listed may result in objectionable air noise in the ducts.
Table 3 Recommended Maximum Duct Velocities, Feet Per Minute (FPM)
Main Ducts*
Branch Ducts
Application
Supply Return Supply Return
Apartments
900
700
600
600
Auditoriums 1200 1000 1000 800
Banks
2000
1500
1600
1200
Hotel
Rooms
1500 1300 1200 1000
Libraries
2000
1500
1600
1200
Meeting
Rooms
2000 1500 1600 1200
Offices
2000
1500
1600
1200
Residences 900 700 600 600
Restaurants
2000
1500
1600
1200
Retail
Stores 2000 1500 1600 1200
*When sound control is critical use branch duct velocities
Table 4 Duct Area Required at Listed Flow Conditions
CFM Area
Sq. In.
600FPM
Area
Sq. In.
800FPM
Area
Sq. In.
1000FPM
Area
Sq. In.
1200FPM
Area
Sq. In.
1600FPM
Area
Sq. In.
2000FPM
50
12
100
24 18 14 12
150
36
27
22
18
14
200
48 36 29 24 18 14
250
60
45
36
30
23
18
300
72 54 43 36 27 22
400
96
72
58
48
36
29
500
120 90 72 60 45 36
750
180
135
108
90
68
54
1000
240 180 144 120 90 72
1250
300
225
180
150
113
90
1500
360 270 216 180 135 108
1750
420
315
252
210
158
126
2000
480 360 288 240 180 144
Note: For Systems not over 100 feet equivalent length. Do not apply this table to duct systems
which exceed 100 equivalent feet in length. For longer systems refer to ACCA Manual D.
Incorrectly sized ducts can result in unsafe or uncomfortable operation.