Domestic Air Conditioner
25
5.2.5.2
˖
TC high temperature-preventing control of the indoor heating unit
˖
Tpg_indoor is the highest value of the effective indoor unit (start it and it is in accord with the running
state).
The indoor heat exchanger sensor tests the temperature of the indoor heat exchanger. If the
temperature is higher than
, decrease the rotate speed of the compressor and do the high
temperature-preventing protection of the indoor heat exchanger; if the temperature of the indoor heat
exchanger is lower than
, recover to the normal control.
TC
The compressor stops
Fgh_t1
ˉ
2
Fgh_t1
N
Decreasing the frequency rapidly
Fgh_t2
Fgh_t2
ˉ
2
P
Decreasing the frequency slowly
Fgh_t3
Fgh_t3
ˉ
2
ˉ
2
ˉ
2
Q
Prohibiting increasing the frequency
Fgh_t4
Fgh_t4
R
Increasing slowly
Fgh_t5
Fgh_t5
Normal
N
˖
Decreasing at the speed of 1HZ/1
second
P
˖
Decreasing at the speed of 1Hz/10
seconds
Q
˖
Continue to keep the last-time instruction cycle
R
˖
Increasing at the speed of 1Hz/10seconds
Remarks: the outdoor unit
5.2.5.3 The control of preventing the overcurrent of the compressor
˖
ƽ
During the starting process of the compressor, if the curren of the compressor is greater than 17A
for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the the power is off.
ƽ
During the starting process of the compressor, if the AC current is greater than 12A, the frequency
of the compressor decreases at the speed of 1HZ/second.
ƽ
During the starting process of the compressor, if the AC current is greater than 10A, the frequency
of the compressor decreases at the speed of 0.1HZ/second.
ƽ
During the starting process of the compressor, if the AC current is greater than 9A, the frequency of
the compressor increases at the prohibited speed.
ƽ
During the starting process of the compressor, if the AC current is greater than 8A, the frequency of
the compressor increases at the speed of no faster than 0.1HZ/second.
Functions and Control
217
198
185
172
159
159
185
°F
°F
°F
°F
°F
°F
°F
Summary of Contents for HSU24VHG(DB)-G&W
Page 41: ...System Configration...
Page 68: ...67 Removal Procedure...
Page 69: ...68 Removal Procedure...
Page 70: ...69 Removal Procedure...
Page 71: ...Release 70 Removal Procedure...
Page 72: ...71 Removal Procedure...
Page 73: ...3 72 Removal Procedure...
Page 74: ...73 Removal Procedure...
Page 75: ...4 74 Removal Procedure...
Page 76: ...75 Removal Procedure...
Page 77: ...6 76 Removal Procedure...
Page 78: ...77 Removal Procedure...
Page 91: ...90 Domestic air conditioner Step Procedure Points 4 Remove the YDOYH EUDFNHW Removal Procedure...