background image

1. If the supply cord is damaged, it must be replaced by the manufacturer or its

service agent or  a  similar qualified person. The type  of  connecting wire is

H05RN-F or H07RN-F.

2. If the fuse on PC board is broken please change it with the type of 

T. 3.15A/250V.

3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.

5.  A  breaker should be incorporated into fixed wiring. The breaker should be

all-pole switch and the distance between its two contacts should be not less
than 3mm.

3

Outdoor unit

Indoor unit

Connecting wiring :

Power cable

3G1.5mm

2

+1x0.75mm

2

3G1.5mm

2

Outdoor unit

Indoor unit

4 G1.5mm

HSU-09RR03/R2(SDB)

HSU-12RR03/R2(SDB)

Connecting wiring (with fresh function):

5G1.5mm

2

Connecting wiring (without fresh function):

4G1.5mm

2

Power cable: ≥3G1.5mm

2

Indoor unit

Outdoor unit

connection line for
indoor PCB signal

connection line for 

heating exchange

HSU-09RUC03/R2(SDB)

HSU-12RUC03/R2(SDB)

Power cable

3G1.5mm

2

Connecting wiring :

2

Indoor unit

Outdoor unit

4G1.5mm

2

HSU-09RUF03/R2(SDB)

HSU-12RUF03/R2(SDB)

Power cable

3G1.5mm

2

Indoor unit

Outdoor unit

Power cable:     3G1.5mm

2

Connecting wiring(with fresh function):      5G1.5mm

2

Connecting wiring(without fresh function):      4G1.5mm

2

HSU-09RU03/R2(SDB)

Outdoor unit

Indoor unit

A

B

Outdoor unit

Indoor unit

A

B

A

B

Outdoor unit

Indoor unit

Oil trap

Outdoor unit

Install according to

Drawing for the installation of indoor and outdoor units

To bend  a  pipe, give the roundness as large as possible not to crush the pipe ,

ƽ

and the bending radius should be 30 to 40 mm or longer.

Connecting the pipe of gas side first makes working easier.

ƽ

The connection pipe is specialized for R410A.

ƽ

Use the same method on indoor unit. Loosen the screws on

ƽ

terminal block and

insert the plugs fully into terminal block, then tighten the screws.

Insert the cable according to terminal number in the same manner as the indoor
unit.

ƽ

If wiring is not correct, proper operation can not be carried out and controller
may be damaged.

ƽ

Fix the cable with  a  clamp.

ƽ

Installation of Outdoor Unit

Half union

Flare nut

Torque wrench

CAUTION

Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 10m, the function of the unit will be
affected. If the pipe has to be lengthened, the refrigerant should be charged,

according to 20 g/m. But the charge of refrigerant must be conducted by profes-

sional air conditioner engineer. Before adding additional refrigerant, perform air
purging from the refrigerant pipes and indoor unit using  a  vacuum pump,then

Spanner

Forced fastening without careful centering may
damage the threads and cause a leakage of gas.

Max.Elevation: Amax=10m

In case the elevation A is more

than 5m, oil trap shoud be
installed every 5~7m
Max. Length: Bmax=15m

In case the pipe length  B  is

more than 10m, the refrigerant
should be charged, according
to 20 g/m.

Connection of pipes

charge additional refrigerant.

Connection

If the drain-elbow is used, please attach it as figure.

ƽ

Attaching Drain-Elbow (Optional)

Purging Method:To use vacuum pump

Pipe Diameter(ǿ)

Fastening torque

Liquid side6.35mm(1/4")

18N.m

Liquid/Gas side9.52mm(3/8")

42 N.m

Gas side 12.7mm(1/2")

55N.m

Gas side 15.88mm(5/8")

60 N.m

Detach the service port’s cap  of

1.

3-way valve, the valve rod’s cap for 2-way valve

and 3-way’s, connect the service port into the projection of charge hose (Iow)

Note

When connecting the cable, confirm the terminal number of indoor and
outdoor units carefully. If wiring is not correct, proper operation can not

be carried out and will cause defect.

After the cable connection,

ƽ

never fail to fasten the connected cable with the

wiring cover.

HSU-12RU03/R2(SDB)

4G1.5mm

2

3G1.5mm

2

+2x0.75mm

2

(RS model with fresh function):

(RS model without fresh function):

HSU-09HVd03/R2(SDB)
HSU-12HVd03/R2(SDB)
HSU-09RS03/R2(SDB)

HSU-12RS03/R2(SDB)

or

4G1.5mm

2

HSU-18RK03/R2(SDB)

To indoor unit

To outdoor fresh 
     air motor

The connecting method of
 fresh air box signal wire

Signal line: 22AWGx2

For the units with
fresh air function
(for Hvd model)

(Note:Not available for North European Area unit)