HALLMARK INDUSTRIES INC 

Shallow Well Jet  Pumps

 

624 Estes Ave, Schaumburg, IL 60193, USA             

www.hallmarkind.com

 

 

Discharge

 

Pipe and Pressure Tank Connections

 

Pre-Charge Tank Connection 

(Figure 4)

 

To Household

 

Water System

 

1.

 

Install two tees in the pump discharge port (see Figure  4). The pipe size

 

must be at least  as large as the discharge port.

 

Run a pipe or reinforced hose from one arm of the first tee to the port 
on the pre-charged tank.

 

Connect the other end of the discharge tee to your plumbing system. 
Cap the tee with  a threaded plug or a pressure gauge.

 

Check the pre-charge  of air in the tank with  an ordinary tire gauge. The 
pre-charge  should be 2 PSI less  than the cut-in setting of the pump

’s 

pressure switch. The pre-charge  is measured when there is no water 
pressure in the tank. Your new pump has a 30/50 PSI switch, so adjust 
the tank pre-charge  pressure to 28 PSI.

 

Pump Priming 
Tee with Plug 
or Gauge

 

2.

 

3.

 

From

 

Well

 

Pressure

 

Switch

 

4.

 

Congratulations! You have just completed the tank connection for your jet

 

pump. Please go to Page 5 for electrical hookup.

 

Standard Tank Connection 

(Figure 5)

 

1.

 

2.

 

Install one tee in the pump discharge port (see Figure  5).

 

Run a pipe from the pump discharge port to the inlet  port of your tank. 
The pipe size must be at least  as large as the discharge port.

 

Install a tee in the suction pipe near the pump. Install a reducer bushing 
down to 

1/8”  NPT in the tee. Run tubing from the tee to the port on the 

AVC mounted on the tank. Seal all pipe joints with T

eflon™ tape. See 

instructions provided with  the tank and the AVC for details.

 

Figure 4: Pre-charged Tank Connections

 

3.

 

Congratulations! You have just completed the tank connection for your jet

 

pump. Please go to Page 7 for electrical hookup.

 

To Household

 

Water System

 

Air Volume

 

Control

 

Pump Priming

 

Tee and Plug

 

Pressure     or Gauge

 

Air Volume

 

Control Tube

 

Switch

 

From

 

Well

 

Figure 5: Standard Tank Connections

 

 

Sealing Pipe Joints

 

Use only 

1

Teflon

™ tape or Teflon™ based joint  compounds for 

making all threaded connections  to the pump itself. 

Do not

 

use pipe  joint compounds on plastic  pumps: 

they can react 

with  the plastic in pump components. Make sure that all pipe 
joints in the suction pipe are air tight as well  as water tight. 

If 

the suction pipe can suck air, the pump will  not be able to pull 
water from the well.

 

1  

E. I. DuPont de Demours and Company Corporation, Delaware

 

 

 

 

 

HALLMARK 

INDUSTRIES 

INC.

Summary of Contents for MA0345X-9

Page 1: ...uttered and properly lighted store properly all unused tools and equipment Keep visitors at a safe distance from the work areas result in death or serious injury indicates a hazard which if not avoide...

Page 2: ...the well as possible Use the fewest possible fittings especially elbows when connecting the pipe from the well point to the pump suction port The suction pipe should be at least as large as the suctio...

Page 3: ...cially elbows in the suction pipe The suction pipe should be at least as large as the suction port on the pump Assemble a foot valve and suction pipe see Figure 3 Make sure that the foot valve works f...

Page 4: ...2 Install one tee in the pump discharge port see Figure 5 Run a pipe from the pump discharge port to the inlet port of your tank The pipe size must be at least as large as the discharge port Install a...

Page 5: ...ly wires There must be a solid metal connection between the pressure switch and the motor for motor grounding protection If the pressure switch is not connected to the motor connect the green ground s...

Page 6: ...all the trapped air out of the piping A pump lifting water 25 may take as long as 15 minutes to prime After the pump has built up pressure in the system and shut off check the pressure switch operati...

Page 7: ...allow Well Jet Pumps 624 Estes Ave Schaumburg IL 60193 USA www hallmarkind com For reference only We do not stock spare parts Parts and repair Stainless steel jet pump Cast iron jet pump H A L L M A R...

Page 8: ...ck valve or foot valve is stuck shut Replace check valve or foot valve Pipes are frozen Thaw pipes Bury pipes below frost line Heat pit or pump house Foot valve and or strainer are buried in sand or m...

Page 9: ...t closer to the motor by hand Figure 1 STEP 2 Open the pressure switch cover flip the rubber grummets cone shape is now outside Figure 2 STEP 3 Connect the motor s cable wires to the pressure switch F...

Page 10: ...s exposed Figure 4 STEP 5 Adjust the pressure switch s in out psi to the desired setting according to the instruction on the back of pressure switch cover STEP 6 Put the pressure switch cover back on...

Reviews: