To be TÜV compliant for the German market, please make sure to adjust the sensor as follows:
Number of IR curtains
2
Max. duration of presence detection
1 or higher (min. 1minute)
External Monitoring Enabled
1 (ON)
Sensitivity (size of detection field)
Min. 1.5m depth
IR curtain immunity
1 to 3
High mounting height
(>3m)
If the sensor is installed higher than 3m above the floor, make sure to use the narrow prism
(see chapter “3 Installation” § 6). Also, set the sensor to “High Mounting”:
or
Installation Configuration
High Mounting Height
Rain/Snow
If the sensor is exposed to rain or snow, use the URC (Universal Rain protection Cover)
Set the sensor to presetting 3 or 4 to increase the immunity of the sensor. You can reduce the influence of rain and snow
even more when selecting the RAIN or SNOW mode for the IR curtain immunity:
RAIN mode
SNOW mode
SNOW mode enhanced
Setup
Assisted Setup (~14sec)
Sensor checks the influence of the door leaves to the IR
curtains (performs a door open/door close cycle)
Standard Setup (~4sec)
Sensor only learns its environment
After adjusting the sensor for the first time, it is recommended to launch an “Assisted Setup”. Refer to chapter “3
Installation” § 8.2 for more information about the LED display)
If the IR sensor module “sees” the door movement, move the curtains out of the door leaves.
Access Code
The access code is recommended to set sensors close to each other with remote control. The access code can be
composed of 1 to 4 digits (factory values or no access code : 0 or 0000). No code is required to unlock during the first minute
after powering.
Overlapping
IR-curtains
Overlapping IR-curtains from sensors installed side-by-side may cause disturbances due to crosstalk (interferences).
Select different frequencies on each sensor to avoid crosstalk (see setting "Installation configuration" on p.5).
Attention: avoid curtains that are overlapping by more than 30cm (at 2,2m mounting height, using the wide prism).
No monitoring on IR
curtain
If no monitoring of the IR sensor module is required, but the product you use has the monitoring enabled by default, set the
“Monitoring” parameter to “0”:
External Monitoring Enabled
0 (= OFF)
Only one single
Impulse input on door
controller
If your door controller has only one single impulse input for motion impulse (open the door) and no safety input (keep the
door open), use the “Safety Output Redirection” to transfer the safety detection (IR sensor module) to the motion impulse
output and connect only the motion output to your door controller:
Safety Output Redirection
1 (= transfer presence detection to the motion output)
PULSE monitoring of
safety sensor (beams)
If your door controller monitors its safety sensors using PULSE (ex. RECORD, ATS, DORMA ES-90 EM2/EM3), make
sure you have a PULSE compatible product (ACTIV8 THREE PULSE).
Check the wiring
Push the left push button to release the outputs. The door should close and the LED should switch off.
4 Installation
Tips