Outdoor unit

6.Purging Method:

7

3-way valve

2-way valve
6.35mm(1/4")

12.7mm(1/2")

HSU-12CVY03

HSU-18CVY03

2-way valve
9.52mm(3/8")

3-way valve

15.88mm(5/8")

HSU-22CVY03

Push the air out of the indoor unit

and piping as followes:

(1) Remove the valve cap on 2-way

      valve in outdoor unit.

(2) Loosen by 1/2 turn the flare nut of

     gas pipe, which is conneted to

     3-way valve.

(3) Loosen 2-way valve by 90

o

 using

     hexagon wrench, and after approx.

     10 sec tighten it up. Gas comes out

     through flare nut on wide pipe. If no

     gas is discharged, tighten flare nut

     with specified torque.

(4) Open 2-way and 3-way valves

      using specified torque.

(5) Tighten the caps on the valves

      with specified torque.

Valve rod

Valve cap

7-9

20-25

Tighten torque N.m

When connecting pipe exceeds 5 meters, 16g refrigerant shall be added

per exceeding meter. Charge according to the following list.

Piping length

Additional amount

5m

7m

10m

No need

32g

During this procedure, 50g(18k) or 80g(24k) refrigerant will be discharged in piping.

(This must be strictly controlled within 90

o

 and 10 sec.)

Brand new outdoor unit is charged 50g(18k) or 80g(24k) more refrigerant than regulated weight.

Only for first installation, this extra 50g(18k) or 80g(24k) can be used to purge air in pipes.

Note: When extending piping, air inside piping shall be removed by using external

         refrigerant gas, charge according to the following list.

80g

Summary of Contents for HSU-18CVY03

Page 1: ...n 10cm more than 10cm Adhesive tape Saddle L S with screws Attention must be paid to the rising up of drain hose Arrangement of piping directions Rear left Rear right Left Below Right Connecting elect...

Page 2: ...er on a wall place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened Place which is less affected by rain or direct sunlight and is sufficiently ventilated...

Page 3: ...When the mounting plate is first fixed for the position of wall hole Fix to side bar and lintel a mounting bar Which is separately sold and then fasten the plate to the fixed mounting bar Make a hole...

Page 4: ...aslant from the underside and then put it down perpendicularly Remove terminal cover at right bottom corner of indoor unit then take off wiring cover by removing its screws When connecting the cable a...

Page 5: ...t the cable ends fully into terminal block then tighten the screws Pull the cable slightly to make sure the cables have been properly inserted and tightened After the cable connection never fail to fa...

Page 6: ...pe Diameter Liquid side 6 35mm 1 4 Liquid side 9 52mm 3 8 Fastening torque Drawing for the installation of indoor and outdoor units Insert the cable according to terminal number in the same manner as...

Page 7: ...alves using specified torque 5 Tighten the caps on the valves with specified torque Valve rod Valve cap 7 9 20 25 Tighten torque N m When connecting pipe exceeds 5 meters 16g refrigerant shall be adde...

Page 8: ...pan of the indoor unit and confirm that drainage is carried out surely to outdoor In case that the attached drain hose is in a room please apply heat insulation to it without fail Please kindly expla...

Reviews: