Troubleshooting
】
Fault
Analysis
Maintenance Measures
1. compressor fails to start
1. Machine storehouse wiring connector plugs s are
damaged
Change the connector plugs
2. Bas wire contact
Check contact and make in good
condition.
3. Display panel connection failure
Checking if it is due to bad
connection, otherwise, change it.
4. Relay, start capacitor or heat protector is
damaged
Change the part.
5. Compressor fault
Change the compressor
6
. User’s voltage is too low
Add a manostat
2.Fan does not rotate
1. Fan wiring is loose
Checking the wiring
2. Fan blades are blocked by foreign matters
Checking and clean them
3. Fan is damaged
Change parts
3.High temperature in
cabinet
1. The temperature setting of outage is too high.
Re-set computer board
2. Refrigerant leaks.
Find leak location and make repair
welding. Infuse refrigerant again.
3.Temperature probe is damaged
Change parts
4. Capillary tube or system is blocked by dirt\ greasy
Clean the capillary tube or change
filter.
5. High ambient temperature
Turn on air-conditioner
,
reduce
ambient temperature.
6. Condenser blockage
Clean condenser
4.Display board displays
F1
1. Temperature probe short circuit or disconnect
Checking the temperature probe
2.No temperature probe
Install a temperature probe
Summary of Contents for DW-25L92
Page 6: ...6 33 Product appearance ...
Page 7: ...7 33 ...
Page 8: ...8 33 ...
Page 9: ...9 33 Dimensions DW 25 L92 DW 40L92 DW 40L188 DW 25L300 DW 40L262 ...
Page 10: ...10 33 Product Specifications ...
Page 11: ...11 33 ...
Page 19: ...19 33 System Schematic Diagram ...
Page 20: ...20 33 System Circuit Diagram ...
Page 24: ...24 33 product nameplate ...
Page 25: ...25 33 ...