Service Diagnosis
55
Domestic Air Conditioner
7.3.5 The communication fault between IPM and outdoor PCB
Outdoor display
LED1 flash 4 times Indoor Display F3
Method of
Communication is detected by checking the IPM module and the outdoor PCB.
Malfunction
Detection
Malfunction
The outdoor PCB broken leads to communication fault
Decision
The IPM module broken leads to communication fault
Conditions
Supposed
The outdoor PCB is broken
Causes
The IPM module is broken
Ƶ
Communication wiring disconnected
Troubleshooting
* Caution
Be sure to turn off power switch before connect or disconnect connector, or
else parts damage may be occurred.
YES
1) Check whether Terminal CN23 and CN24 on the outdoor mainboard
CN10 and CN11 on IPM module
2) Check whether the connected wire between IPM and outdoor
Are they good?
NO
YES
Electrify the machine again and turn it
on, Check whether the voltage between
1 and 2 of Terminal CN23 is about
DC5V, Check whether the voltage
between2 and 3 of Terminal CN23 is
about DC15V,
Replace the outdoor mainboard with a new one
Replace the outdoor IPM module
with a new one.
NO
Malfunction unsolved
1) Pull out and reinsert the terminals.
2) Replace connected wire
Summary of Contents for HSU24VHG(DB)-G&W
Page 41: ...System Configration...
Page 68: ...67 Removal Procedure...
Page 69: ...68 Removal Procedure...
Page 70: ...69 Removal Procedure...
Page 71: ...Release 70 Removal Procedure...
Page 72: ...71 Removal Procedure...
Page 73: ...3 72 Removal Procedure...
Page 74: ...73 Removal Procedure...
Page 75: ...4 74 Removal Procedure...
Page 76: ...75 Removal Procedure...
Page 77: ...6 76 Removal Procedure...
Page 78: ...77 Removal Procedure...
Page 91: ...90 Domestic air conditioner Step Procedure Points 4 Remove the YDOYH EUDFNHW Removal Procedure...