Page 13
31-5000734 Rev. 0
Code
Diagnostic Codes / Status of Equipment
Action Required to Clear and Recover
E200
Hard Lock out - Rollout circuit open or previously
open
Correct cause of rollout trip or replace flame rollout
switch. Test furnace operation. Cleared after fault
recovered.
E201
Indoor blower/communication failure - Unable to
communicate with blower motor
Indoor blower communication failure including power
outage. Lost communication with indoor blower motor.
Possible causes: motor not powered, loose wiring.
Problem may be on control or motor side. Cleared after
fault recovered.
E202
Indoor blower motor mis-match - indoor motor
horsepower does not match unit capacity
Incorrect appliance capacity code selected. Check for
proper configuring under Unit Size Code for Furnace/
Air Hander on configuration guide or in installation
instructions. Cleared after the correct match is detected
following a reset. (Remove thermostat from system while
applying power and reprogramming)
E203
Appliance capacity size is NOT programmed.
Invalid unit codes. Refer to configuration flow
chart.
No appliance capacity code selected. Check for proper
configuring under Unit Size Codes for Furnace on
configuration guide or in installation instruction. Critical
Alert Cleared after valid unit code is read following a
reset (remove thermostat from system while applying
power and reprogramming)
E204
Gas valve mis-wired
Check gas valve operation and wiring. Clears when
repaired
E205
Gas valve control relay contact shorted
Check wiring on control and gas valve. If wiring is correct
replace control.
E206
Gas valve second-stage relay failure
Furnace will operate on 1st stage for remainder of the
heating demand. Will clear after fault recovered. If unable
to operate 2nd stage replace control.
E207
Hot surface igniter sensed open - Refer to
troubleshooting
Measure resistance of hot surface igniter. Replace
if open or not within specified range found in 10M.
Resumes normal operation after fault is cleared.
E223
Low pressure switch failed open
Check pressure(inches W.C) of low pressure switch
closing on heat call. Measure operating pressure (inches
w.c.). Inspect vent and combustion air inducer for correct
operation and restriction. Resumes normal operation
after fault is cleared.
E224
Low pressure switch failed closed -Refer to
troubleshooting
Check pressure(inches W.C) of low pressure switch
closing on heat call. Measure operating pressure (inches
w.c.). Inspect vent and combustion air inducer for correct
operation and restriction. Resumes normal operation
after fault is cleared.
E225
High pressure switch failed open -Refer to
troubleshooting
Check pressure(inches W.C) of high pressure switch
closing on heat call. Measure operating pressure (inches
w.c. Inspect vent and combustion air inducer for correct
operation and restriction Resumes normal operation after
fault is cleared.
E226
High pressure switch failed closed -Refer to
troubleshooting
Check operation of high pressure closing on heat call.
Measure operating pressure (inches w.c.). Inspect vent
and combustion air inducer for correct operation and
restriction. Resumes normal operation after fault is
cleared.