16
Fire detection and evacuation solutions that save lives.
XPander Input/Ouput Unit
The XPander Input/Output unit is a Radio Base Interface and offers up to two monitored input circuits and two relay outputs.
The units are powered by six
‘
AA
’
alkaline batteries.
The XPander Input/Output unit can be used in failsafe operation.
Item Numbers
4110
-
2002 (Single)
4110
-
2003 (Dual)
XPander Input/Output Unit
All data is supplied subject to change without notice.
Specifications are given at 23°C and 50% relative humidity
unless otherwise stated
Technical data
Supply Voltage
3V DC +
Relay Rating
2A at 30V DC
Material
ABS grey plastic
Dimensions and Weight
of Interface
120mm width x 240mm height x 60mm
depth, 620 grams
Environmental
Operating and Storage
Temperature
-
10°C to +55°C
Humidity
0% to 95% relative humidity (no
condensation)
IP rating
65
Electromagnetic
Compatibility
The interface meets the requirements of
BS EN 50 081
-
1 for emissions and BS
EN 50 130
-
4 for susceptibility