ATEX, IECEx and HazLoc Ratings and Classifications 

The Alfred Solenoid Controlled Guard Lock is certified and rated for use within ATEX, IECEx and HazLoc environments of the 

following ratings;

Approvals

IECEx BAS 20.0080X

BAS21UKEX0009X

SGS20ATEX0171X

SGSNA/21/CA/00001X

Specific Conditions of Use

1. 

It is the responsibility of the installation engineer to ensure that a suitable IECEx/ATEX/UKEX equipment certified cable  

    gland is installed in accordance with IEC60079-14, which meets the IP rating of IP67, to ensure that this is maintained on  

    the enclosure. See Electrical Connection section for further detail.

2. 

Flameproof Joints of the Ex Rated Solenoid Module enclosure are not intended to be repaired. 

3. 

If required, any replacement Lid assembly fasteners must be identical to those as supplied by Fortress and as detailed in 

    the 

Lid Assembly Requirements

 section of this document. The specification of these are M8 x 14mm, property class of 

    A2-70 with a minimum yield strength of 700 MPa to ISO 3506, ISO 262, ISO 965-1, and ISO 965-3.

4.

 When used for a Group III application, the adhesive labels and non-metallic coatings may store electrostatic charge and 

    become a source of ignition. Guidance on protection against the risk of ignition due to electrostatic discharge can be found 

    in IEC TS 60079-32-1. Cleaning of the adhesive labels and non-metallic coatings should only be done with a damp cloth.

WARNING

 – Do not open device when an explosive atmosphere is present!

WARNING

 – Do not open device when energised!

The purchaser or Installation Engineer should be aware of any External effects or Aggressive substances that the 

Alfred Solenoid Controlled Guard Lock may be exposed to and should inform Fortress accordingly. 

Symbol Description 

2

Operating Instructions: Alfred Solenoid Controlled Guard Lock

ATEX and IECEx product ratings;
(as per IEC 60079-0)

 

II 2 G  Ex db h IIC T6 Gb

 

II 2 D  Ex h tb IIIC T85°C Db IP67

                 Tamb -20°C to +60°C

North American HazLoc product ratings;

(as per NEC 500, CEC Annex J)

Class I, Division 2, Groups A,B,C,D T4

Class II, Division 2, Groups F,G T110˚C

Class III, Division 2

(as per NEC 505, CEC 18)

Class I, Zone 1, AEx db IIC T4 Gb

Zone 21, AEx tb IIIC T110°C Db IP67

Warning Electricity

Direct Opening Action

Locking monitoring of 

locking elements

Summary of Contents for FORTRESS Alfred

Page 1: ...operating instructions enclosed It must be installed by competent and qualified personnel who have read and understood the whole of this document prior to commencing installation If the equipment is u...

Page 2: ...65 3 4 When used for a Group III application the adhesive labels and non metallic coatings may store electrostatic charge and become a source of ignition Guidance on protection against the risk of ign...

Page 3: ...750mm Can be fitted in two positions at 90 to either hinged or sliding door gates Description Part No Handing Hinged Handle Assembly EXPHL1 Front Integrated handle for guarding applications with hinge...

Page 4: ...21 ALFRED SAFETY SWITCH OPERATING INSTRUCTIONS IMAGES DWG NO SD 00 2 LEFTHAND FACING DIRECTION OF ACTUATOR ENTRY 1 FRONT FACING HEAD 3 REAR FACING 4 RIGHTHAND FACING Head Modules Description Part No H...

Page 5: ...hinery that is required to be isolated before access Safety Key Adaptors Used to provide a personnel key function to prevent unexpected machine start up Extracted Key Adaptor Also used as a personnel...

Page 6: ...dard dustcover Description Part No Extracted Key Adaptor EKL7 Master lock type standard dustcover Description Part No Extracted Key Adaptor EKL3 Standard lock type padlockable dustcover Description Pa...

Page 7: ...olenoid EXPXL416 Power to Unlock device Dual Safety Circuits change state on opening closing of a guarded area or operation of an interlocked key Monitoring circuit on Solenoid action provides feedbac...

Page 8: ...channel Solenoid Voltage N A 24V DC 10 Solenoid Power Rating N A 350mA max 24V DC Solenoid Rating Duty Cycle N A 100 Transient Overvoltages Installation N A Category III Cable Size N A 28 12 AWG Diagn...

Page 9: ...depending on product selection and configuration See specific functioning section below With Solenoid de energised the Internal mechanism of the Power to Unlock Ex Rated Solenoid Module automatically...

Page 10: ...Monitor Circuit opens breaks Safety Circuits remain closed Gate Monitor Circuit remains broken Unlocking De Energise the Solenoid Internal locking mechanism dis engages to remove locking force from th...

Page 11: ...k product An Extracted style Key Adaptor will always be located closest to the Head Module If Extracted style and Safety style Key Adaptors are configured together their operation sequence will combin...

Page 12: ...essinterlocks com THE COPYRIGHT OF THIS DRAWING BELONGS TO FORTRESS INTERLOCKS Ltd THE CONTENT OF THIS DRAWING IS CONFIDENTIAL AND MUST NOT BE DISCLOSED TO ANY 3rd PARTY WITHOUT SPECIFIC WRITTEN APPRO...

Page 13: ...FORTRESS INTERLOCKS Ltd THE CONTENT OF THIS DRAWING IS CONFIDENTIAL AND MUST NOT BE DISCLOSED TO ANY 3rd PARTY WITHOUT SPECIFIC WRITTEN APPROVAL ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED A3 SC...

Page 14: ...ntenance procedures are all easily possible All fixing screws used to mount the complete Alfred Solenoid Controlled Guard Lock product must be permanently prevented from removal If mounting fixings ar...

Page 15: ...ATE 25 02 21 ISSUE 0 ALFRED SAFETY SWITCH OPERATING INSTRUCTIONS IMAGES DWG NO SD 00033 Operating Instructions Alfred Solenoid Controlled Guard Lock 15 Electrical Connection and Installation Tools and...

Page 16: ...Circuit and terminal 13 Solenoid Monitor Circuit Terminal 12 Guard Open Output Signal Control signal produced by the Ex Rated Solenoid Module to indicate that the Machine Guarding is in an open state...

Page 17: ...3 14 INTERNAL EARTHING POINT SHALL BE USED FOR EQUIPMENT GROUNDING CONNECTION FIX WITH M4 FIXING SCREW SUPPLIED SEE OPERATING INSTRUCTIONS FOR DETAILS XPXL471 13 3 4 EXTERNAL EARTHING POINT SHALL BE U...

Page 18: ...ard Lock product If damage or wear is found with an assembly please contact your local Fortress Channel Partner The complete interlock must be replaced after 1 million switching operations Disposal Th...

Page 19: ...the declaration described above is in conformity with the relevant Union harmonisation legislation 2014 34 EU The following harmonised standards and other technical specifications were used in suppor...

Page 20: ...e is in conformity with the relevant Union harmonisation legislation 2014 34 EU The following harmonised standards and other technical specifications were used in support of this declaration Harmonise...