background image

Hamilton

 

Home

 

Products

 

 

Canal

 

Winchester,

 

OH

 

43110

   

 

61MH0028A

   

   

Page

 

6

 

Installing the Duct Connector 

1.

Attach the four (seal strip) foam tape gaskets provided
with the duct connector alongside the perimeter of the
duct opening to seal the duct connector where it attaches
to the top of the duct as shown in Figures 7, 8 and 9.

2.

Insert the duct connector thru the opening in the floor and
attach the duct connector to the top of the duct by
inserting the tabs thru the opening in the top of the duct
and bending the tabs back 90 degrees against the inside of
the duct, so the top of the duct is securely fastened to the
duct connector. Be sure the seal strip has sealed the area
around the duct connector where it attaches to the duct.

3.

Slit the corners of the duct connector that extend above
the floor, and then bend the sides over onto the floor
surface. Refer to Figures 7, 8 and 9.

4.

It is recommended to place insulation with a rating of R-
12 or higher between the floor base and the floor when
used on a combustible floor. The use of insulation
between the duct connector and a combustible floor is not
a requirement, it is a precautionary measure to guard
against the combustible floor from getting to warm. If
insulation is used, be sure to cut the insulation around the
perimeter of the duct connector opening.

5.

Install the floor base over the floor opening with the
flanges on the 11 x 13 inch opening facing down. Refer to
Figures 8 and 9.

6.

Locate the four (4) screws provided with the duct
connector kit and install the four screws through the four
holes provided in the floor base to secure the floor base to
the floor.

The duct connector is designed for use on ducts wider than 12 
inches. When using the connector on smaller width ducts, 
there will not be sufficient clearance to bend the tabs on two 
sides of the duct connector. This furnace is designed to be 
installed on an existing duct connector. 

In such cases the tabs may be attached to the sides of the duct 
by using sheet metal screws or other suitable fasteners. Place 
holes in the tabs for sheet metal screws by drilling the required 
screw holes in three (3) tabs on each side of the duct 
connector. If more than three tabs need to be used to provide a 
more secure and air tight connection, then drill the remaining 
tabs so the additional tabs can also be fastened to the duct with 
screws. Use a duct sealer to seal any air leaks between the duct 
and the duct connector. 
Tape can be used to provide a better air seal. The tape should 
be a type approved by applicable national or local codes. 

Figure 7: Duct Connector and Floor Base Installation 

Figure 8: Duct Connector Measurements 

Figure 9: Duct Connector Installation in the Floor 

Summary of Contents for WE30B Series

Page 1: ...er Location 11 29 Wiring Diagram 20 kW w C T Blower Motor 22 15 Control Box Power Low Voltage Wire Locations 13 LIST OF TABLES 1 Electric Furnace Model Specifications 2 8 Electrical Data 10 2 Model No...

Page 2: ...Single Stage Heating 30 Table 2 Furnace Model Nomenclature Coil Cabinet Model Front Door of Cabinet Open Top 17 3 4 x 21 3 4 Maximum Air Flow CFM 1 Pleated Air Filter In The Door 2 Pleated Air Filter...

Page 3: ...ce heating cooling equipment Untrained service personnel can perform basic maintenance functions such as cleaning of exterior surfaces and replacing the air filters Observe all precautions in the manu...

Page 4: ...y a closet or alcove must have a certain total free area opening for the return air For A C and HP Furnaces 1 3 HP Blower Minimum 200 in free area opening Use Return Grille or Coil Cabinet For A C and...

Page 5: ...to use SECTION IV SUPPLY AIR AND DUCT CONNECTOR INSTALLATION Duct Connectors 90 DCU0 XX Duct Connectors The duct connector is used to provide a sealed connection between the furnace base and a under...

Page 6: ...the insulation around the perimeter of the duct connector opening 5 Install the floor base over the floor opening with the flanges on the 11 x 13 inch opening facing down Refer to Figures 8 and 9 6 Lo...

Page 7: ...to the floor by drilling two holes through the furnace base and the floor base at the right and left front inside corners of the cabinet Use two screws to secure the furnace to the floor Figure 10 Re...

Page 8: ...e coil cabinet 11 Place the cooling cabinet front door on the unit by inserting the tabs in the bottom of the door into the slots in the coil shelf line up the strike in the front flange of the top co...

Page 9: ...Electrical Code Part I CSA C22 1 and local codes for additional requirements concerning supply circuit wiring Electrical data can be found in Tables 6 7 and 8 IMPORTANT All installation on field wiri...

Page 10: ...er supply will require circuit breaker jumper bar or a jumper wire Refer to the National Electrical Code Table 250 95 for Non Sheathed Conductor Ground Wire Ground conductor must be the same size and...

Page 11: ...le codes Figure 14 Control Box Cover and Circuit Breaker Location Dual Element Box For personal safety be sure to turn the electrical power OFF at the main circuit panel Home Circuit Breaker Box and a...

Page 12: ...cated on the blower housing 6 Follow the instructions in the USERS INFORMATION MANUAL to properly start up the air handler POWER SUPPLY CONNECTIONS If the air handler has been installed prior to insta...

Page 13: ...Installation The thermostat heat anticipator must be set at 0 7 Amps if the thermostat has a manual heat anticipator adjustment This setting should be checked at the time of installation The thermost...

Page 14: ...R Figure 16 Separate Thermostats Separate Air handler and Cooling Unit G R W R G Y Heating Thermostat Cooling Thermostat C Y R G W C COM HEAT COOL Thermostat Interlock Switch Air Handler 24 VAC Transf...

Page 15: ...8 strain relief in the control box and place the thermostat wire cable next to the low voltage terminal block 6 Connect the Red 24 VAC supply thermostat wire to the red pigtail wire and secure the two...

Page 16: ...peratureSwitch W2 J u m p e r Figure 22 Typical Heat Pump 2 Stage Heating Cooling Connections SECTION X MOTOR BLOWER AND FURNACE START UP Selecting the Constant Torque Blower Speed This furnace uses t...

Page 17: ...s to the furnace at the main circuit panel House Circuit Breaker 14 Set the thermostat to the desired temperature Figure 24 Blower Assembly and Blower Deck SECTION XI FINAL SYSTEM CHECKOUT 1 Refer to...

Page 18: ...BLK W H T G R N Y E L L2 B L K WHT B LU B L K BM G R N GGS Y E L C L A S S 2 CLASS 2 CC COMPRESSOR CONTACTOR RVS REVERSING VALVE SOLENOID LEGEND TB TERMINAL BLOCK BMFP 6 PIN MOLEX BLOWER MOTOR PLUG A...

Page 19: ...L1 HC1 T2 L2 G R N GGS C L A S S 2 WHT W H T WHT CLASS 2 CC COMPRESSOR CONTACTOR RVS REVERSING VALVE SOLENOID LEGEND TR TRANSFORMER BMFP 6 PIN MOLEX BLOWER MOTOR PLUG ASSEMBLY GND GROUND CONNECTION B...

Page 20: ...N B R N BRN BLK WHT BLK BLK THERMOSTAT W2 BLK BLK BLK BLK B L K B L K B R N BRN B R N BRN B R N HPM 7 RED ST1 8 BLK L1 9 BLU ST4 Y E L L 2 G R N G N D P R P S T 3 B L K S T 5 B R N 2 4 V C O M BRN G N...

Page 21: ...40 VAC 24 VAC BLK 1 BLK SUPPLY WIRING XMC0 402EBBC Contactor L1 T1 L2 T2 HC1 BLU BLU L1 GND G BLK WHT G R N R E D HC1 HTR1 BLK BLU RED RED T1 C B L1 C irc u it 1 L2 C B C irc u it 1 B L K HC1 T2 L2 1...

Page 22: ...BRN BLU GND BLU PRR ST3 ORN ST2 B R N 2 4 V C O M B L U S T 4 O R N S T 2 P R P S T 3 B L U O R N P U R B L U B L U W H T W B R N BLU B L U B L K B L K R E D R E D FOR A TWO STAGE HEATING THERMOSTAT R...

Reviews: