18
31-5000485 Rev. 4
Operating Instructions
This system is designed to provide comfort cooling
at outside temperatures between 50°F (10°C) and
115°F(46°C). Operation outside of this temperature range
may cause unit failure and will void the warranty.
To Operate:
NOTE: Thermostat operation may vary by type and model
used. Please consult the operating manual provided with
the thermostat. The instructions below are generalized
for most models.
1. Move the switch on the thermostat to the Cool
position.
2. Set the desired temperature (between 63-86°F or
17-30°C) on the thermostat. If the room is warmer than
the setting, the unit will turn on and begin to blow cool
air after a few minutes. A hot, humid room or building
may take several hours of continuous operation to
reach the thermostat setting when starting for the first
time or at the beginning of the cooling season.
3. Set the Fan switch on the thermostat to Auto if you
want the fan to run only when cooling is needed, or to
On if you want continuous air circulation.
4. If the space will be unoccupied for four or more hours,
moving the setting to a higher temperature may save
energy. Do not raise the temperature setting by more
than 5 degrees. Changing the temperature over 5
degrees, or turning the unit off can actually cost more.
5. Be sure that furniture or other objects do not block
supply air registers or return air grilles.
IMPORTANT
If the system is turned off, wait at least 3 minutes before
restarting it. This gives the unit time to stabilize. Failure to
do so could cause compressor damage.
Maintenance:
1. Change or clean the air filter monthly, or more often if
conditions require it. Thoroughly dry a washable filter
before re-installing.
2. Contact the installer for factory recommended annual
maintenance.
Final Check
System Test
Please explain to the customer how to operate the system by
using the Owner’s Manual found with the indoor unit.
Check Items for Test Run
No gas leak from linesets?
Are the linesets insulated properly?
Are the connecting wirings of indoor and outdoor firmly
inserted to the terminal block?
Is the connecting wiring of indoor and outdoor fixed?
Is condensate draining correctly?
Is the ground wire securely connected? Is the indoor unit
securely fixed?
Is power source voltage correct according to local code?
Is there any odd noise?
Does the cooling temperature drop between 20-30°F?
Is the room temperature display accurate?
Explaining Operation To the End User
• Using the User Manual, explain to the user how to use
the air conditioner (thermostat, adding/removing the air
filters, cleaning methods, precautions for operation, etc.)
• Review precautions for operation.
• Recommend that the user read the Operating Instructions
carefully.
INSTALLATION INSTRUCTIONS
Summary of Contents for GE UUC112WC Series
Page 11: ...31 5000485 Rev 4 11 INSTALLATION INSTRUCTIONS Wiring cont 24K 30K ...
Page 12: ...12 31 5000485 Rev 4 INSTALLATION INSTRUCTIONS Wiring cont 36K ...
Page 13: ...31 5000485 Rev 4 13 INSTALLATION INSTRUCTIONS Wiring cont 48K ...
Page 33: ...31 5000485 Rev 4 11 INSTRUCTIONS D INSTALLATION Câblage de l unité extérieure 24K 30K ...
Page 34: ...12 31 5000485 Rev 4 INSTRUCTIONS D INSTALLATION Câblage de l unité extérieure 36K ...
Page 35: ...31 5000485 Rev 4 13 INSTRUCTIONS D INSTALLATION Câblage de l unité extérieure 48K ...
Page 55: ...31 5000485 Rev 4 11 INSTRUCCIONES DE INSTALACIÓN Cableado de la Unidad Exterior 24K 30K ...
Page 56: ...12 31 5000485 Rev 4 INSTRUCCIONES DE INSTALACIÓN Cableado de la Unidad Exterior 36K ...
Page 57: ...31 5000485 Rev 4 13 INSTRUCCIONES DE INSTALACIÓN Cableado de la Unidad Exterior 48K ...