HTHBHVR8_2A    HTHBHVR8-NF_2A

1000003018 (Rev. D - 09/18)

Installation

For correct and safe installation, please read these instructions completely.

     •     All Installation work must be performed by an authorized service personnel.

     •     Disconnect electrical supply serving the Installation area to reduce risk of electrocution.

     •     Unit not suitable for installations where water jets could be used. 

DANGER

WARNING

     •     Shut off water supply serving the Installation area to reduce risk of water damage.

     •     Ensure proper ventilation by maintaining clearance from cabinet louvers to wall on each side of Cooler as specified in Rough-In.

     •     Never wire compressor directly to electrical supply.

     •     Thoroughly flush all water lines and fittings of all foreign matter before connecting to Cooler.

     •     Warranty is void if Installation is not made in accordance with current Manufacturing instructions.

CAUTION

     •     Hose-sets are not to be used for connecting to water mains.

     •     If inlet pressure is above 100 psig (0.69 MPa), a pressure regulator must be installed in water supply line. Any damage caused by

           reason of connecting this product to water supply line pressure outside it’s rated pressure, is not covered by warranty.

     •     Tools/Items required but not provided.

                 o      Safety Glasses

                 o      Protective Gloves

                 o      Electric Drill

                 o      ¾” (19mm) Wrench or Crescent Wrench

                 o      Utility Knife

                 o      Tape Measure

                 o      Pencil

Installation: Cooler Mounting

  1. Remove wall mounting plate(s) from Cooler. Install Wall Mounting Plate(s) as per Rough-In.

   •     NOTE: Mounting plate(s) MUST be supported securely. Add fixture support carrier if wall will not provide adequate support. 

  2. Install water cooler onto wall bracket and secure to wall.

Installation: Water Line connection

  1. Ensure Mains Water Supply has Water Shut-off Valve with 3/8” (9.5mm) compression outlet.

  2. Connect loose end of supplied 3/8” (9.5mm) unplated copper tube to Water Shut-off Valve. Other end of tube should be connected to inlet of

      Filter head. If not connected, simply insert into inlet fitting on Filter head until positive stop – approximately ¾” (19mm).Then tighten locknut

      handtight to seal.

        •   NOTE: If 3/8” (9.5mm) copper tube must be cut for proper fit, remove all burrs from the outside of tube and re-flush before use.

  3. Install waste trap. Remove the slip nut and gasket from the waste trap and install them on the cooler waste line making sure that the end of

      the waste line fits into the waste trap. Assemble the slip nut and gasket to the waste trap and tighten securely.

  4. It is recommended that the drain trap be insulated to avoid excessive condensation due to chilled water running through the trap.

  5. Turn on building water supply and open Water Shut-off Valve. Check all connections for leaks and correct any found.

Installation: Electrical connection

  1. Rotate fan to insure proper clearance and free fan action.

  2. Connect modular (C-13) end of International Power Cord Set

      (sold separately) into Power Inlet on Cooler and ensure plug-end

      reaches electrical outlet. Do not plug into electrical outlet!

                 o       Center Punch

                 o       ½” Socket & Ratchet Wrench

                 o       5/32” (4mm) Allen Wrench

                 o       Fasteners for wall type

                 o       Water Shut-off Valve with 3/8” (9.5mm)

                          Compression outlet.

                 o       Waste Trap (non-metallic)

230Vac, 50Hz Wiring Diagram

H

 H) Power Inlet

Summary of Contents for HydroBoost HTHBHVR8-25

Page 1: ...er installation keep these instructions in a safe location for future reference Electric supply must be identical in voltage cycle and phase to that specified on nameplate Electrical supply must have...

Page 2: ...upported securely Add fixture support carrier if wall will not provide adequate support 2 Install water cooler onto wall bracket and secure to wall Installation Water Line connection 1 Ensure Mains Wa...

Page 3: ...m MOUNTING HOLES 3 PL 1 4 X 1 2 6mm X 13mm OBROUND HOLE 5 PL HANGER BRACKET 7 178mm 7 178mm 16 5 16 414mm 1 1 4 32mm 1 1 4 32mm HTHBHVR8 ROUGH IN REDUCE HEIGHT BY 3 FOR INSTALLATION OF CHILDREN S ADA...

Page 4: ...Bottle Filler Do not plug into electrical outlet 7 With the power cord waterline and reset button wires through the hole on top of water cooler place Bottle Filler on to mounting bracket on basin NOTE...

Page 5: ...how FLTR 0 The Green LED should be illuminated indicating that the visual filter monitor has been reset SETTING RANGE OF THE IR SENSOR WHERE APPLICABLE Depress the program button for approximately 2 s...

Page 6: ...ses o Protective gloves o Hex drives Service Adjustments 1 Temperature Control Factory set for 50 F 5 10 C 5 water under normal conditions To adjust water temperature turn screw clockwise for colder c...