TÜV Requirements in 
Germany 

 

 

To be TÜV compliant for the German market, please make sure to adjust the sensor as follows: 

 

Number of IR curtains                             

 

Max. duration of presence detection     

1 or higher (min. 1minute) 

 

External Monitoring Enabled 

1 (ON) 

 

Sensitivity (size of detection field) 

Min. 1.5m depth 

 

 

IR curtain immunity 

1 to 3 

 

 

   

High mounting height 

(>3m) 

 

If the sensor is installed higher than 3m above the floor, make sure to use the narrow prism  
(see chapter “3 Installation” § 6). Also, set the sensor to “High Mounting”: 

 

 

or 

 

 

Installation Configuration  

High Mounting Height 

 

 

   

Rain/Snow 

 

If the sensor is exposed to rain or snow, use the URC (Universal Rain protection Cover) 

 

Set the sensor to presetting 3 or 4 to increase the immunity of the sensor. You can reduce the influence of rain and snow 
even more when selecting the RAIN or SNOW mode for the IR curtain immunity: 

 

  RAIN mode  

 

 

 

SNOW mode 

 

 

 

SNOW mode enhanced 

 

 

 

   

Setup 

 

 

  Assisted Setup (~14sec) 

Sensor checks the influence of the door leaves to the IR 
curtains (performs a door open/door close cycle) 

 

 

Standard Setup (~4sec) 

Sensor only learns its environment 

After adjusting the sensor for the first time, it is recommended to launch an “Assisted Setup”. Refer to chapter “3 
Installation” § 8.2 for more information about the LED display) 
If the IR sensor module “sees” the door movement, move the curtains out of the door leaves. 

 

   

Access Code 

 

The access code is recommended to set sensors close to each other with remote control. The access code can be 
composed of 1 to 4 digits (factory values or no access code : 0 or 0000). No code is required to unlock during the first minute 
after powering.  

 

   

Overlapping  
IR-curtains 

 

Overlapping IR-curtains from sensors installed side-by-side may cause disturbances due to crosstalk (interferences). 
Select different frequencies on each sensor to avoid crosstalk (see setting "Installation configuration" on p.5). 
Attention: avoid curtains that are overlapping by more than 30cm (at 2,2m mounting height, using the wide prism). 

 

   

No monitoring on IR 
curtain 

 

If no monitoring of the IR sensor module is required, but the product you use has the monitoring enabled by default, set the
“Monitoring” parameter to “0”: 

 

  External Monitoring Enabled 

0 (= OFF) 

 

 

   

Only one single 

Impulse input on door 
controller 

 

If your door controller has only one single impulse input for motion impulse (open the door) and no safety input (keep the 
door open), use the “Safety Output Redirection” to transfer the safety detection (IR sensor module) to the motion impulse 
output and connect only the motion output to your door controller: 

 

  Safety Output Redirection 

1 (= transfer presence detection to the motion output) 

 

 

   

PULSE monitoring of 

safety sensor (beams) 

 

If your door controller monitors its safety sensors using PULSE (ex. RECORD, ATS, DORMA ES-90 EM2/EM3), make 
sure you have a PULSE compatible product (ACTIV8 THREE PULSE).  

 

   

Check the wiring 

  Push the left push button to release the outputs. The door should close and the LED should switch off. 

 
 

 
 
 

4 Installation 

Tips 

Summary of Contents for BEA ACTIV8 THREE ON

Page 1: ...otion detection RED LED Presence detection Short flash after a motion or presence detection Monitoring process active ORANGE LED See chapter 5 Troubleshooting 1 Tips Use the Remote Control to adjust the sensor Use the Spotfinder to locate the safety curtains Avoid touching electronical parts Avoid touching optical parts Make sure the operator cover is fixed properly and electrically earthed Avoid ...

Page 2: ...n above 4 Radar motion sensing field width Sensitivity 9 Sensitivity 9 5 Radar motion sensing field depth 15 30 45 30 45 15 0 2 1 0 1 2 1 2 3 1 2 3 15 30 45 Sensitivity 9 2 1 0 1 2 1 2 3 1 2 3 15 45 30 4 4 Sensitivity 9 SENSOR DOOR CONTROLLER 12 24V AC DC Monitoring Input Monitoring Output Beam transmitter Safety Input Beam receiver keep door open Monitored Impulse Input open door Sensor Power Sup...

Page 3: ...rew clockwise To tilt the curtain out turn the screw counterclockwise min 5cm min 5cm 0 4 Keep a minimum distance of 5cm Å between the door and the first curtain Use the Spotfinder accessory to locate and adjust the position of the curtains When mounting one sensor on each side of the door above a highly reflective threshold select different frequencies to avoid crosstalk between the sensors see s...

Page 4: ...Select parameter to check flashes quickly Press Question Mark The number of green flashes indicate the value of this parameter flashes slowly Lock the adjustment session and go back to normal function Press Lock key twice 8 a Important Remote Control adjustments Sensitivity 0 min 9 max Factory value 7 IR curtain immunity 1 normal 2 increased 3 rain mode 4 snow mode 5 snow mode enhanced Output conf...

Page 5: ...process active the sensor learns its environment After finishing the setup process the sensor shows the following behavior RED LED flashing quickly The sensor sees the door movement and can not finish its setup RED LED continuously on The sensor signals a faulty IR monitoring ORANGE LED continuously on The sensor encounters a signal saturation ex due to a highly reflective floor No LED turns on Th...

Page 6: ...ommended to set sensors close to each other with remote control The access code can be composed of 1 to 4 digits factory values or no access code 0 or 0000 No code is required to unlock during the first minute after powering Overlapping IR curtains Overlapping IR curtains from sensors installed side by side may cause disturbances due to crosstalk interferences Select different frequencies on each ...

Page 7: ...le turning the screw counterclockwise The door is not closing LED OFF On Off switch at door control is in wrong position or is faulty Check to insure that On Off switch for door is in the ON or AUTOMATIC position Improper output configuration on the sensor Check the output configuration setting on each sensor Faulty sensor monitoring of the door controller Check if the monitoring mode is ON or PUL...

Page 8: ...essor Spot diameter standard 0 1m max Number of spots 24 or 12 spots by curtain Number of curtains 2 Detection field Width Depth Wide 4 m 2 m Narrow 2 m 2 5 m Width Depth Wide 2 m 0 35 m Narrow 1 m 0 35 m Angle From 15 to 50 in elevation adjustable From 4 to 4 adjustable Output specification Free of potential current source State No detection current source ON Max open circuit voltage 6 5V Output ...

Reviews: