background image

Hamilton

 

Home

 

Products

 

 

Canal

 

Winchester,

 

OH

 

43110

   

 

61MH0028A

   

   

Page

 

4

 

Codes 

The furnace must be installed in accordance with the 
following codes. 

Standard for the Installation of Air Conditioning and
Ventilating Systems (NFPA 90A)

Standard for the Installation of Warm Air heating and
Air Conditioning Systems (NFPA 90B)

National Electrical Code (NFPA 70)

Canadian Electrical Code, Part I (CSA C22.1)

All local codes (State, City, and Township)

NOTE: All applicable codes take precedence over any 
recommendation made in these instructions. 

SECTION IlI: RETURN AIR AND 
CLEARANCE REQUIREMENTS 

Access for servicing is an important factor in the location of 
any furnace. Provide a minimum of 24 inches in front of the 
furnace for access to the control box, heating elements, and 
blower. This access may be provided by a closet door or by 
locating the furnace so that a wall or partition is not less than 
24 inches from the front access door. 

Furnace Clearances 

This furnace is approved for zero (0 inches) clearance to 
combustible material on any part of the furnace exterior and 
the inlet or outlet ducts. Refer to Table 4 for clearance to 
combustibles information. 

ALCOVE

 

(in)

CLOSET

 

(in)

ALL

6

0

0

18

6

0

CLEARANCES

MODEL

FRONT

 

OF

 

FURNACE

TOP

 

(in)

BACK

 

(in)

SIDES

 

(in)

DUCT

 

(in)

Table 4: Clearances to Combustibles 

Figure 2: Closet Clearances 

Return Air 

In order for the furnace to work properly, a closet or alcove 
must have a certain total free area opening for the return air. 

For A/C and HP Furnaces (1/3 HP Blower) 

 

Minimum 200 in² free area opening 

 

Use Return Grille or Coil Cabinet 

For A/C and HP Furnaces (1/2 HP Blower) 

 

Minimum 250 in² free area opening  

 

Use Return Grille, A/C Coil Cabinet, or any return 
grille with a minimum 250 in² free area opening 

For A/C and HP Furnaces (3/4 HP Blower) 

 

Minimum 390 in² free area opening  

 

Use Return Grille, or A/C Coil Cabinet, or any return 
grille with a minimum 390 in² free area opening 

Top Return Only – Recommended Grille Size 

800 CFM – 20 X 20 Grille – 324 in² 
1000 CFM – 20 X 25 Grille - 414 in² 
1200 CFM – 25 X 25 Grille - 414 in²  

1400 CFM – 25 X 30 Grille - 644 in² 
1600 CFM – 25 X 30 Grille - 644 in² 
1800 CFM – 30 X 30 Grille - 784 in² 

Louvered Door and Top Return – Recommended Grille 
Size 

800 CFM – 10 X 20 Grille – 144 in² 
1000 CFM – 12 X 20 Grille -180 in² 
1200 CFM – 14 X 20 Grille - 216 in² 
1400 CFM – 18 X 20 Grille - 288 in² 
1600 CFM – 18 X 20 Grille - 288 in² 
1800 CFM – 20 X 20 Grille - 324 in² 

The return air opening can be located in a closet front door or 
a side wall above the furnace casing, or in a louvered door on 
the furnace. If opening for the return air is located in the floor, 
side walls, or closet door anywhere below the furnace casing 
height, a 6 inch minimum clearance must be provided on the 
furnace side where the return is located to provide for proper 
air flow. The 6 inch minimum clearance is not required if 
there is a return grille installed above the furnace with the 
sufficient return air opening. 

Figure 3: Typical Closet Installations 

Summary of Contents for WE30B Series

Page 1: ...er Location 11 29 Wiring Diagram 20 kW w C T Blower Motor 22 15 Control Box Power Low Voltage Wire Locations 13 LIST OF TABLES 1 Electric Furnace Model Specifications 2 8 Electrical Data 10 2 Model No...

Page 2: ...Single Stage Heating 30 Table 2 Furnace Model Nomenclature Coil Cabinet Model Front Door of Cabinet Open Top 17 3 4 x 21 3 4 Maximum Air Flow CFM 1 Pleated Air Filter In The Door 2 Pleated Air Filter...

Page 3: ...ce heating cooling equipment Untrained service personnel can perform basic maintenance functions such as cleaning of exterior surfaces and replacing the air filters Observe all precautions in the manu...

Page 4: ...y a closet or alcove must have a certain total free area opening for the return air For A C and HP Furnaces 1 3 HP Blower Minimum 200 in free area opening Use Return Grille or Coil Cabinet For A C and...

Page 5: ...to use SECTION IV SUPPLY AIR AND DUCT CONNECTOR INSTALLATION Duct Connectors 90 DCU0 XX Duct Connectors The duct connector is used to provide a sealed connection between the furnace base and a under...

Page 6: ...the insulation around the perimeter of the duct connector opening 5 Install the floor base over the floor opening with the flanges on the 11 x 13 inch opening facing down Refer to Figures 8 and 9 6 Lo...

Page 7: ...to the floor by drilling two holes through the furnace base and the floor base at the right and left front inside corners of the cabinet Use two screws to secure the furnace to the floor Figure 10 Re...

Page 8: ...e coil cabinet 11 Place the cooling cabinet front door on the unit by inserting the tabs in the bottom of the door into the slots in the coil shelf line up the strike in the front flange of the top co...

Page 9: ...Electrical Code Part I CSA C22 1 and local codes for additional requirements concerning supply circuit wiring Electrical data can be found in Tables 6 7 and 8 IMPORTANT All installation on field wiri...

Page 10: ...er supply will require circuit breaker jumper bar or a jumper wire Refer to the National Electrical Code Table 250 95 for Non Sheathed Conductor Ground Wire Ground conductor must be the same size and...

Page 11: ...le codes Figure 14 Control Box Cover and Circuit Breaker Location Dual Element Box For personal safety be sure to turn the electrical power OFF at the main circuit panel Home Circuit Breaker Box and a...

Page 12: ...cated on the blower housing 6 Follow the instructions in the USERS INFORMATION MANUAL to properly start up the air handler POWER SUPPLY CONNECTIONS If the air handler has been installed prior to insta...

Page 13: ...Installation The thermostat heat anticipator must be set at 0 7 Amps if the thermostat has a manual heat anticipator adjustment This setting should be checked at the time of installation The thermost...

Page 14: ...R Figure 16 Separate Thermostats Separate Air handler and Cooling Unit G R W R G Y Heating Thermostat Cooling Thermostat C Y R G W C COM HEAT COOL Thermostat Interlock Switch Air Handler 24 VAC Transf...

Page 15: ...8 strain relief in the control box and place the thermostat wire cable next to the low voltage terminal block 6 Connect the Red 24 VAC supply thermostat wire to the red pigtail wire and secure the two...

Page 16: ...peratureSwitch W2 J u m p e r Figure 22 Typical Heat Pump 2 Stage Heating Cooling Connections SECTION X MOTOR BLOWER AND FURNACE START UP Selecting the Constant Torque Blower Speed This furnace uses t...

Page 17: ...s to the furnace at the main circuit panel House Circuit Breaker 14 Set the thermostat to the desired temperature Figure 24 Blower Assembly and Blower Deck SECTION XI FINAL SYSTEM CHECKOUT 1 Refer to...

Page 18: ...BLK W H T G R N Y E L L2 B L K WHT B LU B L K BM G R N GGS Y E L C L A S S 2 CLASS 2 CC COMPRESSOR CONTACTOR RVS REVERSING VALVE SOLENOID LEGEND TB TERMINAL BLOCK BMFP 6 PIN MOLEX BLOWER MOTOR PLUG A...

Page 19: ...L1 HC1 T2 L2 G R N GGS C L A S S 2 WHT W H T WHT CLASS 2 CC COMPRESSOR CONTACTOR RVS REVERSING VALVE SOLENOID LEGEND TR TRANSFORMER BMFP 6 PIN MOLEX BLOWER MOTOR PLUG ASSEMBLY GND GROUND CONNECTION B...

Page 20: ...N B R N BRN BLK WHT BLK BLK THERMOSTAT W2 BLK BLK BLK BLK B L K B L K B R N BRN B R N BRN B R N HPM 7 RED ST1 8 BLK L1 9 BLU ST4 Y E L L 2 G R N G N D P R P S T 3 B L K S T 5 B R N 2 4 V C O M BRN G N...

Page 21: ...40 VAC 24 VAC BLK 1 BLK SUPPLY WIRING XMC0 402EBBC Contactor L1 T1 L2 T2 HC1 BLU BLU L1 GND G BLK WHT G R N R E D HC1 HTR1 BLK BLU RED RED T1 C B L1 C irc u it 1 L2 C B C irc u it 1 B L K HC1 T2 L2 1...

Page 22: ...BRN BLU GND BLU PRR ST3 ORN ST2 B R N 2 4 V C O M B L U S T 4 O R N S T 2 P R P S T 3 B L U O R N P U R B L U B L U W H T W B R N BLU B L U B L K B L K R E D R E D FOR A TWO STAGE HEATING THERMOSTAT R...

Reviews: