Service Diagnosis
59
Domestic Air Conditioner
˄
A
˅
YES
NO
Yes
Check the indoor mainboard.
No
If the voltage is of a constant
value of 0V DCto5V DC
YES
Measure the voltage between Jumpers 3 and
4 of IC1 on the indoor mainboard with a
multimeter.
The outdoor mainboard is damaged;
Replace them with a new one.
Measure the AC voltage between
positions 1 and 3 on the terminal of
outdoor unit with a multimeter.
If 230VAC is available but 310DC not,
the power module is damaged, replace it
with a new one.
Test the outdoor power supply (230VAC
and +310VDC) with a multimeter.
The outdoor mainboard is damaged; replace
it with a new one.
The indoor mainboard is damaged; replace
it with a new one.
If the value varies between 0 and 80 VAC, the
outdoor mainboard is damaged, replace it
with a new one.
If the value is constant at about 30V, the
indoor mainboard is damaged, replace it with
a new one.
If both 230VAC and 310DC are
available, measure
+12V(from7805) is available.
No
Summary of Contents for HSU24VHG(DB)-G&W
Page 41: ...System Configration...
Page 68: ...67 Removal Procedure...
Page 69: ...68 Removal Procedure...
Page 70: ...69 Removal Procedure...
Page 71: ...Release 70 Removal Procedure...
Page 72: ...71 Removal Procedure...
Page 73: ...3 72 Removal Procedure...
Page 74: ...73 Removal Procedure...
Page 75: ...4 74 Removal Procedure...
Page 76: ...75 Removal Procedure...
Page 77: ...6 76 Removal Procedure...
Page 78: ...77 Removal Procedure...
Page 91: ...90 Domestic air conditioner Step Procedure Points 4 Remove the YDOYH EUDFNHW Removal Procedure...