9.6 Replacing the filter on air filter LF-AD-x
Figure 104:
Replacing the LF-AD filter inserts
Perform the following work steps to clean or replace the filter inserts:
► Only perform the following work with the device disconnected from the
mains.
► Loosen the four screws and remove the housing cover.
► Remove the filter inserts and visually check for dirt. The filter inserts can
be cleaned if the dirt level is low. The filter inserts must be replaced in
case of a high level of dirt.
► Carefully clean off any dust deposits from the inside of the housing. Now
insert the cleaned or new filter inserts in the correct order. The correct
order can be found on the information sign on the housing base.
► Put the housing cover back on and tighten the screws.