(2)  Piping size

Gas pipe

15.88x1.0mm

Install the removed flare nuts to
the pipes to be connected, then
flare the pipes.

Liquid pipe

Gas pipe

9.52x0.8mm

19.05x1.0mm

Liquid pipe

9.52x0.8mm

(3) Limitations for one way piping length and vertical height difference.

Precautions for refrigerant piping

Do not twist or crush piping.
Be sure that no dust is mixed in piping.
Bend piping with as wide angle as possible.
Keep insulating both gas and liquid piping.
Check flare-connected area for gas leakage.

Connecting method (indoor unit)
Apply refrigerant oil at half union as large and flare nut.
To bend a pipe, give the roundness as possible not to crush
the pipe.
When connecting pipe, hold the pipe centre to centre then
screw nut on by hand, refer to Fig.
Be careful not to let foreign matters, such as sands enter
the pipe.

(4) Piping connection

Forced fastening without centering
may damage the threads and cause a
gas leakage.

Gas pipe

12.7x1.0mm

Liquid pipe

6.35x0.8mm

Pipe dia

Fastening torque

Liquid pipe 6.35mm

Gas pipe 15.88mm

Liquid pipe 9.52mm

Gas pipe 19.05mm

14.2-17.2N.m

61.8-75.4N.m

32.7-39.9N.m

97.2-118.6N.m

Gas pipe 12.7mm

49.5-60.3N.m

AU36NAIEAA
AU362AIEAA

AU48NAIEAA
AU60NAIEAA

Refrigerant piping

8

90+0.5

AU242AGEAA
AU282AHEAA
AU28NAHEAA

Installation Procedure

AU182AEEAA

Model

One way piping length

     Vertical  height difference

(between indoor  and outdoor)

less than 30 m

AU362AIEAA   AU36NAIEAA
AU48NAIEAA  AU60NAIEAA

AU242AGEAA  AU282AHEAA
AU28NAHEAA

less than 50 m

less than 15 m

less than 30 m

AU182AEEAA

less than 20 m

less than 10 m

Summary of Contents for AU182AEEAA

Page 1: ...ad this manual carefully Please keep this manual properly for future use CONTENTS Name of Parts 1 Safety Cautions 2 3 Installation Procedure 4 13 INSTALLATION INSTRUCTIONS No 0010577959 D AU242AGEAA A...

Page 2: ...unit Compressor AU36NAIEAA AU362AIEAA AU48NAIEAA AU60NAIEAA AU242AGEAA AU182AEEAA Air inlet Air outlet Inside of unit Compressor Air inlet Air outlet Inside of unit Compressor Air inlet Air outlet In...

Page 3: ...autions Carefully read the following information in order to operate the airconditioner correctly WARNING If any abnormal phenomena is found e g smell of firing please cut off the power supply immedia...

Page 4: ...tioner Incorrect installation may cause water leak electrical shock and fire hazard Call the dealer to take measures to prevent the refrigerant from leaking If conditioner is installed in a small room...

Page 5: ...b the neighborhood Place where there is not heavy snowfall in the winter time Place where obstacles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a st...

Page 6: ...HEAA Install the unit so that the angle of inclination must be less than 3 degrees Note 1 Give enough room for the concrete foundation to fix by anchor bolts 2 Place the concrete foundation deep enoug...

Page 7: ...ion Procedure AU182AEEAA AU282AHEAA AU28NAHEAA AU242AGEAA 730 630 308 335 Power Wiring Terminal Power Wiring Distribution Hole 860 Power Wiring Terminal Power Wiring Distribution Hole 25 780 640 500 2...

Page 8: ...id pipe Flare connection Indoor unit Flare connection 3 way stop valve Outdoor unit 3 way stop valve Gas pipe Liquid pipe Flare connection Indoor unit Flare connection 2 way stop valve AU362AIEAAAU36N...

Page 9: ...pe hold the pipe centre to centre then screw nut on by hand refer to Fig Be careful not to let foreign matters such as sands enter the pipe 4 Piping connection Forced fastening without centering may d...

Page 10: ...ll in close state In order to prevent the nitrogen entering the circulation system of outdoor unit tighten the valve rod before giving pressure both gas and liquid valve rods Outdoor Completely tighte...

Page 11: ...remove the air inside the system After air tightness test and discharging all the nitrogen connect the vacuum pump as the following figure shown Refrigerant piping 10 When the total length L of the t...

Page 12: ...o contacts should be no less 3 mm If the supply cord is damaged it must be replaced by the manufacturer or its service agent or a similar qualified person If the fuse on PC board is broken please chan...

Page 13: ...on the side panel WARNING DO NOT CONNECT THE NEUTRAL WIRE TO OR PHASE INTERCONNECTING WIRES MUST BE WIRED ACCORDING TO FIG 1 FIG 2 FIG 3 INCORRECT WIRING CAUSE EQUIPMENT DAMAGE N R S T Installation Pr...

Page 14: ...abnormal Temperature protection malfunction 0D Power LED flashes 13 times Drainage system malfunction 08 Power LED flashes 10 times 0B Power LED flashes 11 times Alarm of exterior annunciator 7 Troub...

Page 15: ...HAIER GROUP Qingdao Haier Air Conditioner Electric Co Ltd Address Haier Garden Qianwangang Road Economic Development Zone Qingdao Shandong 266500 P R China Web Site http www haier com...

Reviews: