ISOLGUARD HIG93, HIG93/L, HIG94 

 

  V5.8/23 

HAKEL spol. s r.o. Hradec Králové                     

www.hakel.com

                                                               

Page 9 / 15 

5.1 

Displayed information HIG93, HIG93/L, HIG94 

Opening text

 

It is displayed for a short time after switching ON the module. The name of the module and software version is displayed. After 
the insulation status measuring is started, the measured value of insulation resistance is displayed automatically. 

Measured value of insulation resistance

 

It is displayed in a range as specified in the table of technical characteristics in units of kΩ or MΩ. The value is rounded to 
units of kΩ within the adjustable critical insulation resistance range and to tens of kΩ if lying beyond that range. 
Pressing 

TEST

 push-button activates test of the device, pressing 

MENU

 push-button displays parameter settings menu. By 

pressing  the  middle  push-button  current  temperature  inside  the  module  is  indicated  in  the  upper  part  of  the  display.  The 
signalling relay's status is indicated by the symbol of contact. If both relays are released (there is no fault in the monitored 
power supply system) the open contact is displayed. If there is 

R

crit1

 or 

R

crit2

 fault signalled, the close contact is displayed. 

In a case the non-zero value for the time t

ON

 (time until the fault signalling) is set, then when 

R

isol

 drops below the 

R

crit

 value 

the countdown of the time t

ON

 starts. The display shows the time until fault signalling. After the time is expired, the fault is 

signalled. 

Insulation monitoring device test  

Test may be performed by pressing push-button on the module, by remote 

TEST

 push-button or by the ISOLGUARD RS485 

communication line order. 
Testing of the insulation monitoring device is performed for 5 seconds or during the time of holding the button. The insulation 
resistance  value  is  set  lower  than 

R

crit1 

and 

R

crit2

.  Invoked alarm is signalled  by  indicator lamp 

FAULT1, FAULT2 

and  by 

FAULT1

 and 

FAULT2

 signalling relays’ status according to

 Set Relay FA

 parameter. The insulation resistance value is not 

shown on the display while testing. 
If the push-button on the module is used to initiate the test, then the test starts running immediately. 
When using the remote test push-button, the test starts after 

t

TEST

 parameter delay. When the 

t

TEST

 value is set greater than 

zero the display is recovered immediately after pressing the remote test push-button and test is performed after 

t

TEST

 parameter 

delay. 
Remote test via the communication line is performed immediately after receiving the order and takes 5 seconds. If the 

FAULT

 

memory is set (

Mem.FAULT

 menu), the signal relay remains in a status of alarm indication even after the test is over, until it 

is released by the operator pressing the button on the module. It is also possible to release the relay by an order from the 
communication line in the case of remote test via communication line. 
The initiation and termination of the device test is indicated by a short display flash. 

FAULT

 

memory 

This parameter is set in the menu as 

Mem.FAULT

.  

If this parameter is set to 

YES,

 the 

FAULT1

FAULT2

 relay stays in the fault signalling status even after insulation resistance 

fault termination and the word 

DEBLOCK

 appears on the display. It is possible to release the relay by pushing device’s middle 

button S2. This push-button can be also used when locked device is indicated by the padlock symbol on the display. 

FAULT1

FAULT2

 relay can be also released by the order from the communication line.  

The usage of the 

FAULT

 memory including 

FAULT

 signalling status after termination is defined by the user. 

Parameter settings Menu  

Menu to set one of the following values can be selected by using push-buttons arrow up and down  

 

display of device’s set parameters, menu 

Info

 

monitored critical resistance, menu 

Set R

crit1, 

Set R

crit2

.  

 

insulation resistance hysteresis, menu 

Set R

hyst

,  

 

delay in response of signalling the fault, menu 

Set t

ON

,  

 

external inductor resistance, menu 

Set TL

ext

.

,  

 

delay in start of module test by remote test push-button, menu 

Set t

TEST

 

 

FAULT 

memory parameter, menu 

Mem.FAULT

 

 

device addresses on the RS485 bus, menu 

SET 485ADDR

 

 

terminating resistance 

R

te

 of the RS485 bus in the device, menu 

Set 485R

te

 

 

FAULT1

 and 

FAULT2 

relay status when insulation status fault, menu 

Set Relay FA

  

 

device’s control buttons can be locked, menu

 Lock Up

 

For initiating of all menus use the push-button 

SEL

 and for exit select 

ESC

.  

Information menu  

Displays control program version of HIG93, HIG93/L, HIG94 and set operation parameters of the device. Serial number of the 
device is also displayed. For exit select the push-button ESC. 

Menu set R

crit1

,

 

R

crit2

 

 

New value of the critical insulation resistance is set in kΩ by pressing or holding the 

+

 or 

 push-buttons. The value can be set 

in the range of 0,1 kΩ to 90 kΩ for HIG93/L, 5 kΩ to 300 kΩ for HIG93 or in the range of 200 kΩ to 900 kΩ for HIG94. New 
value is saved by long holding the 

ESC/SET

, pressing this push-button shortly ends setting procedure and 

R

crit

 value remains 

unchanged. Both 

R

crit1

R

crit2

 values can be set independently in the whole value range. 

Summary of Contents for ISOLGUARD HIG93

Page 1: ...LGUARD HIG93 HIG93 L HIG94 V5 8 23 HAKEL spol s r o Hradec Kr lov www hakel com Page 1 15 Insulation monitoring device ISOLGUARD HIG93 HIG93 L HIG94 Operating instructions Document s name DOK 70915 V5...

Page 2: ...ion 5 Picture 2 Connection of HIG93 94 device 7 Picture 3 Connection of HIG93 94 device 7 Picture 4 Displayed information 8 Picture 5 Insulation resistance fault evaluation 11 Picture 6 Insulation sta...

Page 3: ...1 1 Variants of devices ISOLGUARD HIG93 HIG93 L HIG94 Type Display Menu Signalling relay 1 Signalling relay 2 Range of displayed value Critical insulation resistance Communication bus bar MDS D connec...

Page 4: ...c Outputs Two signalling relays with switching contact electric strength to the internal circuits electric strength to the supply circuits 250 V AC 1 A 3750 Vrms 3750 Vrms Communication line RS485 typ...

Page 5: ...u is shown on the display When the insulation resistance Risol is viewed it activates the parameter setting menu Within the parameters setting menu the prolonged pressing of this push button terminate...

Page 6: ...connections of the insulation monitoring Device Terminals A B SH These terminals are intended for connection of galvanic isolated communication line ISOLGUARD RS485 Individual insulation monitoring de...

Page 7: ...FAULT2 FAULT1 S1 S2 S3 SH B A FAULT2 FAULT1 MENU 1 2 3 4 5 6 PE L1 L1 L2 PE L2 L3 N L3 TL400 L1 L2 L3 CENTRE Rtl ext TEST ALARM 2 ALARM 1 RS485 ISOLGUARD PE 4 Recommended connection of HIG93 HIG93 L...

Page 8: ...C SET Relay Logic ESC SET N C FAULT ESC SET Picture 4 Displayed information 5 Information on the display Operating principles The meaning of the push buttons in each menu is shown on the display Press...

Page 9: ...ation line is performed immediately after receiving the order and takes 5 seconds If the FAULT memory is set Mem FAULT menu the signal relay remains in a status of alarm indication even after the test...

Page 10: ...label as Rin Typical values for three phase HAKEL inductors are as follows TL400 4 5 k TL500 4 5 k TL600 4 5 k TL1600 12 5 k TL6003 19 6 k Exact values may be obtained by measuring the inductor s wind...

Page 11: ...LT2 is only terminated when the insulation resistance increases above the value Rcrit1 Rhyst or Rcrit2 Rhyst Signalling relay is released and FAULT1 FAULT2 signalling is terminated The following left...

Page 12: ...assigned by the MASTER station In practice the communication proceeds in such a way that the MASTER station sends requests subsequently to all connected units and the SLAVE stations response The acces...

Page 13: ...nt data determining the status of this measurement e g fault occurrence Parameter data are extended of priority character determining the importance of the set parameter This character divides paramet...

Page 14: ...20 20 20 Delay in response of signalling the fault Set tON tON 0 sec 0 sec 0 sec External inductor resistance Set TLext Rtl ext 0 k 0 k 0 k Delay in device test start by remote test button Set tTEST t...

Page 15: ...and service It is necessary to follow specified conditions for reliable operation do not expose the device to rough handling keep it clean and ensure maximum admissible temperature of the environment...