shutdown.
Electronics
10 Secs
1 Sec
Electronics temp > 110° C, Fault.
If fault exists and Electronics temp > 115° C for 10 Secs,
shutdown.
Electronics temp > 110° C, Fault.
If fault exists and Electronics temp > 100° C for 15 Secs,
shutdown.
Table 3-4. Fault Configuration For OVERTEMP Alarm
Automatic Shutdown Feature
The ACT2000 has a self-protective shutdown feature. The ACT2000 will
shutdown if:
•
Any two motor winding temperatures exceed 135
°
C for ten (10)
seconds
or more (130
°
C for 60 seconds
)
•
The electronics temperature exceeds 115
°
C for 10 seconds
or
more (100
°
C for 15 seconds
)
Note:
The POSITION and MOTOR CURRENT feedback signals
will both be set to 0 mA when the current to the actuator
motor is removed.
WARNING
Property Damage and Injury Hazard – If the motor windings exceed
135
°
C
(130
°
C
) or the electronics exceed 115
°
C
(100
°
C
), the MCE will shut down power to the motor and electronics
thereby allowing the actuator to move with load. Touching the
actuator may result in serious burn injury
CH. 3: OPERATING THE ACT2000
43
Summary of Contents for Precision ACT2000 Series
Page 13: ...Figure 1 1 ACT2000 590P Dimensions INSTALLING THE ACT2000 7...
Page 14: ...8 ACT2000 USER GUIDE Figure 1 2 ACT2000 200F Dimensions...
Page 15: ...Figure 1 3 ACT2000 590P Pin Mounting Provisions INSTALLING THE ACT2000 9...
Page 16: ...10 ACT2000 USER GUIDE Figure 1 4 ACT2000 200F Flange Mounting Provisions...
Page 29: ...Figure 2 1 ACT2000 Electronics System Block Diagram CH 2 UNDERSTANDING THE ACT2000 23...
Page 34: ...28 ACT2000 USER GUIDE Figure 2 2 ACT2000 590P Cut Away View...
Page 37: ...Figure 2 5 Typical Refurbishment Plate CH 2 UNDERSTANDING THE ACT2000 31...
Page 38: ...32 ACT2000 USER GUIDE INTENTIONALLY BLANK...
Page 41: ...Figure 3 1 ACT2000 Basic Operation Flow Chart CH 3 OPERATING THE ACT2000 35...
Page 52: ...46 ACT2000 USER GUIDE INTENTIONALLY BLANK...
Page 54: ...48 ACT2000 USER GUIDE INTENTIONALLY BLANK...
Page 60: ...54 ACT2000 USER GUIDE INTENTIONALLY BLANK...