Installation site
prearrangement
At the mounting and installation phase be sure all safety precautions have been
considered. Always consider how important it is the correct positioning of gas
detectors to get the optimum response.
I
Be careful never to install gas detectors close to air intakes or fans
causing strong air currents.
II
Be sure the detectors are attached to a firm base to prevent vibration
that can damage them, producing unreliable results.
III
Although the electronics comply with the electromagnetic
compatibility rules, it is advised to keep the detectors at a distance
from any radio frequency senders (such as radio links or similar).
IV
Please be also sure that detectors are placed in a convenient location
for future maintenance and calibration requirements.
V
All of the gases lighter than air (Methane, Hydrogen, Ammonia) tend
to spread upwards; the detector should be placed at 30 cm from the
ceiling in order to maximise the effectiveness of the detection.
VI
All of the gases heavier than air (LPG, Butane, Petrol Vapours) tend to
spread downwards; the detector should be placed at 30 cm from the
floor.