6.90
6.90
4.50
4.50
4.40
3.05
2.40
2.25
2.05
2.05
8
31-5000755 Rev. 0
ENGLISH
9k
12k
18k
24k
30k
36k
Capacity
Cooling
Btu/h
9000
12000
18000
24000
30000
36000
Heating
Btu/h
8500
13500
20000
27000
34000
40000
Electrical
Power supply
V/Ph/Hz
208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60 208-230/1/60
MCA
A
MOP
A
15
15
15
15
15
15
ESP
in. W.G.
0.3/0.5/0.9
0.3/0.5/0.9
0.3/0.5/0.9
0.3/0.5/0.9
0.3/0.5/0.9
0.3/0.5/0.9
42k
48k
Capacity
Cooling
Btu/h
42000
48000
Heating
Btu/h
46000
54000
Electrical
Power supply V/Ph/Hz
208-230/1/60 208-230/1/60
MCA
A
MOP
A
15
15
ESP
in. W.G.
0.3/0.5/0.9
0.3/0.5/0.9
54k
60k
Capacity
Cooling
Btu/h
54000
60000
Heating
Btu/h
60000
66000
Electrical
Power supply V/Ph/Hz
208-230/1/60 208-230/1/60
MCA
A
MOP
A
15
15
ESP
in. W.G.
0.3/0.5/0.9
0.3/0.5/0.9
Operating Conditions:
Normal operating conditions are listed below
Cooling Dry
Indoor
Max DB: 90ºF (32ºC)
WB: 74ºF (23ºC)
Min
DB: 64ºF (18ºC)
WB:57ºF (14ºC)
Outdoor
Max DB: 115ºF (46ºC)
WB: 74ºF (23ºC)
Min
DB: 23ºF (-5ºC)
Heating
Indoor
Max DB: 80ºF (27ºC)
Min
DB: 59ºF (15ºC)
Outdoor
Max DB: 75ºF (24ºC)
WB: 59ºF (15ºC)
Min
DB: -4ºF (-20ºC)
SPECIFICATIONS