Menu set R
hyst
New value of the critical insulation resistance hysteresis is set in % by pressing or holding the
+
or
-
push-buttons. The setting
range of this value is 0 to 100 %
R
crit
. New value is saved by long holding the
ESC/SET
, pressing this push-button shortly
ends setting procedure and the
R
hyst
value remains unchanged. The hysteresis level in % applies to both of the critical
insulation resistance levels
R
crit1
and
R
crit2
.
Menu set t
ON
time
New value of the delay in response of
FAULT1
or
FAULT2
is set in seconds by pressing or holding the
+
or
–
push-buttons.
The value can be set in the range of 0 to 60 sec. New value is saved by long holding the
ESC/SET
, pressing this button shortly
ends setting procedure and
t
ON
value remains unchanged.
Menu set TL
ext.
External inductor connected in front of the HIG93, HIG93/L, HIG94 device is necessary when monitoring higher voltages, see
recommended connection diagrams. Value of
R
tl.ext
DC resistance of the connected inductor winding is set in this menu. This
value must be set zero in case of application without the external inductor.
New value of the
R
tl.ext
resistance is set in kΩ to one decimal place by pressing or holding the
+
or
–
push-buttons. The value
can be set in the range of 0 to 20,0 kΩ. New value is saved by long holding the
ESC/SET
, pressing this button shortly ends
setting procedure and
Rtl.ext
value remains unchanged.
The value of
R
tl.ext
inductor’s DC resistance winding is indicated on the inductor’s label as
R
in
. Typical values for three-phase
HAKEL inductors are as follows: TL400 4,5 kΩ, TL500 4,5 kΩ, TL600 4,5 kΩ, TL1600 12,5 kΩ, TL6003 19,6 kΩ. Exact values
may be obtained by measuring the inductor’s winding resistance with interconnected L outlets at the operational temperature
of the inductor.
Menu set t
TEST
time
New value of the delay in module test start by pressing remote test push-button is set in seconds by pressing or holding the
+
or
–
push-buttons. The value can be set in the range of 0 to 6 seconds at 0,1 second step. New value is saved by long holding
the
ESC/SET
, pressing this button shortly ends setting procedure and
t
TEST
value remains unchanged.
When
t
TEST
value setting is greater than 0 the display is re-activated immediately after pressing the remote test button.
Menu Mem.FAULT
Menu for setting the
FAULT1/FAULT2
memory. This parameter can be set to
YES
, when the
FAULT1
/
FAULT2
relay remains
in alarm signalling status even after the fault is eliminated and the button on the device must be pressed to release the relay.
Parameter can be also set to
NO
without fault memorizing. An order through the RS485 communication line can also release
the relay.
Menu Set Relay FA
FAULT1
and
FAULT2
relay status when insulation status fault occurs is set in this menu. This parameter can be set to
N/C
or
N/O
value. The meaning is given in the terminals’ description, page 5.
Menu Lock Up
Menu is intended for locking the device's control push-buttons. When selecting this menu, button combination for unlocking
the module is displayed while holding down the push-button. Measured
R
isol
value and lock symbol are displayed after exiting
the menu. The module is unlocked while holding the middle and right push-button at the same time for more than 5 sec.