background image

Enabling Wellbeing

 

All rights reserved ©Halton

 

 

 

 

 

 

 

 

 

Halton Max Ultra Circular (MUC) - Quick 

guide for commissioning

 

Summary of Contents for Max Ultra Circular

Page 1: ...Enabling Wellbeing All rights reserved Halton Halton Max Ultra Circular MUC Quick guide for commissioning...

Page 2: ...nel start up views 7 3 1 5 Modbus RTU communication 8 3 1 6 Self diagnosis function 8 3 2 Step by step instructions 9 3 2 1 Configuring basic controller settings in analog mode 9 3 2 2 Configuring bas...

Page 3: ...this document or associated materials may only be used for the purpose specified in this document Halton disclaims any and all liability related to this document Halton gives no explicit or implied w...

Page 4: ...using the ultrasound technique for airflow measurement Application areas Variable VAV and constant CAV airflow control applications Supply and exhaust installations Key features Insensitive to dust c...

Page 5: ...tings The airflow range for Halton Max Ultra Circular MUC is preset at the factory The factory settings for the control signal and feedback signal are the same but they can be configured individually...

Page 6: ...button to move to the next view Press the ESC button to move to the previous view Press the left or right arrow buttons to move between different parameter settings When the Settings view is displaye...

Page 7: ...ir flow AF l s CtrlSig 5 6 7 Aux temperature CtrlSig 8 9 Butto S1 n Settings OK to enter Air speed m s CtrlSig Air temperature C CtrlSig Damper position CtrlSig LAC1 U01 FW ver 01 Halton 3 1 4 Airflow...

Page 8: ...nd the register value you want to change After that send value 9055 to Holding register 40905 then send value 0 to Holding register 40905 3 1 6 Self diagnosis function Halton Max Ultra Circular MUC in...

Page 9: ...Type accordingly Possible values 0 51 Default 0 For information on the installation cases and their corresponding SelectDuctType parameter values see chapter Halton Max Ultra Circular MUC installation...

Page 10: ...meter SelectDuctType accordingly Possible values 0 51 Default 0 For information on the installation cases and their corresponding SelectDuctType parameter values see chapter Halton Max Ultra Circular...

Page 11: ...the right arrow button and the OK button at the same time for 2 seconds The second level of the controller parameter menu opens 3 Select parameter Actuator param Recal then set a value hours between r...

Page 12: ...GND Ground 4 Standard RS 485 B Data receive send line B 5 Standard RS 485 A Data receive send line A 6 GND Ground 7 AI3 Input for NTC 10k temperature sensor 8 GND Ground 9 AI1 Input for airflow or dam...

Page 13: ...ters 5 2 1 Halton Max Ultra Circular MUC installation cases Installation case Sensor position Safety distance L Value of parameter SelectDuctType 7D 0 1D 1 1D 7D 2 1D 3 2D 4 3D 5 3D 7D 6 Outwards 1D 7...

Page 14: ...Sensor position Safety distance L Value of parameter SelectDuctType Outwards 1D 22 2D 23 3D 24 5D 25 5D 7D 26 Inwards 1D 27 2D 28 3D 29 5D 30 5D 7D 31 Side 1D 32 2D 33 3D 34 5D 35 5D 7D 36 Outwards 1...

Reviews: