Halma Ampac XPander Product Manual Download Page 13

 

13

 

Fire detection and evacuation solutions that save lives.

 

XPander Audible Visual Alarm Indicators

 

The combined device range is designed to provide one point 

of notification and detection. 

 

Combined Sounders and Combined Sounder 
Visual Indicators 

 

XPander  sounders  are  ceiling  mounted  and  use  a  bi

-

directional  monitored  radio  platform  to  communicate.  They 

feature 4 tone pairs, including the Temporal T3 tone, and a 

self  test  which  causes  a  fault  signal  to  be  sent  if  the 

sounders fail to operate. 

 

The  address  of  a  sounder  or  a  combined  sounder/visual 

indicator  is  set  at  the  commissioning  stage  by  means  of  a 

DIL switch. The sounder address is plus one of the address 

set.  The  sounders  and  combined  sounder/ visual indicators 

are powered by two packs of batteries, one with three 

AA

” 

and one with three 

C

” 

size alkaline batteries which provide 

a  working  life  of  typically  3

-

5  years.  The  fiveyear  life 

includes  weekly  tests  and  a  half

-

hour  sounding  in  a  fire 

condition. 

 

The  Combined  Sounders  and  Sounder  Visual  Indicators 

incorporate  audible  and  visual  alarm  indicators  within  one 

unit.

 

 Sound output: 

 

74dB (low) 

 

 

 

 

87dB (high) 

 

Individual parts may be ordered separately 

 

These products are tested and approved to the following 

standards: AS 7240

-

5, AS 7240

-

7, and AS 7240

-

25.

 

Item Numbers 

 

4111

-

1303

 

XPander Combined Sounder 
and Optical Detector

 

Item Numbers 

 

4111

-

1501

 

XPander Combined Sounder 
Visual Indicator (Clear) and 
Heat Detector (Class A1R)

 

Item Numbers 

 

4111

-

1401

 

Combined Sounder Visual 
Indicator (Red) and Heat 
Smoke Detector 

 

Product Variants

 

Part Number

 

Product Name

 

4111

-

1403 (Optical) 

 

XPander Combined Sounder Visual Indicator (Red) and Optical Smoke Detector

 

4111

-

1401 (A1R) 

 

XPander Combined Sounder Visual Indicator (Red) and Heat Detector (Class A1R) 

 

4111

-

1402 (CS) 

 

XPander Combined Sounder Visual Indicator (Red) and Heat Detector (Class CS) 

 

4111

-

1404 (Multi)

 

XPander Combined Sounder Visual Indicator (Red) and  Multisensor Detector

 

4111

-

1503 (Optical) 

 

XPander Combined Sounder Visual Indicator (Clear) and Optical Smoke Detector 

 

4111

-

1501 (A1R) 

 

XPander Combined Sounder Visual Indicator (Clear) and Heat Detector (Class A1R) 

 

4111

-

1502 (CS) 

 

XPander Combined Sounder Visual Indicator (Clear) and Heat Detector (Class CS) 

 

4111

-

1504 (Multi)

 

XPander Combined Sounder Visual Indicator (Clear) and Multisensor Detector

 

4111

-

1303 (Optical) 

 

XPander Combined Sounder and Optical Smoke Detector 

 

4111

-

1301 (A1R) 

 

XPander Combined Sounder and Heat Detector (Class A1R) 

 

4111

-

1302 (CS) 

 

XPander Combined Sounder and Heat Detector (Class CS) 

 

4111

-

1304 (Multi)

 

XPander Combined Sounder and  Multisensor Detector

 

Summary of Contents for Ampac XPander

Page 1: ...Product Guide Ampac addressable range expansion Wireless Minimises disruptions to buildings and occupants Enables rapid retrofit or temporary solution AS7240 25 Dual batteries for enhanced integrity...

Page 2: ...either impracticable or undesirable It may also be used in sites with discrete buildings which need to be connected to a central control panel but where wiring might present problems XPander has been...

Page 3: ...here to Use Optical Detectors 10 Detector Operating Principles 10 Technical Data 10 Contents XPander MultiSensor Smoke Detector 11 Where to Use MultiSensor Detectors 11 Detector Operating Principles 1...

Page 4: ...comprises of two types of interface the Radio Hub and the Radio Communications Cluster or RCC The Radio Hub communicates with the control panel using the XP95 addressable two wire power and communica...

Page 5: ...s for ease of installation Radio Communications Fire detection systems are life saving systems and must therefore be highly reliable in use Radio communications have been developed to a point where hi...

Page 6: ...included in the booklet supplied with the survey kit and is also available from the Ampac website Training in the technique of surveying a site and designing an XPander system is mandatory Optical Sm...

Page 7: ...arily developed to enable fully wireless fire alarm systems to be designed providing almost unlimited configuration and installation options With each Hub capable of supporting up to 500 field devices...

Page 8: ...Diversity Interface transmits and receives signals via the integral Diversity Aerials which require no adjustment or maintenance This product is tested and approved to the AS7240 25 standards Item Nu...

Page 9: ...adio Hub supports up to four loops of detection and alarm devices An integral LCD display is provided on the Radio Hub along with function buttons to allow programming and diagnostics to be carried ou...

Page 10: ...articles over a wide range of angles The optical arrangement comprises an infrared emitter with a prism and a photo diode at 90 to the light beam with a wide field of view The detector s microprocesso...

Page 11: ...Photo electric detection of light scattered by smoke particles over a wide range of angles The optical arrangement comprises an infra red emitter with a prism and a photo diode at 90 to the light beam...

Page 12: ...measures the air temperature every 2 seconds A microprocessor stores the temperatures and compares them with preset values to determine whether a fixed upper limit the alarm level has been reached In...

Page 13: ...are tested and approved to the following standards AS 7240 5 AS 7240 7 and AS 7240 25 Item Numbers 4111 1303 XPander Combined Sounder and Optical Detector Item Numbers 4111 1501 XPander Combined Sound...

Page 14: ...e with three C size alkaline batteries which provide a working life of typically 3 5 years The three year life includes weekly tests and a half hour sounding in a fire condition The Sounder Visual Ind...

Page 15: ...nual Call Points are supplied with a resettable operating element as standard The call point uses the priority interrupt feature to give a fast response on operation This product is tested and approve...

Page 16: ...Output Unit All data is supplied subject to change without notice Specifications are given at 23 C and 50 relative humidity unless otherwise stated Technical data Supply Voltage 3V DC Relay Rating 2A...

Page 17: ...Adding Devices to the XPander Interface Up to 31 wireless detectors or alarm signalling devices may be assigned to a single interface Prior to adding devices to the Interface batteries must be enabled...

Page 18: ...s Eliminates cable problems Minimises disruption Enables rapid retrofit Modern styling Loop powered interface 915MHz Wireless addressing Radio base with wireless circuitry and battery compartment Auto...

Reviews: