DRY CONTACT ALARM FUNCTION

A dry contact relay (Alarm Relay) can be activated in certain conditions.  This is useful for connecting 
the control panel to a central building automation or monitoring system.

Parameter name: P08
Allowed values: 

0  Relay closes only when Fire Alarm is detected

1  Relay closes only when any of the following is detected:
 

 

 

- UV Door alarm

 

 

 

- No Filter alarm

 

 

 

- No Fan alarm

 

 

 

- Any of the statistics reaches its preset value

2  Relay closes in any of the above conditions
Factory default: 

0

TROUBLE SHOOTING GUIDE

INOPERATIVE

PROBLEM CAUSE

SOLUTION

Exhaust fan and UVC lamp will 

not function

Control Panel Message: 

No Fan or Error

Field Wiring or Breaker

- Verify field wiring for proper  

  connections

- Check fuse at control panel

Fan on but no UVC lamps

Control Panel Message:

No Fan or door OPEN

UV door open

Pressure switch malfunction

- Close door

- Check wiring

- Check air tube for blockage

- Replace pressure switch if 

  necessary 

Power off within ten seconds

Control Panel Message: 

No Fan

No air flow

Panel not reading air flow

- Check fan for proper operation

- Check pressure switch 

  connection and tube

- Replace pressure switch if 

  defective 

UV failure lamp flashes on and 

off

Control Panel Message:

Error

UV lamp failure or lamp ballast 

failure

- Replace failed cassette with a 

  new one. 

- Replace ballast if defective. 

Summary of Contents for KVE-UV

Page 1: ...Operators Manual Operation Maintenance and Service Capture RayTM Hoods Model KVE UV KVC UV KVW UV...

Page 2: ...hanging weight Do not lift exhaust hoods from their end panels Lift from four corners All exhaust hoods and control panels are fitted together and factory tested prior to shipping for alignment and o...

Page 3: ...HERS 18 GA MAT L BY OTHERS EXHAUST DUCT EXHAUST COLLAR CONTINUOUS LIQUID TIGHT WELD HANGER BRACKET DETAIL ALL THREAD TURN BUCKLE HANGER BRACKET EXHAUST DUCT PER CODE SUPPLY DUCT ALTERNATIVE WELD LIQUI...

Page 4: ...nnel on starting from one end and going to the other A Splice Strip Insert splice strip over bottom front edge first then over top front of the hood Secure to top of the hood by welding or sheet metal...

Page 5: ...Velocities of make up air should be kept to a minimum especially near the exhaust hood perimeter CAUTION High make up air velocities will distrub smoke capture Many codes call for a number of air cha...

Page 6: ...ween ambient air and the exhaust plenum the T A B Port reading AccuFlow installs in Capture Jet plenum for easy viewing and access The device shares an electrical circuit with the Capture Jet fan Phot...

Page 7: ...irflow K Factors have been determined by Halton Research and Development personnel Bluetooth capability also allows an Authorized Service Agent to determine the airflow of an exhaust hood on site if a...

Page 8: ...cuFlow device Loose or improper electrical connections Verify or reconnect electrical connections Low airflow alarm Not reaching design airflow Plastic tubing disconnected from Accuflow device or TAB...

Page 9: ...hed by use of a thermal fusible link in the exhaust collar and detection line above the appliances If the fusible link should activate it would close the fire damper if supplied and automatically rele...

Page 10: ...t by the correct model number including perfix and suffix letters and numbers and serial numbers if shown The model plate affixed to the unit contains this information and is mounted on the inside of...

Page 11: ...ure the unit is turned off at the control panel Remove the KSA grease extractor and clean the interior sections of the exhaust plenum where there is any grease build up Gently wipe any grease off the...

Page 12: ...t the 10 000 hour clock it is necessary to use the keypad to reset the timer DISPLAY CAUSE SOLUTION Error A lamp has failed the voltage to the lamp is too low or the lamp ballast has failed Check line...

Page 13: ...5 When switch is closed UV shuts off immediately without delay UV is the only output affected After Flow Alarm Delay time buzzer sounds and display scrolls No Fan If switch is open again thereafter fo...

Page 14: ...alarm buzzer Total to display the total number of hours of UV operation Clean to display the number of hours of operation since last UV cleaning There are six LEDs from left to right UV lamps ON UV ac...

Page 15: ...ATISTICS Two types of statistics are recorded Total Hours Of Operation and Total Hours Since Last Cleaning These are simply displayed as a number of hours If this exceeds 999 hours then the dis play r...

Page 16: ...p if the Clean key is pressed the unit will reset all parameters to their default values MAXIMUM UV CLEANTIME Maximum time allowed in kilo hours before UV Service LED lights Parameter name P01 Allowed...

Page 17: ...ter name P05 Allowed values 0 off never sounds alarm to 999 Factory default 30 REMOTE ON OFF Enables or disables the remote On Off switch If enabled keypad On Off no longer controls the unit except to...

Page 18: ...UIDE INOPERATIVE PROBLEM CAUSE SOLUTION Exhaust fan and UVC lamp will not function Control Panel Message No Fan or Error Field Wiring or Breaker Verify field wiring for proper connections Check fuse a...

Page 19: ...EXHAUST PLENUM CLIP C EYE BOLT CLIP B CLIP A COLLAR FIRE DAMPER 2 LINK 3 LINK 1 LINK D 1 REMOVE GREASE FILTERS 2 UNRAVEL S S CABLE AT CLIP A 3 FEED LOOSE END OF CABLE THROUGH EYEBOLT AT CLIP B THEN BA...

Page 20: ...e charges miscellaneous tools material charges and labor charges resulting from inaccessibility of equipment will not be paid by Manufacturer This LIMITED WARRANTY SHALL APPLY ONLY to products that ha...

Reviews: