background image

Only operates if TT=OC. This is the heating temperature that will be used in 

Occupied 

mode” and will temporarily replace the user heat set point while the TT terminals are 
shorted together.   

oC=OFF Occupied Mode Cool Set. 

Only operates if TT=OC. This is the cooling temperature that will be used in 

Occupied 

mode” and will temporarily replace the user cool set point while the TT terminals are 
shorted together.   

SP=2 Stage 1 Span 

Hysteresis for Stage 1. (difference between heating and cooling turning on and off) Sp=1 
0.5c SP=2 1.0c Sp=3 1.5c.   

Sd=2 Stage 2 Span 

Hysteresis for Stage 2. (difference between heating and cooling turning on and off) Sd=1 
0.5c Sd=2 1.0c Sd=3 1.5c.   

DT=35 Upstage delay time 

Time in minutes before next stage of heating or cooling is to be called. Delay only 
operates if stage trip temperature has not yet been reached. Adjustable between 10 ~ 90 
Minutes in 5 minute steps.   

OS=0 Optimised Start/stop. (Adaptive Recovery)   

OS=0 

Optimised start/stop function Off.   

OS=1 

Optimised start/stop function running. 

C2=0.0 Calibration Remote Sensor   

Calibration Offset for the TT terminal temperature sensor. Adjustable range +/

5 deg C 

(+/

9 F).   

Co=0(41F) Cooling OFF temperature. 

Only operates if TT=OA and outside temperature sensor is fitted. Outside air 
temperature below this value will force the cooling function OFF. Adjustable between 5 
~37c. (41~98F).   

Ho=35 (95F) Heating OFF temperature. 

Only operates if TT=OA and outside temperature sensor is fitted. Outside air 
temperature above this value will force the heating function OFF. Adjustable between 5 
~37c. (41~98F).   

HB=37 (98F) High Balance Point. 

TT=OA, the outside temperature sensor must be fitted and Sw 1=off. 2nd (or 3rd) stage 
heating is locked out when the outside air is above this temperature. Adjustable between 
5 ~37c. (41~98F).   

LB=9.5 (15f) Low Balance point. 

TT=OA, the outside temperature sensor fitted, H3=EH, Sw 1=off and Sw2=on. Outside 
temperatures below this value will automatically select Emergency Heat mode. 
Adjustable between 

9.5 ~37c. (15~98F).   

Ft=off Filter warning time Return air filter cleaning warning time.   

Adjustable between off and 900 hours. Ad=07 Modbus Address. Modbus 
communications address   
Cd=01 Commissioning Mode..   
Cd=0 

Commissioning mode is OFF. 

Cd=1 

All time delays are off or reduced to a very small value.   

tS=0 Factory test mode   

TS=0 

Factory test Mode OFF. TS=1 

Display configuration code.* TS=2 

Step 

cycle all relays in sequence, 1 2 3 4 5 etc.   

Control logic   

Single Set Point mode Two Set   
Point mode This simple diagram   
provides a general insight into   
the control logic of the A4100   
thermostat. It attempts to   
describe the action of the   
DB=XX, the SP=XX and SD=XX   
advanced installer control   
capabilities in both two set point and single set point mode. By adjusting these three 
values to suit the needs of the user or equipment extremely tight temperature control can 
be achieved, or a more energy efficient temperature control profile can be set.   
In single set point mode (sw8=off) the individual heating and cooling set points are 
replaced by a 

Dead Band” where the heating and cooling differential is controlled by a 

installer set value. This is the simplest method of temperature control.   

Commissioning 

As with any thermostat, commissioning ensures that the thermostat and the equipment 
connected to it are operating correctly and as expected. Although the A4100 is a 
multifunctional thermostat, commissioning is quite a simple process. Follow the steps 
detailed below and use the trouble shooting guide if you encounter a problem. 
When the thermostat is fitted to the base plate and when 24VAC power is first applied, 
the LCD should briefly show all available segments (a LCD function test), then display 
the time and operating mode etc.   
The A4100 is fitted with a number of safety and energy saving time delays. If desired,   

these can be disabled for commissioning purposes by entering the 
installer mode and setting the CD=00 value to read CD=01. After exiting 
the installer menu you will note a 

Spanner” icon flashing on the LCD to   

remind you that commissioning mode is ON. After commissioning has 
been completed it is important to disable commissioning mode by 
entering the installer menu once again and setting the CD=01 value back   
to CD=00. 

 

NOTE:when in commissioning mode ALL time delays are either OFF or 

reduced to a extremely low value, it is therefore normal to potentially call for 3rd stage 
heating almost instantly 0.5deg below the heating set point.   
If you choose not to use commissioning mode you may see various words and Icons 
flashing in the LCD when ever a time period is in use. For example, the word 

HEAT” 

may flash to indicate heating is required but being held off by the 4 minute anti

cycle 

timer. Or the word 

HEATING” may be flashing to indicate set point has been achieved 

however heating is being held ON by the minimum run timer.   

The golden rule with the A4100 is anything that flashes is a time period overriding what 

would normally be expected to occur; either a function is being held on or off 

momentarily. Please be patient.   

Test fan operation.   

With the thermostat OFF (tap the mode key to show OFF in the LCD). Simply tap the fan 
key to cycle through the available fan speeds. As the LCD changes to show the fan 
speed or fan mode you should here faint 

clicks” as the A4100 internal relays change, 

the equipment fan speed should change accordingly. 

Test heating and cooling (if both fitted).   

Turn the A4100 to Auto season change mode by tapping the mode key until the words 

Heat” and 

Cool” are shown on the LCD.   

Using the temp + or Temp 

  key set the desired temperature a few degrees below the 

ambient temperature. After a few moments you will hear a click and the word 

Heat” will 

change to 

Heating”. Verify that the heating system is on and operating correctly.   

Using the temp + or Temp 

  key set the desired temperature a few degrees above the 

ambient temperature. After a few moments you will hear a click and the word 

Cool” will 

change to 

Cooling”. Verify that the cooling system is on and operating correctly.   

Tap the mode key turn the A4100 OFF. After any necessary timers have expired all 
heating, cooling and fan functions should stop. Verify that the system has shut down. 

NOTE:in HP mode (SW2=ON) it is normal for the reversing valve to remain energised 

after the compressor has stopped. This is done to prevent 

decompression HISS” and 

to limit the wear on the reversing valve. 30 minutes after the last reversing valve use it 

will deenergise to conserve power. 

 

This commissioning of the A4100 is complete. If commissioning mode has been used it 
is important that the function be turned OFF before handover to the user. 
Using the User Manual as a guide set the real time clock and the preferred user 
programme (if applicable). Explain equipment & thermostat operation to the user. 
Commissioning is complete. 

Using Remote Temperature   

Single or multiple room   
air temperature   
sensors can be   
connected to the   
A4100 

TT”  

terminals if temperature   
averaging over a   
larger area is   

desired. Shown are 4 examples of   

commonly used sensor configurations. 
Note 

Either TT=RS (remote sensor) or 

TT=Av (Averaging sensors) value must be 
set in the advanced installer menu for   
these sensors to be used.   
Please note the configuration of RS

01 & 

RS

02 sensors in the examples provided 

above. Other sensor configurations are 
also available. 

When used in Start / Stop    commercial  programmable mode 
(SW6=on SW8=off),the after hours run timer   
can be toggled on or off as required with a   
momentary press key on the remote sensor.   
See figure 14 Left.   
As the A4100 

Auto detects” sensors   

connected to the Switch Override Switch   

TT” terminals, temperature sensors can 
also be switched on and off as required 
by placing a switch in the sensor wiring 
to open circuit the sensor loop. See figure 13 Right.   

Advanced Functions   

Modbus Communications   

The A4100 has integrated Modbus communications capabilities where, using a remote 
PC or building Direct Digital Control (DDC) system may view or adjust any of the A4100 
functions remotely.   
It is not the scope of this manual to provide detail on the communication capability of the 
A4100.  
The communications port of the A4100 has 3   
terminals marked 

A”, 

B” & 

C”. Terminals 

A”  

B” are used for communication, terminal 

C” is   

used as a screen ground to protect the integrity of   
the Acommunication signal. To Network maximum   
of 35 A4100 can be connected to any single hub.   
Each A4100 on the hub must have a unique network address (factory default is 7). 
These settings are adjustable from the advanced installer menu. 

Factory Test Mode   

The A4100 is fitted with a simple factory Test Mode where you can confirm that all relays 
outputs functions and the current configuration of the thermostat.   
Ts=0 Factory Test Function is OFF   
Ts=1 Test current switch configuration. The A4100 will display a unique code that will 
identify the current switch settings.   
Ts=2 The A4100 will cycle each of its relays on then off in an endless loop. 

High and Low balance points   

The A4100 is fitted with both High and Low Balance Point control capability. For these 
functions to operate the Installer setting must be TT=OA (outside air temperature sensor 
fitted), the outside air sensor must be installed and SW1 must be OFF (Single fan speed 
mode).  

High Balance point   

Set the installer menu value 

HB=XX”. When the outside air temperature is above this 

value, second or third stages of heating are held off regardless of the room and set 
temperature. Set this function to prevent the excessive consumption of energy when the 
outside air temperature is warm enough not to require additional heating stages to be 
used.  

Low Balance point   

SW2=on, W3 =EH (Emergency Heat Mode) Set the installer menu value 

LB=XX”. 

When the outside air temperature is below this value the A4100 will automatically switch 
to emergency heat mode when only use the emergency heating system when heating is 
required. If the outside temperature is above this LB=XX value the emergency heat 
mode can be selected manually at anytime with the 

PROG DAY” key.   

Setting up the Heat & Cool Off functions   

To conserve energy, the A4100 can suspend the heating or cooling functions if the 
outside air temperature is within a prescribed installer set range. If the outside air 
temperature is above the HO=XX (heating OFF) value, heating will not be called 
regardless of the room and set temperature. If the outside air temperature is below the 
CO=XX value, cooling will not be called regardless of the room and set temperature. 

Heat” or 

Cool” and the word 

Locked” will flash on the LCD to show that these 

modes have been restricted.   

Adaptive recovery   

 

 

 

 

 

 

 

 

 

 

 

Only available in programmable mode (sw6=on). The adaptive recovery function of the 
A4100 permits the user to program a time that a desired set temperature is required, 
letting the thermostat calculate the most energy efficient time to turn on to achieve the 
desired temperature at the selected time.   
For example, if the user typically returns home at 5:00pm at the end of the work day, 
setting program #3 (if used in residential programmable mode) to 5:00pm the A4100 will 
calculate the most energy efficient time based on set, room temperature and history of 
temperature change to bring on the Equipment to meet the set temperature by 5:00pm.   
Adaptive recovery may also prevent the A4100 from running for a few moments just prior 
to a program change occurs. 

recovery” is shown in the LCD when ever Adaptive 

recovery is being used.   

Specifications 

Input Voltage                                          24VAC 50/60 Hz +/

15%. 

Relay rating                                                                    24VAC @ 1Amp maximum per relay.   
Operating Temperature                                                                            0

50C (32 to 122F).   

Operating                                                                                    RH 0

95% (non condensing).   

Storage Temperature                                        0

65C (32 to 150F).   

Size 113 x 103 x 23mm.                                                                    Display Size 74 x 55mm.   
Temperature Sensor(s)                                                                                    10K NTC type 3. 
Accuracy                                                                                        +/

0.3deg C @ 25 C. (77F)   

Stage Delays                       Minimum temperature change over time method.  
Timed upstage Delay                                                                                            5~90 minutes. 
Anti

cycle Delay                                                                                              Off to 4 minutes.   

Maximum hourly cycles                         Unlimited, 30, 10 or 6. (Installer set) 
Display resolution                                                                                                0.5 deg C (1F).   
Control Range                                                                                                  Off to 38c (100F).   
Outside Air temp display range                                                         

8 ~ +60c (17 ~ 140F).   

Back light Blue EL.                      Backlight life 3,000 hours to half brightness.  
Optimised Start/Stop method     Time to start vs temp differential method 

updating.  

Communications Protocol                                  Modbus 

  contact factory for objects list.   

Fan speeds                       Based on difference between room and set temp. 
Approvals FCC (Part 15) (pending),                                                                              C

tick.  

Warranty                                                                                                                              3 years   
Sensor Reference Table 

K

  24.3 22.0 20.0 18.1 16.2 14.3 13.7 

C  6  8  10 12 14 16 18 
F  42.8 46.4  50  53.6 57.2 60.8 64.4 

K

  12.5 11.4 10.4 10.0 9.57 8.75 8.05 

C  20 22 24 25 26 28 30 
F  68 71.6 75.2 77 78.8 82.4 86 

 

Troubleshooting 

Symptom

 

Suspected Fault

 

Suggested remedy

 

Temperature 

Air from the wall cavity may be 

Plug holes in wall with tape 

leaking into therear of the thermostat 

/ sensor enclosure. 

to prevent leaks 

 

The internally fitted temperature 

sensor is foldedback inside the 

Chameleon and not beingexposed to 

the room air temperature. 

Carefully move the room 
temperaturesensor bead 

so that it is just behind 

thesensor opening in the 

case. 

External heat or cool source such as 
lamps,televisions or drafts from open 

doors affecting the accuracy of 

sensor. 

Move lamps, vents or 

other sources of abnormal 

temperature away from 

sensors 

display seems 

inaccurate

 

Sensor calibration may setting are 

incorrect 

Adjust C1=XX value in 

installer mode to correct 

perceived sensor 

inaccuracy.  

 

“Locked” 

appears on LCD 

and heating or 
cooling will not 

operate.

 

This is not a fault.Outside air temp to 

high to require heating Outside air 

temp to low to require cooling. 

The Ho=XX &/or Co=XX 

value is inhibiting heating 

or cooling calls. Change 

these values in the 

installer menu, 

A4100 incorrectly set to HP mode. 

(A4100 keeps reversing valve 

energised after eating / cooling has 

stopped to limit ecompression noise 

from AC system.) 

Set SW2=OFF and retest 

heating & cooling 

operation. 

Minimum run period has not yet 

expired. Words Heating” or “Cooling 

flash in the LCD 

Sw7 sets minimum run 

period from 2 or 6 

minutes. 

Heating or 

cooling runs in 

dead band. 

Compressor and reversing valve 

wiring crossed in HP mode (sw2=on)

Check W1 & Y1, Y2 for 

correct connections. 

Wall controller 
has no display 

Power failure or faulty A4100 

Check for 24VAC on the 

24 & 24C terminals 

Reversing valve 

remains 

energised after 

heating or 

cooling has 

stopped. 

This is not a fault 

 

The reversing valve 

remains energised after 

the heating/cooling has 

stoped to limit 

decompression hiss. 

Reversing valve will 

deenergise within 2 hours 

of the last call. 

Spanner 

Symbol flashes

on LCD 

This is not a fault Commissioning 

mode enabled. 

Exit commissioning mode 

before handover to user.   

E.Heat or 

E.Heating is 

shown on LCD 

without 

manually 

selecting it. 

This is not a fault. 

LBP reached, outside air 

too cold for reliable 

HP operation. Set LBP 

with the LB=XX value 

in the installer menu, 

The word OFF 

is flashing in the 

LCD. Mode 

button has no 

effect. 

This is not a fault 

TT=Of in advanced 

installer menu. 

Some buttons 

do not appear to 

operate. 

Padlock is show 

on LCD. 

Key board lock is on. 

LC=XX value in advanced 

installer mode set 

the lock values. 

Cannot enter 

heat or cool 

modes 

A4100 thermostat set for Heating or 

cooling only modes 

Heating or cooling mode 

not available on your air 

conditioning system. 

Cannot set 

heating and 

cooling to 

desired value. 

Padlock symbol 

flashes 

This is not a fault. 

HL=XX (heating set point 

limit) and CL=XX (cooling 

set point limit) restrict 

control range.. 

Outside air temperature air sensor 

has failed. 

Check wiring and outside 

air sensor. Replace 

outside air sensor 

Outside Air 

Temp display 

is showing 

dashes  

No outside air sensor fitted. 

Change TT=AO to TT=RS 

in advanced installer 

menu. 

“Heat” or “Cool” 

is flashing in the 
LCD. Heating or 

cooling has not

started. 

This is not a fault. Heating or cooling 

will start shortly. 

Anti cycle delay in 

progress. This can be 

disabled if required for 

commissioning. 

The Fan runs 

on for some 

time after the 

heating or 

cooling stops, 

even when I 

turn the A4100 

OFF. 

This is not a fault.` 

The fan purge mode is set. 

FP=XX value 

A4100 displays 

wrong 

mode (C or F). 

The A4100 can operate in both Deg 

C and Deg F mode as set in installer 

menu. 

Check the CF=XX value 

Can not select 

multiple fan 

speeds  

A4100 set for single fan speed 

Sw=OFF 

Turn SW1 to ON. NOTE, 3 

fan speed mode can only 

be used on single stage 

systems. 

FAN ON

Room

SCHED

CLOCK

SCREEN

SYSTEM

.

COOL

FAN

 

MON

MED

Cool On

Recovery  

PM

HOLD

DAY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reviews: