Haiwell PLC - Analog Module User Manual

4 / 18

3

RJ45 Ethernet indicator:

there are two Ethernet LEDs, green and yellow, as shown on the picture:

Color

Status description

Green light is long bright

Physical connection of TCP module and external device is normal;

Green light goes out

TCP module fails to connect with external device or the module itself is abnormal

Yellow light blinks

TCP module is connected to an external device normally, and blinking frequency

indicates the data transmission speed. When speed is fast, human eye is not easy

to distinguish, at this time, yellow light is long bright.

Yellow light goes out

No data transmission communication of TCP module and external device

3. Power Supply Specification

4. Environmental Specifications for Product

Item

Environment Specification

Temperature/Humidity

Operating temperature:0~+55

Storage temperature:-25~+70

Humidity: 5~95%RH, No condensation

Vibration Resistance

10~57 HZ, amplitude=0.075mm, 57HZ~150HZ acceleration=1G, 10 times each for X-axis, Y-axis and Z-axis

Impact Resistance

15G, duration=11ms, 6 times each for X-axis, Y-axis and Z-axis

Interference Immunity

DC EFT:±2500V

Surge:±1000V

Over Voltage Resistance

1500VAC/1min between AC terminal and PE terminal, 500VAC/1min between DC terminal and PE terminal

Insulation Impedance

B

etween AC terminal and PE terminal

@500VDC,>=5

,

all input/output points to PE terminal @500VDC

Operating environment

Avoid dust, moisture, corrosion, electric shock and external shocks

5. Analog Input (AI) Specification

Item

Voltage input

Current input

Input range

-10V~+10V

0V~+10V

0V~+5V

1V~+5V

0~20mA 4~20mA

Resolution

5mV

2.5mV

1.25mV

1.25mV

5μA

Input impedance

6MΩ

250Ω

Maximum input range

±

13V

±

30mA

Input indication

LED light ON means normal ,OFF means external disconnect

Response time

5ms/4 Channel

Digital input range

12 bits,Code range:0~32000(H series module 16 bits A/D convert)

Precision

0.2% F.S

Power supply

MPU use internal power supply, extend module use external power supply 24VDC ±10% 5VA

Isolation mode

O

ptoelectronic isolation,Non-isolation between Channel

s

, between analog and digital is optoelectronic isolation

Power consumption

24VDC ±20%,100mA(maximum)

6. Analog Output (AQ) Specification

Item

Voltage output

Current output

Output range

-10V~+10V

0V~ +10V

0V~+5V

1V~+5V

0~20mA

4~20mA

Resolution

5mV

2.5mV

1.25mV

1.25mV

5uA

5uA

Output load impedance

1KΩ@10V

≥500Ω@10V

≤500Ω

Output indication

LED ON means normal

Drive capability

10mA

Response time

3ms

Digital output range

12 bits,Code range:0~32000(H series module 16 bits D/A convert)

Precision

0.2% F.S

Power supply

MPU use internal power supply, expansion modules use external power supply 24VDC ±10% 5VA

Isolation mode

Optoelectronic isolation,Non-isolation between Channels ,between analog and digital is optoelectronic isolation

Power consumption

24VDC ±20%,100mA(maximum)

Item

DC Power Supply

AC Power Supply

Power supply voltage

24VDC

-15%~+20%

100~240VAC

Power supply frequency

——

50~60Hz

Instantaneous surge

MAX 20A 1.5ms @24VDC

20A 1.5ms MAX @220VAC

Power loss time

10ms or less

20ms or less @220VAC

Fuse

0.3A, 250V

2A, 250V

24V Output voltage (for input and expansion)

None

24V, -15%~+15%, 200mA (Max)

Isolation Type

No Electrical isolation

Transformer isolation or optoelectronic

isolation,1500VAC/1 minute

Power Protection

DC input power polarity reverse, over

voltage protection

DC 24V output over current protection

Summary of Contents for S04AI

Page 1: ...Xiamen Haiwell Technology Co Ltd www haiwell com Haiwell PLC User Manual Programmable Logic Controller Analog Module User Manual Application Case...

Page 2: ...skills 10 1 4 Display analog value on SCADA HMI 10 1 5 When the engineering value is not used the default code value is 0 32000 11 1 6 Module CR code application example Read the module channel disco...

Page 3: ...rallel port in communication Green jitter indicator on 30ms and off 30ms Parallel power supply not enough must connect to external power supply Without serial or parallel port in communication Yellow...

Page 4: ...V 5V 1V 5V 0 20mA 4 20mA Resolution 5mV 2 5mV 1 25mV 1 25mV 5 A Input impedance 6M 250 Maximum input range 13V 30mA Input indication LED light ON means normal OFF means external disconnect Response ti...

Page 5: ...AI0G AI1I GND AI1V AI1G B AI2I AI3I AI2V AI3V AI2G AI3G AI0I A AQ0V AQ0G AQ1I GND AQ1V AQ1G B AQ2I AQ3I AQ2V AQ3V AQ2G AQ3G AQ0I A AI0V AI0G AI1I GND AI1V AI1G B AQ0I AQ1I AQ0V AQ1V AQ0G AQ1G AI0I A S...

Page 6: ...engineering lower limiting value input channel 2 zero point correction value 1DH channel 1 engineering upper limiting value channel 1 engineering upper limiting value Channel 1 2 input disconnection a...

Page 7: ...2AH channel 2 engineering upper limiting value channel 2 engineering upper limiting value output channel 1 output value 2BH channel 3 engineering upper limiting value channel 3 engineering upper limi...

Page 8: ...r a better heat dissipation do not mount PLC to a position near to the bottom top of the cabinet Do not mount PLC in vertical direction Expansion Module Wiring Connections between expansion modules an...

Page 9: ...the module is added external power supply it can still work this time the module will automatically determine and give priority to external power supply 1 2 The analog need t be written any conversio...

Page 10: ...program of PLC can be written as follows 1 4 Display analog value on SCADA HMI If the configuration touch screen text and other PC software want to display the current pressure only need to set three...

Page 11: ...ed to check the use of engineering value so that the analog will be very convenient without writing any program 1 6 Module CR code application example Read the module channel disconnection alarm In th...

Page 12: ...roduce the operation key points and techniques 2 1 Module power supply When the module is used as remote IO there are two optional models of 24VDC and 220VAC such as S08AI model for the DC 24V power s...

Page 13: ...n be configured via MODW instructions through the serial communication 2 5 Parameter configuration example The module is configured by programming software remote module tool Hardware connection 1 Thr...

Page 14: ...e found and achieve parameter configuration Click to exit enter the configuration interface as shown below We can change the module name address IP subnet mask baud rate data format and other communic...

Page 15: ...address is 1 baud rate is 19200 data format is N 8 2 RTU The program of PLC reads the 4 channel liquid level values is as follows The host PLC reads the 4 channel liquid level values of S04AI by Modb...

Page 16: ...ng is 50 0 2 8 Remote IO application example Ethernet mode PLC read and write each channel input and output values of S08XA e 1 Hardware wiring PLC and module Ethernet port connected with a shielded n...

Page 17: ...n choose serial port or Ethernet according to the module which supports the Ethernet or RS485 this example for serial port the serial port number of USB to 485 is COM6 as shown below Default parameter...

Page 18: ...ding channel variable values If you need to display the decimal places it can set the corresponding decimal places on the display primitive As shown below Thanks for choosing Haiwell PLC If you have a...

Reviews: