31-5000485 Rev. 4
15
Pairing with A-coils
(cont)
When installers pair 14 SEER Side-discharge outdoor with a pre-existing AHU
1) Ensure the 3rd party AHU is a R410a, TXV, tonnage to tonnage matched AHU
2) Ensure to install a bi-flow Filter Dryer (Field supplied) in liquid line
3) Ensure the lineset size matches 14 SEER Side-discharge outdoor as stated in the outdoor unit installation manual (If
existing lineset size is different new lineset must be installed).
4) Ensure proper airflow
5) Ensure existing linesets are cleaned by flushing if re-used.
6) Ensure to install a bi-flow Filter Dryer (Field supplied) in gas line
7) Ensure to triple evacuation the pre-existing coil
If installation guidelines and procedures are followed for each type of application above, the outdoor unit will qualify for
a Limited Standard Base Warranty (i.e., 5-year parts and compressor), subject to the other limitations in the standard
warranty document.
Model Number
UUC112WCD
A
UUC118WCD
A
UUC118WCDB
A
UUC124WCD
A
UUC124WCDB
A
UUC130WCD
A
UUC130WCDB
A
UUC136WCD
A
UUC136WCDB
A
UUC148WCD
A
Factory Charge
Oz
49.4
75.84
81.20
97.00
100.60
116.40
119.90
123.50
127.00
141.10
Liquid O.D. (Std)
Inch 1/4"
1/4"
1/4"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
3/8"
Suction O.D.(Std)
Inch 1/2"
1/2"
1/2"
5/8"
5/8"
5/8"
3/4"
3/4"
3/4"
3/4"
Max. Refrigerant Line
between Indoor and
Outdoor
Ft
66
66
66
66
66
66
66
66
66
66
Max. Refrigerant Line
elevation between
Indoor and Outdoor
Ft
33
33
33
33
33
33
33
33
33
33
Additional charge
Additional charge
if refrigerant line
exceeding 25 ft
oz/
FT
0.16
0.16
0.16
0.32
0.32
0.32
0.32
0.32
0.32
0.32
Memo: Colored columns are paired with ADP A-coils
Note: Factory charge for UUC124WCDBA is 100.6 oz and UUC130WCDBA is 119.9 oz.
INSTALLATION INSTRUCTIONS
Summary of Contents for GE UUC112WC Series
Page 11: ...31 5000485 Rev 4 11 INSTALLATION INSTRUCTIONS Wiring cont 24K 30K ...
Page 12: ...12 31 5000485 Rev 4 INSTALLATION INSTRUCTIONS Wiring cont 36K ...
Page 13: ...31 5000485 Rev 4 13 INSTALLATION INSTRUCTIONS Wiring cont 48K ...
Page 33: ...31 5000485 Rev 4 11 INSTRUCTIONS D INSTALLATION Câblage de l unité extérieure 24K 30K ...
Page 34: ...12 31 5000485 Rev 4 INSTRUCTIONS D INSTALLATION Câblage de l unité extérieure 36K ...
Page 35: ...31 5000485 Rev 4 13 INSTRUCTIONS D INSTALLATION Câblage de l unité extérieure 48K ...
Page 55: ...31 5000485 Rev 4 11 INSTRUCCIONES DE INSTALACIÓN Cableado de la Unidad Exterior 24K 30K ...
Page 56: ...12 31 5000485 Rev 4 INSTRUCCIONES DE INSTALACIÓN Cableado de la Unidad Exterior 36K ...
Page 57: ...31 5000485 Rev 4 13 INSTRUCCIONES DE INSTALACIÓN Cableado de la Unidad Exterior 48K ...