background image

Hamilton

 

Home

 

Products

 

 

Canal

 

Winchester,

 

OH

 

43110

   

 

61MH0028A

   

   

Page

 

9

 

8.

Insert the green wire into the ground lug and tighten the
set screw.

Dual Circuit Line Wiring Connections: 12kW, 15kW or 
20kW Models

 

9.

You will need to insert the black wire from the second
power supply into the L1 screw terminal on the second
circuit breaker down from the top and tighten the set
screw to clamp down on the wire.

10. You will need to insert the white or red wire from the

second power supply into the L2 screw terminal on the
second circuit breaker down from the top and tighten the
set screw to clamp down on the wire.

11. You will need to insert both green wires into the ground

lug and tighten the set screw.

12. Tighten the screws on the cable connectors until the

power supply wires are securely fastened to the
connector.

NOTE: 

The furnaces are equipped with either one or two 

circuit breakers. These circuit breakers protect the wiring 
inside of the furnace in the event of a short circuit. 
Additionally, these breakers provide a means of disconnecting 
the power to the unit. The circuit breakers in the furnace are 
not meant to protect the branch circuit wiring between the 

furnace and the home's breaker panel. General wire and 
breaker sizes are shown in Tables 6 and 7. If sheathed cable is 
used, refer to NEC National Electrical Code (NFPA 70) or the 
Canadian Electrical Code, Part I (CSA C22.1) and local codes 
for additional requirements concerning supply circuit wiring. 
Electrical data can be found in Tables 6, 7, and 8. 

IMPORTANT -

 

All installation on field wiring must be rated 

at 60ºC or higher. Please refer to the wiring diagrams on the 
furnace or this book for more information. 

The 12kW 15kW and 20kW models may be connected to a 
single or dual branch circuit. 

IMPORTANT -

 

Refer to the NEC National Electrical Code 

(NFPA 70) or the Canadian Electrical Code, Part I (CSA 
C22.1) and local codes for wiring material requirements. 

10

 

kW

 

Heater

 

Amps

 ‐ 

208/240

 

VAC

12

 

kW

 

Heater

 

Amps

 ‐ 

208/240

 

CAC

15

 

kW

 

Heater

 

Amps

 ‐ 

208/240

 

VAC

20

 

kW

 

Heater

 

Amps

 ‐ 

208/240

 

VAC

Indoor

 

Blower

 

Type

Indoor

 

Blower

 

Amps

Circuit

 

Load

 ‐ 

FLA

 ‐ 

240

 

VAC

44.87 53.20 65.70 86.53

Heater

 ‐ 

kW

10

12

15

20

Min.

 

Wire

 

Size

 

(90°C)

#6

#4

#3

#4

Minimum

 

Wire

 

Size

 

(75°C)

#6

#4

#3

#3

Minimum

 

Wire

 

Size

 

(60°C)

#4

#4

#2

#2

Ground

 

Wire

 

Size

*

*

*

*

Max

 

Fuse/Circuit

 

Breaker

 

Amps

60

70

90

125

Constant

 

Torque

3.20

47.6/62.5

63.33/83.33

31.66/41.66

38/50

WE30B4

AIR

 

HANDLER

 

MODELS

Table 6: Wiring Requirements – Single Branch Circuit 

10kW Single Stage model can only be wired as a single power supply. 
Single power supply will require circuit breaker jumper bar or a jumper wire. 
+ Refer to the National Electrical Code Table 250-95 for Non-Sheathed Conductor Ground Wire. 

* Ground conductor 

must be the same size and temperature rating

 as the other conductors listed in Table 6.

Indoor Blower Amps are the tested blower motor amps, not FLA. The FLA’s are: 1/3 HP is 2.8A, 1/2 HP is 4.1A and 3/4 HP is 6.0A 

Summary of Contents for WE30B Series

Page 1: ...er Location 11 29 Wiring Diagram 20 kW w C T Blower Motor 22 15 Control Box Power Low Voltage Wire Locations 13 LIST OF TABLES 1 Electric Furnace Model Specifications 2 8 Electrical Data 10 2 Model No...

Page 2: ...Single Stage Heating 30 Table 2 Furnace Model Nomenclature Coil Cabinet Model Front Door of Cabinet Open Top 17 3 4 x 21 3 4 Maximum Air Flow CFM 1 Pleated Air Filter In The Door 2 Pleated Air Filter...

Page 3: ...ce heating cooling equipment Untrained service personnel can perform basic maintenance functions such as cleaning of exterior surfaces and replacing the air filters Observe all precautions in the manu...

Page 4: ...y a closet or alcove must have a certain total free area opening for the return air For A C and HP Furnaces 1 3 HP Blower Minimum 200 in free area opening Use Return Grille or Coil Cabinet For A C and...

Page 5: ...to use SECTION IV SUPPLY AIR AND DUCT CONNECTOR INSTALLATION Duct Connectors 90 DCU0 XX Duct Connectors The duct connector is used to provide a sealed connection between the furnace base and a under...

Page 6: ...the insulation around the perimeter of the duct connector opening 5 Install the floor base over the floor opening with the flanges on the 11 x 13 inch opening facing down Refer to Figures 8 and 9 6 Lo...

Page 7: ...to the floor by drilling two holes through the furnace base and the floor base at the right and left front inside corners of the cabinet Use two screws to secure the furnace to the floor Figure 10 Re...

Page 8: ...e coil cabinet 11 Place the cooling cabinet front door on the unit by inserting the tabs in the bottom of the door into the slots in the coil shelf line up the strike in the front flange of the top co...

Page 9: ...Electrical Code Part I CSA C22 1 and local codes for additional requirements concerning supply circuit wiring Electrical data can be found in Tables 6 7 and 8 IMPORTANT All installation on field wiri...

Page 10: ...er supply will require circuit breaker jumper bar or a jumper wire Refer to the National Electrical Code Table 250 95 for Non Sheathed Conductor Ground Wire Ground conductor must be the same size and...

Page 11: ...le codes Figure 14 Control Box Cover and Circuit Breaker Location Dual Element Box For personal safety be sure to turn the electrical power OFF at the main circuit panel Home Circuit Breaker Box and a...

Page 12: ...cated on the blower housing 6 Follow the instructions in the USERS INFORMATION MANUAL to properly start up the air handler POWER SUPPLY CONNECTIONS If the air handler has been installed prior to insta...

Page 13: ...Installation The thermostat heat anticipator must be set at 0 7 Amps if the thermostat has a manual heat anticipator adjustment This setting should be checked at the time of installation The thermost...

Page 14: ...R Figure 16 Separate Thermostats Separate Air handler and Cooling Unit G R W R G Y Heating Thermostat Cooling Thermostat C Y R G W C COM HEAT COOL Thermostat Interlock Switch Air Handler 24 VAC Transf...

Page 15: ...8 strain relief in the control box and place the thermostat wire cable next to the low voltage terminal block 6 Connect the Red 24 VAC supply thermostat wire to the red pigtail wire and secure the two...

Page 16: ...peratureSwitch W2 J u m p e r Figure 22 Typical Heat Pump 2 Stage Heating Cooling Connections SECTION X MOTOR BLOWER AND FURNACE START UP Selecting the Constant Torque Blower Speed This furnace uses t...

Page 17: ...s to the furnace at the main circuit panel House Circuit Breaker 14 Set the thermostat to the desired temperature Figure 24 Blower Assembly and Blower Deck SECTION XI FINAL SYSTEM CHECKOUT 1 Refer to...

Page 18: ...BLK W H T G R N Y E L L2 B L K WHT B LU B L K BM G R N GGS Y E L C L A S S 2 CLASS 2 CC COMPRESSOR CONTACTOR RVS REVERSING VALVE SOLENOID LEGEND TB TERMINAL BLOCK BMFP 6 PIN MOLEX BLOWER MOTOR PLUG A...

Page 19: ...L1 HC1 T2 L2 G R N GGS C L A S S 2 WHT W H T WHT CLASS 2 CC COMPRESSOR CONTACTOR RVS REVERSING VALVE SOLENOID LEGEND TR TRANSFORMER BMFP 6 PIN MOLEX BLOWER MOTOR PLUG ASSEMBLY GND GROUND CONNECTION B...

Page 20: ...N B R N BRN BLK WHT BLK BLK THERMOSTAT W2 BLK BLK BLK BLK B L K B L K B R N BRN B R N BRN B R N HPM 7 RED ST1 8 BLK L1 9 BLU ST4 Y E L L 2 G R N G N D P R P S T 3 B L K S T 5 B R N 2 4 V C O M BRN G N...

Page 21: ...40 VAC 24 VAC BLK 1 BLK SUPPLY WIRING XMC0 402EBBC Contactor L1 T1 L2 T2 HC1 BLU BLU L1 GND G BLK WHT G R N R E D HC1 HTR1 BLK BLU RED RED T1 C B L1 C irc u it 1 L2 C B C irc u it 1 B L K HC1 T2 L2 1...

Page 22: ...BRN BLU GND BLU PRR ST3 ORN ST2 B R N 2 4 V C O M B L U S T 4 O R N S T 2 P R P S T 3 B L U O R N P U R B L U B L U W H T W B R N BLU B L U B L K B L K R E D R E D FOR A TWO STAGE HEATING THERMOSTAT R...

Reviews: